  1. Replies
    6
    Views
    265

    So depending on what the LAN setup was the new...

    So depending on what the LAN setup was the new network will likely be on a different subnet from where the controllers are. BACnet BBMD and/or Foreign Device may need to be updated.
  2. Replies
    6
    Views
    265

    I'm not familiar with Envision but in this...

    I'm not familiar with Envision but in this industry seems like most software is tied to hardware somehow. I'd say you found the issue with that USB copier, might help if you had the original key too....
  3. Replies
    168
    Views
    10,494

    Still applicable; https://xkcd.com/927/ I...

    Still applicable; https://xkcd.com/927/

    I don't see a good way to get everyone on board with one thing. Too many conflicting interests.
  4. Replies
    168
    Views
    10,494

    Seriously need to work on marketing there. We...

    Seriously need to work on marketing there. We fight in every way we can against becoming a commodity. This is a value add but in competition with what OEMs are already doing.
  5. It is set individually for each user, that's why...

    It is set individually for each user, that's why it's there.
  6. Replies
    9
    Views
    461

    I've played around with it and it works but...

    I've played around with it and it works but haven't had a calling to use the data.

    I do know from other apps that a paid weather solution gets much better data. One of those many areas they have...
  7. Replies
    3
    Views
    265

    Right, export table for exposing those points to...

    Right, export table for exposing those points to ALC.

    If you pay attention to your folder names and automatically creating the BACnet point names in the export table things can get really slick...
  8. Replies
    9
    Views
    461

    I'm sure many do. ALC can pull in several weather...

    I'm sure many do. ALC can pull in several weather sources through a paid addon and you can utilize that in about any way you want.

    What system are you dealing with?
  9. Thread: EasyIO FT04

    by MaxBurn
    Replies
    31
    Views
    2,206

    I got the email the 14th.

    I got the email the 14th.
  10. Thread: EasyIO FT04

    by MaxBurn
    Replies
    31
    Views
    2,206

    Just got this email, looks like it is obtainable...

    Just got this email, looks like it is obtainable now;
  11. What is the jar file name? I had a similar...

    What is the jar file name? I had a similar experience with the 'asd.jar' and current 'ibmsAsd.jar'. In talks with maxline they did have a newer version of the older driver name that I was able to...
  12. Replies
    3
    Views
    270

    I think all the points you need are exposed to...

    I think all the points you need are exposed to that third party driver but the likelyhood they are mapped is pretty low. You could likely pull them all in via discovery and do what you need to do...
  13. Thanks, that also explains why I couldn't find...

    Thanks, that also explains why I couldn't find anything with search.

    Edit, you wouldn't happen to have one with all the normal system alarms in it would you?
  14. Thread: NEWS

    by MaxBurn
    Replies
    27
    Views
    1,418

    Huh, my money was on Schneider.

    Huh, my money was on Schneider.
  15. Need old cmnetalerttext.properties file from ALC

    Does anyone have an old legacy alarm file that resolves the legacy alert ID's (A1, A2 etc) to the alarm text for a WebCTRL system? I believe it was named cmnetalerttext.properties, I thought it lived...
  16. Replies
    15
    Views
    1,373

    During my short time serving on a condo board I...

    During my short time serving on a condo board I learned that if you have ice dams that big you have a problem with insulation and/or attic vents which are a combination of soffit and ridge vents....
  17. Replies
    2
    Views
    350

    Both jaces need unique device ID's and MACs that...

    Both jaces need unique device ID's and MACs that do not collide on the MS/TP trunk.

    At least one needs routing turned off to avoid a circular network.

    Trunk network number is the same on both.
  18. Replies
    6
    Views
    389

    We use a USB-K to change IP in the LGR. Pretty...

    We use a USB-K to change IP in the LGR. Pretty sure you can use any RS485 dongle and attach it to the Rnet port to accomplish the same thing.

    Disconnect anything attached to Rnet port and S2...
  19. Replies
    7
    Views
    538

    I'm not sure but I don't think the NAE is a...

    I'm not sure but I don't think the NAE is a BACnet router, or maybe that feature isn't turned on. If it can't be a router I don't see that it needs to go away but you will have to add a BACnet...
  20. Replies
    2
    Views
    320

    The issue is that EnOcean is a short range...

    The issue is that EnOcean is a short range protocol, 60 feet tops generally in a building or two or three walls. So you need a bunch of receivers and a jace driver and receiver would be super...
  21. Replies
    1
    Views
    198

    Huh, that thing sure looks a lot like a EasyIO...

    Huh, that thing sure looks a lot like a EasyIO device. Check some of the EasyIO default IPs.
  22. As a lynxspring dealer are we allowed to have...

    As a lynxspring dealer are we allowed to have this? I know no one in my company has this now. Would like to have access, I know I need to email licensing every month or so to change something.
  23. Water source HP? Is there a point indicating loop...

    Water source HP? Is there a point indicating loop water good?
  24. Replies
    7
    Views
    538

    FC = Field Controller. Pretty sure it's just...

    FC = Field Controller. Pretty sure it's just MS/TP.

    https://cgproducts.johnsoncontrols.com/MET_PDF/12011034.pdf
  25. Replies
    19
    Views
    1,571

    They shipped it with the COV threshold defaulting...

    They shipped it with the COV threshold defaulting to 0? I've dealt with plenty of Carel sytle devices, plenty in greenheck and never noticed that. Good to know.

    I've seen their software to set...
  26. Replies
    3
    Views
    282

    Sounds like another one of those yes it's...

    Sounds like another one of those yes it's possible but it's going to take more time than doing it manually?

    The next generation of ALC integration will make this pretty easy though, can't wait.
  27. Replies
    16
    Views
    921

    You sound like one of those super rare master...

    You sound like one of those super rare master systems integrators. Sounds like a win with things running that smoothly.
  28. Take the file you found and send it to virus...

    Take the file you found and send it to virus total. Odds are its fine,AV just doesn't like how it arrived on your machine. Maybe have VT test the rest of the stuff you found too.
  29. You might measure OA flow but the amount of...

    You might measure OA flow but the amount of bypass flow nobody cares about.

    The VAV is a variable volume and it needs a fairly stable air pressure to be able to have time to react and control the...
  30. Did you get a docComFour.pdf with your driver? It...

    Did you get a docComFour.pdf with your driver? It won't help with specific point questions like this though. Reach out through your vendor and see if you have the latest driver and see if they can...
  31. Replies
    16
    Views
    921

    That's actually something I'd like to read more...

    That's actually something I'd like to read more on, what should you do with the supervisor? Best practices and standards etc.

    If I had a AAON VAV RTU with factory jace in it and another jace with...
  32. Replies
    16
    Views
    921

    I'm sure it is a reason why these are the sites...

    I'm sure it is a reason why these are the sites I'm seeing.

    Another thing I just thought of is if they had any turnover they might not even know they have a supervisor somewhere.
  33. Replies
    5
    Views
    436

    Is this something newer than these:...

    Is this something newer than these:
    NSTV_V2.2_ZIP.zip
    FTDIDriverV2.12.26_UTCSigned.zip

    If so I would like to get a copy.
  34. Replies
    16
    Views
    921

    No supervisor, is this normal?

    I can't tell you how many jobs we've been invited into that are a mess and consist of multiple jaces running different versions in the same building sometimes and mostly there is nothing tying the...
  35. So four times a second, is that going to overload...

    So four times a second, is that going to overload any pages that take longer than a quarter second to load?
  36. Replies
    4
    Views
    303

    Going to take a wild guess and say ux is for pix,...

    Going to take a wild guess and say ux is for pix, wb is the palettes and programs though rt contents looks more like that.

    I don't think you are supposed to do those one at a time, load all or...
  37. In ALC the schedule object has a locked value for...

    In ALC the schedule object has a locked value for occ/unocc. Can you find that property in BACnet? Also check it in iVU and see if it is locked. Not sure what you are looking at in the discovery...
  38. They should. Any way into their network they...

    They should. Any way into their network they don't control is a problem.

    When talking to IT about BACnet routers always use both words, dropping a "router" on their network will lead to some...
  39. Replies
    36
    Views
    1,586

    Are you referring to the "Applications...

    Are you referring to the "Applications (Edge-Centric)" section? Is there more elsewhere?
  40. Replies
    25
    Views
    1,032

    Thinking back to the ones I've set up, yes most...

    Thinking back to the ones I've set up, yes most do seem to have that. A VFD and that Verris should be all that is necessary. We never do it that way though, we always have our controller in the...
  41. Replies
    6
    Views
    463

    What that communicates to me is they were clearly...

    What that communicates to me is they were clearly confident that they could not execute that type of live counting in a robust enough manner to prevent cheating on licensing. Anything that might...
  42. Replies
    25
    Views
    1,294

    Depends on who you work for and the niche you can...

    Depends on who you work for and the niche you can fit in to. Of the things you list the only things I don't get are that amount of paid vacation and that many holidays. In general I only take...
  43. Replies
    36
    Views
    1,586

    Are those Inputs off of the physical IO pallette?...

    Are those Inputs off of the physical IO pallette? Set up to read a point? That fault state doesn't look right. Not sure what it is named.

    Also can't run a digital low temp right into the CHW valve...
  44. Replies
    36
    Views
    1,586

    They are coming out with unitary and VAV control...

    They are coming out with unitary and VAV control lines so I believe part of that will be some templates to run those modules at a very minimum. Soon(TM).
  45. What line of controls?

    What line of controls?
  46. Replies
    36
    Views
    1,586

    Isn't there some new tridium thing coming out...

    Isn't there some new tridium thing coming out that boots in seconds and starts controlling while the station is still starting? I saw a demo of it and can't remember what it was called. I do remember...
  47. Replies
    24
    Views
    1,809

    Zero. I'm just of the opinion it's easier to...

    Zero. I'm just of the opinion it's easier to teach HVAC to a CS guy rather than the other way around, or better yet team the two up.
  48. There's a ALC dealer in Honolulu.

    There's a ALC dealer in Honolulu.
  49. Thus the Jace for each building/campus...

    Thus the Jace for each building/campus suggestion? Looking at a mess it starts making sense.

    Might be that a balance could be struck between the two, pull the organized parts up to super and cover...
  50. Yeah, that will be a pain and time waster....

    Yeah, that will be a pain and time waster. Understood.