Search:

Type: Posts; User: simux

Page 1 of 13 1 2 3 4

Search: Search took 0.02 seconds.

  1. Replies
    2
    Views
    182

    Thermal Well Sensor Holder

    I need to add some sensors to our system. I already have the sensors and was going to go with the 36P622 from Johnson Controls. Unfortunately they wanted $80.00 each. I just want something that can...
  2. Thread: Delta DSC-1616

    by simux
    Replies
    2
    Views
    363

    Fixed

    It was our IT department. The port our system was on was changed and it blocked the controller.
  3. Thread: Delta DSC-1616

    by simux
    Replies
    2
    Views
    363

    Delta DSC-1616

    I have a Delta DSC-1616 and it will not come online. A few questions; 1. Does it have an Ethernet address 2. Is there a way to figure out the ethernet address 3. What does the red scan light mean...
  4. LCT

    The LCT program exists at the supervisory front end level.
  5. You can accomplish a reset using LCT.

    You can accomplish a reset using LCT.
  6. Replies
    3
    Views
    504

    Johnson Controls CVM VAV Controller

    How do I tighten the temperature control up on these new controllers. Basically if the setpoint is 70 F, it sets cooling at 72 F and Heating at 68 F.
  7. Controllers

    Back when I started with controls i would set up a trainer in my garage. Basically build a complete system and practice writing programs, graphics, and unique situations.
  8. Replies
    5
    Views
    447

    Control Systems

    Are you still able to create a control system and use LCT?
  9. Replies
    5
    Views
    447

    Johnson Controls MUI

    What functionality do you lose with MUI. For example LCT etc...
  10. Replies
    6
    Views
    763

    Shielded Cable

    Always utilize shielded cable and properly terminate the ground.
  11. Replies
    5
    Views
    587

    I would calibrate the thermostat to bring the...

    I would calibrate the thermostat to bring the heat valve on fully first, then fire the fan as sort of a second stage.
  12. Replies
    10
    Views
    644

    I'm going over to check that out today. Thanks

    I'm going over to check that out today. Thanks
  13. Replies
    10
    Views
    644

    Either

    It causes the issue whether or not the network is plugged in.
  14. Replies
    10
    Views
    644

    Bacnet MS/TP Module

    Bacnet MS/TP Module
  15. Replies
    5
    Views
    485

    Pretty sure you have to purchase from Johnson...

    Pretty sure you have to purchase from Johnson Controls.
  16. Replies
    10
    Views
    644

    Daikin Chiller Microtech III

    Having issues with a Bacnet communication module for a Daikin Microtech III (MT3006) . The original condition is the controller goes offline and basically shuts down the controller display. If we...
  17. Thread: Trane UC800

    by simux
    Replies
    3
    Views
    772

    I think I found the issue. Although we were...

    I think I found the issue. Although we were switching the occupancy switch BI of the UC800 on the Trane DX unit, the Occupancy BV point was not releasing. Apparently Metasys had take control of the...
  18. Thread: Control Acronyms

    by simux
    Replies
    35
    Views
    8,748

    LOM Lack of Maintenance BFH Big F@%king Hammer

    LOM Lack of Maintenance
    BFH Big F@%king Hammer
  19. Thread: Trane UC800

    by simux
    Replies
    3
    Views
    772

    Trane UC800

    Have a Trane Unit with a UC800 BacNet Controller. The unit runs with the BAS occupancy switch open??? I can see the occupancy switch inside the controller switch with no impact on whether the unit...
  20. Thread: JCI CCT

    by simux
    Replies
    2
    Views
    462

    My bad, didn't run as administrator!!!!

    My bad, didn't run as administrator!!!!
  21. Thread: JCI CCT

    by simux
    Replies
    2
    Views
    462

    JCI CCT

    I get an alert when I try to access Johnson Controls CCT; Please select a different device, or a different connection point to access this device. What is causing this issue?
  22. Replies
    4
    Views
    461

    Johnson Controls Network Thermostat

    How do you lock out the setpoint on a NSB8BHN240-0 Network Thermostat.
  23. Replies
    15
    Views
    1,492

    AHU Program into UNT

    I've actually put a AHU program into a UNT. It involved changing the type back to a UNT. I have the directions somewhere if you need them.
  24. Thread: Metasys Freezes

    by simux
    Replies
    4
    Views
    913

    I looked at the computers that worked fine and...

    I looked at the computers that worked fine and the ones that freeze and there was one difference. The computers that freeze had Silverlight installed. I uninstalled Launcher and Silverlight. Then I...
  25. Thread: Metasys Freezes

    by simux
    Replies
    4
    Views
    913

    Metasys Freezes

    The Metasys SMTP freezes when you try to load from computers on the Network. If I connect through the Network with my laptop it works just fine. It works just fine from the server (2012). It...
  26. Replies
    23
    Views
    2,579

    Curious to see where this project went and all. I...

    Curious to see where this project went and all. I worked at a Air Force Hospital with DCMs, which of course you cant take directly to NAE's. Against my advice they put in NIE's as integrators and...
  27. Replies
    8
    Views
    970

    Pretty much time to upgrade if you want to...

    Pretty much time to upgrade if you want to migrate to MUI
  28. Replies
    8
    Views
    1,686

    OrCA View or Intelliweb

    So I have a choice between ORCA View for Windows 10 and Intelliweb, we have a small system with about 120 points. Anyways I have a few questions. 1. Does Intelliweb support GCL+ programming? 2. Is...
  29. Replies
    8
    Views
    1,686

    Any issues with the upgrade?

    Any issues with the upgrade?
  30. Replies
    8
    Views
    1,686

    Delta Orca View 3.4

    Will the Delta Control System ORCAview 3.4 work with Windows 10 64 Bit?
  31. Replies
    2
    Views
    1,452

    Never mind I found the manual and suddenly my...

    Never mind I found the manual and suddenly my memory came back LOL
  32. Replies
    2
    Views
    1,452

    Delta Orca View Back Up

    Was shown once a few years ago how to perform a back up. Can't quite figure out how to back up the system. Help
  33. Replies
    21
    Views
    2,455

    Direct Connect

    When I worked at Johnson Controls, quite a few of my counterparts had a set up just like the one I stated. I totally agree if you use a direct connect wrong that could cause some issues. Of course in...
  34. Replies
    21
    Views
    2,455

    Direct N-2 Buss Connect Cable Direct N-2 Buss...

    Direct N-2 Buss Connect Cable
    Direct N-2 Buss Connect Cable

    N-2 connect cable

    1. (Serial Port Connector. 5 to N2+, 2 to N2-, and 3 to ref, with a 470 ohm resistor between 2 and 5.

    2....
  35. Replies
    28
    Views
    3,550

    The DX FAC Adapter can be installed right on the...

    The DX FAC Adapter can be installed right on the DX-9100 base. You can make this device N-2 or BaCnet protocal. Just an idea.
  36. Replies
    3
    Views
    910

    Thanks JCIman, I'll give the network tolerance...

    Thanks JCIman, I'll give the network tolerance setting a try.
  37. Replies
    3
    Views
    910

    NAE offline Online

    A few times a day our NAE goes offline and back online for a few seconds at a time. How do I delay this offline nuisance alarm?
  38. Replies
    13
    Views
    5,438

    You can always create the processes in JC Basic.

    You can always create the processes in JC Basic.
  39. Replies
    13
    Views
    5,438

    Macro Files? Not sure of the files you speal of...

    Macro Files? Not sure of the files you speal of and all!!!
  40. Replies
    28
    Views
    3,550

    The DCM's we had in the hospital had every slot...

    The DCM's we had in the hospital had every slot filled and the number of wires in the panel was staggering.
  41. Replies
    28
    Views
    3,550

    DCM's

    I use to work at a hospital that had DCM's at every mechanical area. I think like 10 or so of them. The boss was so proud to have sold like 12 NAE's to replace the NCM's. I was like you know the...
  42. Replies
    4
    Views
    1,468

    What type of field controllers do you have? The...

    What type of field controllers do you have? The FEC controllers can have quite a bit of logic programmed inside the controllers. I wrote a Outside Air Reset of Discharge Air with a Return Air trim....
  43. Replies
    3
    Views
    814

    Delta Orca View Security Vulnerabilities

    We have a Delta Orca View system and was wondering what security vulnerabilities the system might have. I know our system hasn't been touched in years and was hoping someone might have some inside...
  44. Replies
    64
    Views
    15,775

    No worries, use to teach pneumatic controls back...

    No worries, use to teach pneumatic controls back in the day.
  45. Replies
    11
    Views
    2,002

    Back in the day we would use pneumatic step...

    Back in the day we would use pneumatic step controllers. It was basically a damper actuator that extended and made electric switches depending on where they were adjusted within the stroke of the...
  46. Replies
    7
    Views
    1,318

    Still not sure which type sensors the older Delta...

    Still not sure which type sensors the older Delta Controllers use.
  47. Replies
    7
    Views
    1,318

    Delta Controls Sensor Type

    We have an old Delta System with Orca View. When I go to add a sensor it gives me an option of 10K with a range of -35 to 240. Is this sensor a Type II or Type III. Thanks
  48. Thread: Older MS-FEC2610

    by simux
    Replies
    2
    Views
    680

    Thanks man.

    Thanks man.
  49. Thread: Older MS-FEC2610

    by simux
    Replies
    2
    Views
    680

    Older MS-FEC2610

    Thinking of purchasing an older MS-FEC2610-0 to practice with and all. Any concerns with revisions?
  50. Hopefully you have an old 32 bit windows XP...

    Hopefully you have an old 32 bit windows XP computer with HVACPRO loaded and a CVT Pro or direct connect cable. Retired Air Force Controls
Results 1 to 50 of 625