Search:

Type: Posts; User: sammybear

Search: Search took 0.02 seconds.

  1. Could I possibly get a copy of this as well? We...

    Could I possibly get a copy of this as well? We do mainly work with JCI products, so this would help a ton.
  2. Replies
    24
    Views
    10,208

    You want to use the one that has the "E" in...

    You want to use the one that has the "E" in front, not the "W"

    Map-[last 6 digits on the E mac address]
  3. After you and orion's email I believe I am and...

    After you and orion's email I believe I am and fine for now. I should have quite a bit to work with for what info I need.

    Thanks again you two.
  4. Awesome, thanks for the help. My plan is to make...

    Awesome, thanks for the help. My plan is to make something similar to what Optigo has, but it will allow for more protocol types. I hope to get it working with modbus and N2 at a bare minimum.

    I...
  5. Does anyone have any bacnet mstp wireshark captures?

    Hello, I am trying to check the feasibility of writing some JS/Python to sort and troubleshoot the data from a wireshark capture of a bacnet mstp network. I am not currently on a site with bacnet...
  6. Replies
    15
    Views
    877

    I can see how it would push people away. It does...

    I can see how it would push people away. It does not bother me, heck I even have my Veto MB Tool Bag attached to one of the upper side loops my tech pack. It is kind of like backpack-ception, as my...
  7. Replies
    15
    Views
    877

    I use VETO's Tech Pac LT Backpack Tool Bag, and I...

    I use VETO's Tech Pac LT Backpack Tool Bag, and I love it :)
  8. Replies
    2
    Views
    290

    I saw the Mirius at the AHRExpo, I was quite...

    I saw the Mirius at the AHRExpo, I was quite impressed. We plan to try to use it in our current project (a 16 story hospital addition) as we have a lot of Modbus devices that we need to switch to...
  9. Replies
    17
    Views
    951

    Several people in my company are going to it. I...

    Several people in my company are going to it. I was the one who brought it up to our boss, and said it might be something beneficial.

    Hell, I think my wife might be going with me as well lol.
  10. That is a good point :)

    That is a good point :)
  11. I know it would only require the server itself to...

    I know it would only require the server itself to be upgraded, but I do worry it would frustrate some owners. I would be a bit annoyed too if one of my 30-40 NAE's went down, and for that single one...
  12. The benefits of the new versions seem quite nice....

    The benefits of the new versions seem quite nice. I like not needing a battery as well.
  13. I did get a response from our rep: The NAE’s...

    I did get a response from our rep:

    The NAE’s coming out next Summer/Fall will not be backwards compatible, so a server upgrade would be necessary.
  14. You could use the trunk utilities to test and...

    You could use the trunk utilities to test and write values on multiple controllers at once, as long as the programs are close to the same. I normally test a whole floor at once using the trunk...
  15. Will the new Linux based NAE's be able to go back to previous versions (6, 6.5, etc)?

    I had recently read in another thread that JCI NAE's will soon become linux based instead of embedded windows based. While this is interesting, I do have a major concern: Will you still be able to...
  16. Replies
    4
    Views
    749

    @Synyster - that was not my issue, but it is good...

    @Synyster - that was not my issue, but it is good to know of another fix for this issue if it arises again on a different system.
  17. Replies
    4
    Views
    749

    Issue resolved: my Map gateway was at software...

    Issue resolved: my Map gateway was at software version 4.0, and that did not allow for bacnet routing. The update added the option to settings, so I could configure the ip/port info and connect to my...
  18. Replies
    4
    Views
    749

    CCT programming via MAP gateway issue

    Hello all. I just got the MAP-1810 gateway yesterday, and now I am working on testing it out. We normally use the Bluetooth tool to program/commission into boxes using the CCT/PCT software.

    I...
  19. CCT 13 allows for both metasys and FC based...

    CCT 13 allows for both metasys and FC based commissioning. Granted that does not help if you do not have it, but they are seemingly phasing out the brand lockouts.
  20. I thought we had replaced 1 or 2 of them and...

    I thought we had replaced 1 or 2 of them and still had the issue, though I am unsure if the replacement ones were "old" as well.

    Most of the boxes we work on are updated to CCT version 10.2, but...
  21. This is still an issue, and I've not found a way...

    This is still an issue, and I've not found a way to stop the nuisance alarms from popping up.

    Even though I have changed the temp range to 0-104, a 20 degree reading will occasionally pop up on...
  22. Thanks for the responses. It seems that there is...

    Thanks for the responses. It seems that there is not a huge reason to push for Bacnet/IP on most of our existing sites, as we mainly do service on existing buildings/campuses, and add maybe 5-20 VMAs...
  23. Replies
    8
    Views
    804

    Unless they are using an older image (I cannot...

    Unless they are using an older image (I cannot remember exact release but it seems like pre-6) then it is:

    XMG3-Rel.1
  24. What are the advantages of Bacnet/IP over mstp in regards to a JCI based site?

    Hello all, I have just started looking into Bacnet/IP and am curious what, if any, advantages it has for a JCI based site. The controls contractor I work for uses JCI controllers for 99% of the work...
  25. Even though your issue is fixed, I have also seen...

    Even though your issue is fixed, I have also seen this happen when your device/instance ID’s are duplicates (in your case they are all 1). It usually does not hinder operation, but it does make your...
  26. Hrmm, not quite sure then. I know a lot of times ...

    Hrmm, not quite sure then. I know a lot of times some of the writable points in a bacnet device will be brought in as non-writable in Niagara if you just bring them in using defaults, and it would...
  27. And are you bringing this into Metasys, or into...

    And are you bringing this into Metasys, or into Niagara?
  28. I could check your caf file if you want. A lot of...

    I could check your caf file if you want. A lot of times there are deadbands added into the setpoint determination, and it gives a pretty wide swing between heating and cooling mode. I have bypassed...
  29. Weird Netsensor and/or metasys temp/rh issue

    Hello all, I am experiencing an odd issue on 3 1630vma's.

    Every couple days 1 or two of the netsensors that are attached to the vma's will out of the blue show 20 degrees F and 42% rh. This will...
  30. Disabling the web server and stopping all the...

    Disabling the web server and stopping all the services worked

    Thanks for the advice ��
  31. Metasys question: any way to get rid of alarms on devices not listed?

    Hello all. I have tried various methods of finding this alarm but I cannot find it.

    We have an old ADX that is now only used for hvacpro passthrough.

    The old adx causes an alarm pop up every...
  32. Could you guys tell me which driver you used, and...

    Could you guys tell me which driver you used, and what version of Niagara it was for?

    I the drivers I have found have all been for AX, and the install we are doing is N4. I just want to make sure...
  33. Replies
    10
    Views
    1,173

    I was planning on getting the point info from the...

    I was planning on getting the point info from the sage front end (either by a points list or by the graphics page and using the current values as a translation guide)

    The VAST majority of devices...
  34. Replies
    10
    Views
    1,173

    While the part number exists the driver will not...

    While the part number exists the driver will not actually be released till sept/October.
  35. Replies
    10
    Views
    1,173

    I keep hearing that lol. What part is bad...

    I keep hearing that lol.

    What part is bad about it? The point discovery? Getting the ports to work? Or just all of it?
  36. Replies
    10
    Views
    1,173

    Yeah my company loves JCI so nothing I can really...

    Yeah my company loves JCI so nothing I can really do there.

    And thanks for the info, you basically confirmed that I can use third party drivers on an FX jace. That takes some of the stress off my...
  37. Replies
    10
    Views
    1,173

    I suppose I should have asked about FX jaces in...

    I suppose I should have asked about FX jaces in general.

    It seems from some searching that you can use third party drivers, but I just wanted to be certain before we buy 2-3 jaces just to find...
  38. Replies
    10
    Views
    1,173

    Can an FX-80 use a driver made by Tridium?

    Hello all :)

    I am in need of an American Auto-Matrix PUP network driver for a project. My boss talked to Johnson Controls and they said they do not have a pup driver available. I know Tridium...
Results 1 to 38 of 38