Search:

Type: Posts; User: numbawunfela

Page 1 of 20 1 2 3 4

Search: Search took 0.05 seconds.

  1. Replies
    2
    Views
    70

    What I am looking for is 'upgraded firmware and...

    What I am looking for is 'upgraded firmware and my NRIO died once'
    Basically, I been burned by JCI firmware upgrades on their controller and ever since I am extra cautious before upgrading any...
  2. Replies
    2
    Views
    70

    NRIO Firmware upgrade

    I usually do Niagara NRIO firmware upgrades when I am getting them fresh. I do not usually do it when I have existing stuff.
    I have a chiller plant with 16 NRIO modules at firmware 1.31. Workbemch...
  3. The time I did this was when the computer being...

    The time I did this was when the computer being used was inadequate. So I needed to make Niagara wait for Windows, because the PC effectively locked up for around 3-5 minutes at startup - he was just...
  4. I have had experience placing the Niagara service...

    I have had experience placing the Niagara service to a delayed start. It allows the normal computer stuff to finish happening, close out of RAM, and free up resources before Niagarad tries to make an...
  5. Thread: Going Pro

    by numbawunfela
    Replies
    12
    Views
    358

    Yeah, that is what I meant. As in, no BAS...

    Yeah, that is what I meant. As in, no BAS specific stuff needed.
    VAEngineer - Instead of focusing on BAS qualifications to get into the Pro side on Htalk - remember this is a predominantly...
  6. Thread: Going Pro

    by numbawunfela
    Replies
    12
    Views
    358

    I got my pro membership with my mechanical...

    I got my pro membership with my mechanical qualifications. Then got involved with BMS later. So focus on the mechanical qualifications. Give them a lot, expect them to turn you down, ask them what...
  7. Replies
    5
    Views
    301

    They were on Niagara with an OLD Digilux front...

    They were on Niagara with an OLD Digilux front end. It used flash, and by extension, older Delta used that as well.
  8. Replies
    5
    Views
    301

    Hehe, we have been preparing for that for the...

    Hehe, we have been preparing for that for the last year. I have 4 or 5 sites that have flash front ends and we were migrating the graphics. I have 1 that we had a proposal for and they never bit. ...
  9. Replies
    12
    Views
    300

    Filtering inputs is often done with a moving or...

    Filtering inputs is often done with a moving or rolling average. If the rolling average is accross a 30 second period, it will produce the issues you are seeing. If the rolling average is a 5 second...
  10. Replies
    15
    Views
    462

    200 units is peanuts... last internal statistic I...

    200 units is peanuts... last internal statistic I had from around 7 years ago put the truck-based workforce at over 10k, and I think it was over 13k. 200 units would likely not even be one per US...
  11. Replies
    15
    Views
    462

    Hahaha!! I always wondered why there never was a...

    Hahaha!!
    I always wondered why there never was a Bacnet version of the Commbus quicktester as N2 faded... sounds about right
  12. Replies
    15
    Views
    439

    If I hada waited just another 30 to 40 minutes to...

    If I hada waited just another 30 to 40 minutes to post I wuda been up to my armpits in a proprietary TUX stuff with the 8vdc bus - challenging my 'Alerton always did BacNet' worldview - and it might...
  13. Replies
    15
    Views
    462

    Hehe good for you!

    Hehe good for you!
  14. Replies
    15
    Views
    439

    The BCMs very well might have logic in them. It...

    The BCMs very well might have logic in them. It is programmed the same way controllers are.
  15. Replies
    15
    Views
    462

    Ya know, there is a 1.5 pair, lo cap, bacnet wire...

    Ya know, there is a 1.5 pair, lo cap, bacnet wire sold that JCI COULD use.... in case you needed to add verbiage like that in your future specs. I can dig up a part # if you have trouble finding it....
  16. Thanks Digo I swear I cannot find a thing ever on...

    Thanks Digo I swear I cannot find a thing ever on there....

    Anyway, the suggested solution is to:
    Of course the reason for the conversion is that they already have all 3 of these, but the TUX...
  17. I can't find a thing. The search feature on there...

    I can't find a thing. The search feature on there really sucks....
  18. No no more BCM-TUX, but the ACM has a TUX option...

    No no more BCM-TUX, but the ACM has a TUX option card.... seems promising
  19. Alerton TUX system conversion to Niagara

    I got a building full of TUX controllers from Alerton. Can a JACE talk to these? I did a ctrl+f search of my price list and I got no hits for Alerton or TUX.
    The BCMs on-site will not talk to...
  20. Replies
    15
    Views
    439

    You gotta be kidding me! I remember telling a...

    You gotta be kidding me! I remember telling a coworker how shameful it is he finds himself regularly working with the Blue Screen interface when it is 2016... and he says 'But Alerton was first to...
  21. Replies
    15
    Views
    439

    Funny you should mention Tux... I am on a site...

    Funny you should mention Tux...
    I am on a site with a few TUX BCMs and TUX VAVs....
    Diagnosing comms there.
    My alerton time was short and always JACE Based, and often doing Distech. So I am...
  22. Replies
    15
    Views
    439

    Thanks for the clarification.

    Thanks for the clarification.
  23. Replies
    12
    Views
    507

    That is rather inconvenient...

    That is rather inconvenient...
  24. Replies
    12
    Views
    507

    Do they have a -ILC extension at the end of them?...

    Do they have a -ILC extension at the end of them? That would allow the functionality you are looking for with a Vykon Jace.
    Does that model number maybe show up when looking at the list of...
  25. Replies
    15
    Views
    439

    Alerton has always been all Bacnet. They never...

    Alerton has always been all Bacnet. They never had a proprietary protocol. So they will be all Bacnet. The FLG-MODBUS is a translator from Modbus to Bacnet.
    My experience has been that the Bacnet...
  26. Replies
    15
    Views
    462

    I saw one in someone's bag, it was out of use for...

    I saw one in someone's bag, it was out of use for a while when I was in JCI.
  27. Aw cumon! That was years ago! So annoying...

    Aw cumon! That was years ago! So annoying...
  28. Replies
    15
    Views
    462

    Sounds like the FINALLY got around to updating...

    Sounds like the FINALLY got around to updating the old Comm Bus Quick Tester that they had for N2... around 10-12 years ago for BacNet....

    821237
    ...
  29. Replies
    15
    Views
    462

    JCI Field Inspection Tool FIT

    Anybody use it? Like it? Opinions?

    This is relatively new apparently. I have a guy I met the other day who likes it. I have no experience with it and I have barely skimmed the manual. I want to...
  30. Replies
    9
    Views
    346

    Interesting. Light on useful details. Sounds a...

    Interesting. Light on useful details. Sounds a lot like Alper's project Sandstar. Prophetic maybe?
    Interesting how it promised to level the industry, did not find enough support, and ended up being...
  31. Replies
    9
    Views
    346

    Super awesome, thanks Digo. I will be chewing on...

    Super awesome, thanks Digo. I will be chewing on this for a while.
  32. Replies
    9
    Views
    346

    I remember a nifty thread on here about Baja......

    I remember a nifty thread on here about Baja... it is a subset of JAVA...? Basically Java, but with some changes... I do not know what those are.
    Any comment Digo?
  33. I heard about this but have not yet gotten bit by...

    I heard about this but have not yet gotten bit by it. Thanks for the good details, helpful.
  34. It should also be mentioned that Envision went to...

    It should also be mentioned that Envision went to version 3.5, I believe, and then migrated to Compass which is around rev 1.8 or thereabouts.... Basically, you may have issues with knowing how to...
  35. Thread: Not again

    by numbawunfela
    Replies
    8
    Views
    562

    I had classic shell and loved it. At some point,...

    I had classic shell and loved it. At some point, something IT put on the laptop and classic shell did not get along and killed the laptop. Of course, I had no idea what it was, so I kindly asked for...
  36. Thread: Not again

    by numbawunfela
    Replies
    8
    Views
    562

    Win 7 is out of support, so it is past the end on...

    Win 7 is out of support, so it is past the end on that...
  37. Thread: Not again

    by numbawunfela
    Replies
    8
    Views
    562

    You been traumatized by windows 8 maybe? :D I...

    You been traumatized by windows 8 maybe? :D
    I sure was. There needs to be a line where everyone pissed off can punch someone on the team that made that ui change happen.
  38. Techservices, why are your posts always broken...

    Techservices, why are your posts always broken up? 2 lines, a space, 2 more lines.... it is odd...
    Thanks for the update!
  39. Replies
    27
    Views
    635

    I may need to wait a minute for a post edit...

    I may need to wait a minute for a post edit here.... you did what now via the school of hard knocks?
  40. Replies
    27
    Views
    635

    Go JACEless. Use BacnetIP controllers, local...

    Go JACEless. Use BacnetIP controllers, local native bacnet schedules, all controllers have a local graphic.
  41. To make sure we are on the same page here, a...

    To make sure we are on the same page here, a KitControl block on the worksheet is supervisory logic that only works as long as the JACE is there to execute that code. It cannot get put into any...
  42. Replies
    11
    Views
    444

    I love this 'not in the manual' type stuff. Super...

    I love this 'not in the manual' type stuff. Super helpful.
  43. Replies
    11
    Views
    444

    Exactly

    Exactly
  44. Replies
    11
    Views
    444

    What you describe here sounds like what I would...

    What you describe here sounds like what I would expect to see when a device's RS485 transceiver kicks the bucket. The Leibert guy is talking to the controller over the CAT5 port, and Leibert says 'I...
  45. Replies
    27
    Views
    635

    I had a J8 fail 2 weeks ago. It was corrupted and...

    I had a J8 fail 2 weeks ago. It was corrupted and offline, unreachable. It was a good chance to show the new guy how to serial shell, do a backup button reset and load a .dist file. So it came back....
  46. Replies
    27
    Views
    635

    You may have to 'recover an unreachable JACE'....

    You may have to 'recover an unreachable JACE'. Search for that on this forum and Niagara Central and you will get a lot of hits.
    The process is not short, and it is done when your JACE is...
  47. Replies
    27
    Views
    617

    Funny, that is exactly the same thing I do as...

    Funny, that is exactly the same thing I do as well! :D
    It should be in Modbus manuals.
  48. Replies
    27
    Views
    617

    I always wonder why it exists at all.... Plenty...

    I always wonder why it exists at all.... Plenty of super cool 70s technology is gone by the wayside. Modbus could too one would think.
    This is why LON will never die. [emoji846]
  49. Sticky: Whats this?

    Whats this?
  50. Sticky: I most often see this when there is an electrical...

    I most often see this when there is an electrical issue. For example, a guy was trying to get a bunch of ungrounded controllers with a 2 wire trunk to talk to a grounded AS-P, after letting the trunk...
Results 1 to 50 of 1000
Page 1 of 20 1 2 3 4