Search:

Type: Posts; User: Cool breeze 38

Page 1 of 8 1 2 3 4

Search: Search took 0.01 seconds.

  1. Replies
    9
    Views
    999

    my email is in my profile send me one and ill...

    my email is in my profile send me one and ill give it to you
  2. Controls, you're right, I read right past where...

    Controls, you're right, I read right past where he said he had the license.

    OP did you recently do an update to your FA. did you try adding the license again?

    I'd pay to know the work...
  3. So you can understand the wiring better. They do...

    So you can understand the wiring better. They do not connect by rnet. The rnet port is for a licensed field assistant or equivalent. ZS sensors or the equipment touch for access.

    Controller to...
  4. Bottom line You cant. Carriers field...

    Bottom line You cant. Carriers field assistant doesn't have the permission license to do so.
    I-VU will not upload it either.

    You can do a network discovery and get all the bacnet points just...
  5. keep in mind everything becomes the control guys...

    keep in mind everything becomes the control guys problem.
    to many times I hear this isn't working. First thing I say is did you act like a technetium and diagnose the issue.
    Never loose site of...
  6. Replies
    8
    Views
    792

    if the contactor doest pull in you get that code....

    if the contactor doest pull in you get that code. I have a chiller with a bad contactor coil, and I get that code.
  7. max its Carrier open not alc. In carrier we...

    max its Carrier open not alc. In carrier we can make very organized properties pages. I've seen it on alc also. Whoever put the system in made their own program, didnt do property pages cleanly,...
  8. Replies
    4
    Views
    241

    are you paying attention to the devices tab? when...

    are you paying attention to the devices tab? when you click on the system name. it would have told you to download upload or resolve there
  9. We did that. he sent me the program and I...

    We did that. he sent me the program and I reviewed it. What he needed was there already. The person who wrote the program appeared to be new at it and the properties page was a mess.
  10. Replies
    4
    Views
    241

    to put the board back to new factory status you...

    to put the board back to new factory status you use app loader. its on the ivu tools cd. Being you have FA I will give it to you if needed.
    You use app loader to load the clipping file into the...
  11. Replies
    7
    Views
    248

    To better answer your question as read only...

    To better answer your question as read only during a third part integration. I don't know, haven't tried. I think I need to set up some test programs to check
  12. Replies
    7
    Views
    248

    Doing it in snap makes it read only 100% Even...

    Doing it in snap makes it read only 100% Even using field assistant you cant change the info. So if mr building engineer likes to change something he shouldn't you can lock it.
    You would need to...
  13. Replies
    7
    Views
    248

    In snap. you right click in the info field where...

    In snap. you right click in the info field where you set the properties. then hit read only.

    818843
  14. well done with the diagnostic

    well done with the diagnostic
  15. Replies
    9
    Views
    854

    real the manual. most factory installed...

    real the manual. most factory installed condensate pumps on cassettes can lift 24 inches or so. Just high enough to get the water into a gravity drain.
  16. Replies
    2
    Views
    605

    333 or 3333

    333 or 3333
  17. Make sure the thermostat uses is a 2 heat 2 cool....

    Make sure the thermostat uses is a 2 heat 2 cool. not a heat pump stat. thats a very common mistake when someone installs a carrier commercial ( over 5 ton) unit.

    if they hooked the O up as you...
  18. For boiler operation it would have a programmable...

    For boiler operation it would have a programmable controller. So that give many possibilities. If they program used was out of equipment builder it will have a standard feature to do what you want....
  19. When you go to devices the manage with in the...

    When you go to devices the manage with in the installer tab. Do you always see the routers? Does the loss of comm color on the oval co inside with the routers not being seen?
  20. Replies
    6
    Views
    282

    a module status is not going to tell you where a...

    a module status is not going to tell you where a comm issue is. directly
    it looks like comm 1 on router 1 has issues but lets check some things so I know where you are at.

    when you look at...
  21. Replies
    9
    Views
    999

    if you email me, yes

    if you email me, yes
  22. Replies
    26
    Views
    609

    818026

    818026
  23. Replies
    26
    Views
    609

    there is a member Balbie (i believe thats how its...

    there is a member Balbie (i believe thats how its spelt) he would be the best to ask.
  24. Replies
    26
    Views
    609

    Unless its the IVU Pro he doesn't have site...

    Unless its the IVU Pro he doesn't have site builder to use.
    I have never came across this. But I am logging into a site of ours to see if I can see why
  25. thanks max. mental note made!!!

    thanks max. mental note made!!!
  26. In the upper right of the IVU screen his the...

    In the upper right of the IVU screen his the question mark. The IVU has great help files. hit search type email and what you need comes up.
  27. Email for IVU

    depending on which version IVU it is the email is ina different spot. the pic is of IVU 7. the full screen pic is 6.5 IVU 6.5 and down is done in the alarms page.

    You can set the ivu up to...
  28. I have one site set up like this. I don't watch...

    I have one site set up like this. I don't watch it constantly. I have it set at 50 hrs balance delta. I do see them swap though.
    This is what I see on the IVU using a ccn router ( not the upc...
  29. Let me address the license. First field...

    Let me address the license. First field assistant 5.1 is ancient. Call who sold it to you and tell him to give you the correct 7.0 version.

    The license is there since they only want people part...
  30. Replies
    2
    Views
    266

    how are you connecting to it with the I-VU. are...

    how are you connecting to it with the I-VU. are you using the ccn dongle?
  31. Replies
    9
    Views
    833

    when using CO2 control I still use a 10% min...

    when using CO2 control I still use a 10% min damper to start. I then watch the trend to see where it stays. If it constantly opens on DCV control the minimum needs to be opened more.
    In one space...
  32. Replies
    54
    Views
    3,087

    Carrier and alc are the same company. At the...

    Carrier and alc are the same company. At the carrier expo they were talking about IP controllers. They have them developed. The way they are going to do it was with sub Ip addresses. The hold up...
  33. Replies
    32
    Views
    4,932

    what tools do you currently have? I need an...

    what tools do you currently have?
    I need an email address.
  34. Replies
    68
    Views
    21,880

    carrier makes a chiller optimizer. works with...

    carrier makes a chiller optimizer. works with all bacnet systems.
  35. Replies
    6
    Views
    849

    is the fan going to full speed on reheat?

    is the fan going to full speed on reheat?
  36. https://www.dropbox.com/sh/9pez4wlrv9y5c1e/AABvN9a...

    https://www.dropbox.com/sh/9pez4wlrv9y5c1e/AABvN9ax8kieOkoGTt5NkyIZa?dl=0
  37. Replies
    13
    Views
    3,356

    the only thing new left ( maybe) is the master...

    the only thing new left ( maybe) is the master stat. But if the master stat works along with the relay kit you can put a 3v vvt controller as a slave.
  38. 1. even though it would take a long ass time...

    1. even though it would take a long ass time water beats down everything, including rubber. So its a simple action to assist in durability.
    2. its messy to do PM work on a wet roof.
    3. stops...
  39. Replies
    3
    Views
    211

    if it is already windows 10 you should be fine. ...

    if it is already windows 10 you should be fine. Although windows 10 pro is needed.
    The driver should be on your cd with the rest of the tools. Its in the utilities folder.

    Do you have the most...
  40. everyone got them correct?

    everyone got them correct?
  41. Replies
    0
    Views
    1,028

    Job openings in Northern Virginia

    Hello, we are looking for several positions.

    Service Manager.
    Commercial installer.
    Commercial service tech.
    Controls tech.

    Perry Aire Services
    www.perryaire.com
    Offices in Fredericksburg...
  42. that will work with ivu pro. If its an appliance...

    that will work with ivu pro. If its an appliance you need to check on that. If someone has installer or admin privileges then can find it through system options /general/management tool
  43. Replies
    13
    Views
    621

    ccn address on the chillers comes as buss 0...

    ccn address on the chillers comes as buss 0 element 1. as long as you're not connecting the ccn comms together you wont need to change addresses on the ccn side.

    You will need to change the...
  44. Replies
    13
    Views
    621

    with the UPC its more then 60. the bacnet is...

    with the UPC its more then 60. the bacnet is addressed by the rotary switch. carriers are default 16101+ rotary or mac address The ref_name_1 or _2 or _3 is in relation to the program number on...
  45. Replies
    13
    Views
    621

    are you using the old translator or the UPC? I...

    are you using the old translator or the UPC?
    I can send you the documents on whichever it is.
  46. excelent

    excelent
  47. Replies
    14
    Views
    3,992

    motor pulley divided by blower pulley times motor...

    motor pulley divided by blower pulley times motor rpm. You wont know if the motor is doing the actual rpm on the name plate or slippage. But it will get you close.
  48. Replies
    12
    Views
    2,600

    id do discharge of any chiller or pump. its...

    id do discharge of any chiller or pump. its better to keep the impeller loaded then not on the pump.
    And by keeping pressure on the chiller reduces the possibility of any cavitation.
  49. Your salesman is correct. the carrier VAV (...

    Your salesman is correct. the carrier VAV ( unless you have the newest program) must have a carrier vav controller to operate. ( even if just one with a space sensor) The linkage is the...
  50. was the unit they sent you a 0-10 or 3 step vfd?

    was the unit they sent you a 0-10 or 3 step vfd?
Results 1 to 50 of 358