Search:

Type: Posts; User: MaxBurn

Page 1 of 20 1 2 3 4

Search: Search took 0.05 seconds.

  1. Was the run LED solid and the error 2x a second...

    Was the run LED solid and the error 2x a second when that modstat was taken? I'm now thinking if it were exec startup halted you might not even be able to get a modstat in that state.

    Anyway one...
  2. Damn skippy. Near the top of the modstat you...

    Damn skippy. Near the top of the modstat you didn't show it will probably say something like 1 PRGs initialized. 0 PRGs running. after it locks up.

    Not having an ACTnet actuator attached at all...
  3. The ACTnet controllers are somewhat new so it's...

    The ACTnet controllers are somewhat new so it's important to stay on top of driver updates. I'm showing 6-06-041 is current for the ALC version of the ACTnet zone module, can you check if you have...
  4. Look up relay logic XOR. That will get you...

    Look up relay logic XOR. That will get you started.
  5. Replies
    54
    Views
    1,959

    Same, but we use a pink wire to indicate...

    Same, but we use a pink wire to indicate something that goes down when a safety trips. We come off the strip red and the first smoke or float sensor transitions to pink before it goes to our...
  6. Replies
    54
    Views
    1,959

    Oh, so you took black off the strip and went to...

    Oh, so you took black off the strip and went to the float sensor and came back with the black in the background with the two reds? Which presume go to the stat and outside?

    We handle things a...
  7. Replies
    54
    Views
    1,959

    What's with mixing up the red and black wires? ...

    What's with mixing up the red and black wires?

    Looks really clean though.

    -controls tech
  8. Replies
    190
    Views
    17,782

    By the way, in ALC discovery while the quick list...

    By the way, in ALC discovery while the quick list I shared before in plain text does appear to have a problem displaying names with pipe in them the REAL view you need to work with does not.
    ...
  9. Replies
    190
    Views
    17,782

    That's perfect, thank you!

    That's perfect, thank you!
  10. Replies
    5
    Views
    508

    I'm going to guess you got blocked because what...

    I'm going to guess you got blocked because what was being sent (rate/contents/whatever) triggered a spam filter somewhere. That's going to be VERY hard to troubleshoot and depending on where it's...
  11. Thread: Outages

    by MaxBurn
    Replies
    5
    Views
    264

    Like HVAC-talk is getting attacked? Just got...

    Like HVAC-talk is getting attacked?

    Just got this a few seconds ago;

    Database Error Database error
    The database has encountered a problem.
    Please try the following:
    Load the page again by...
  12. Thread: Outages

    by MaxBurn
    Replies
    5
    Views
    264

    Outages

    The entire site is up and down this morning and yesterday morning, wondering if this will even post.

    This site canít be reachedhvac-talk.com took too long to respond.

    ERR_CONNECTION_TIMED_OUT
  13. Thread: Barf

    by MaxBurn
    Replies
    23
    Views
    1,563

    dedupe, site issues...

    dedupe, site issues...
  14. Thread: Barf

    by MaxBurn
    Replies
    23
    Views
    1,563

    It doesn't take a genius and a calculator to know...

    It doesn't take a genius and a calculator to know each room needs a return, supplies need to be near outside walls, and the ductwork/grills etc CFM needs to be in the ballpark of the unit CFM. We are...
  15. Replies
    4
    Views
    352

    I'm willing to bet nobody here is dealing with...

    I'm willing to bet nobody here is dealing with analog POTS modems. What does that tell you?
  16. Unplug one cable at a time until it doesn't ping...

    Unplug one cable at a time until it doesn't ping and then follow the cable?
  17. Thread: Barf

    by MaxBurn
    Replies
    23
    Views
    1,563

    When I needed mine replaced I had five companies...

    When I needed mine replaced I had five companies out to give me a quote. I specifically asked what is wrong with this install, even gave them a hint the filter return sure makes a lot of noise. I...
  18. Oh you mean you physically can't find the jace? ...

    Oh you mean you physically can't find the jace?

    If you have managed switches you would be able to track it down to a switch port number and then follow a cable. Should be easy to find the jace MAC...
  19. Replies
    190
    Views
    17,782

    Niagara specifically uses "." for a delimiter in...

    Niagara specifically uses "." for a delimiter in their auto folder naming scheme for exposed BACnet points and it's not compatible with WebCTRL modules at all. I always need to go in and rename those...
  20. Replies
    190
    Views
    17,782

    Little more; the | delimiter appears to be a...

    Little more; the | delimiter appears to be a problem for WebCTRL discovery. Just not liking that at all, rarely even shows the configured points in BACRouter and when it does it doesn't have any |...
  21. Replies
    190
    Views
    17,782

    As you can see from the discoveries I'm showing...

    As you can see from the discoveries I'm showing I'm not seeing names like that, so I'd say maybe that is part of the problem. I'll also mention that the discovery text capture I'm posting is the...
  22. Replies
    190
    Views
    17,782

    After applying the updated firmware I received...

    After applying the updated firmware I received the message "the config has some problems, please check carefuly". Can we get an idea on what to check in that error message?

    In the modbus section...
  23. If your laptop was set to 101.10.100.15 and the...

    If your laptop was set to 101.10.100.15 and the subnet mask on the network is 255.255.255.248 or .252 then you would be out of bounds to reach that module even if you are plugged right into it.
    ...
  24. Try page 45;...

    Try page 45; http://powellcontrols.com/pdf/NetConnectGuider23D0205.pdf

    If it has BACnet this can help you ask it about BACnet to get device instance etc;

    nmap --script bacnet-info -sU -p 47808...
  25. What was the network mask for that primary port? ...

    What was the network mask for that primary port?

    Ping?

    Rarely these days you might find a computer that does not support crossover on the network port. You might need a crossover cable to do...
  26. Honeywell Comfortpoint CP-VAV 2.5.6 BACnet points list?

    Does anyone have the points list for a Honeywell Comfortpoint CP-VAV 2.5.6 BACnet controller points list?

    OR if you have any of these anywhere all I really need is the multistate values key value...
  27. Replies
    10
    Views
    555

    Looks good. Just verify the baud rate, bits,...

    Looks good. Just verify the baud rate, bits, stop, parity etc all can agree with what you are already using. You can't use different data bits for two things on the same wire in ALC for example.
  28. Replies
    10
    Views
    555

    Simon/logicbuilder is where programs are made....

    Simon/logicbuilder is where programs are made. You might start with the existing one and rename it.
  29. Replies
    10
    Views
    555

    Each model needs a different integration program...

    Each model needs a different integration program with the specific modbus points for it. The actual function of the program may be different depending on the points given. The point documentation...
  30. Thread: VPN Routers

    by MaxBurn
    Replies
    178
    Views
    12,101

    Actually, yes they do. Forums are active too, so...

    Actually, yes they do. Forums are active too, so there's people that have caught on to these out there.

    https://forum.gl-inet.com/t/firmware-3-201-3-203-release-notes-and-upgrade-q-a/15620

    ...
  31. Replies
    15
    Views
    684

    Based on what you are saying I don't think you...

    Based on what you are saying I don't think you have this problem, it's not going to change by itself that I've ever seen. I only write these once every couple hours for example, it's only meant to...
  32. https://www.carrier.com/commercial/en/us/products/...

    https://www.carrier.com/commercial/en/us/products/controls/building-automation/networking-and-integration/rep485/
  33. OK that worked, thanks. Apparently this is one of...

    OK that worked, thanks. Apparently this is one of those things that has been broken on the old ivu system forever. In the program itself there is a chilled water valve but in the live system someone...
  34. I just added that using the info it gave me. I'll...

    I just added that using the info it gave me. I'll upload that program tonight and give this a try.
  35. Wasn't the program auto generated? Maybe not for...

    Wasn't the program auto generated? Maybe not for these? Just want to be sure editing this program is the right way to go. Looks like I can, just want to know if I should.

    824348
  36. Replies
    11
    Views
    545

    Just annoying, we are limited to one on our...

    Just annoying, we are limited to one on our version of that module.
  37. Quick iVu info in tables display on graphics question

    How can we show the chilled water valve position on a graphic? We can see the valve percentage in two tables but Can't figure out how to get it on a graphic view.

    URL's shown for these two...
  38. Replies
    11
    Views
    545

    Ugh, really?

    Ugh, really?
  39. Replies
    19
    Views
    654

    My two coworkers are the ones that need to be...

    My two coworkers are the ones that need to be reimbursed, all I did was spread the problem around a bit.

    They did finally figure out a sequence of saving parameters and power cycling that got it...
  40. Replies
    19
    Views
    654

    "never attribute to malice that which is...

    "never attribute to malice that which is adequately explained by stupidity".
  41. Replies
    19
    Views
    654

    After a little back and forth; The docs did...

    After a little back and forth;

    The docs did have microsoft word metadata all over them, no doubt the new doc was created from another models doc.
  42. Replies
    190
    Views
    17,782

    Really good info, thanks. I just don't have to...

    Really good info, thanks. I just don't have to deal with this much, ALC switches automatically based on what it sees. What I don't know is if it will request a COV for these properties or if it just...
  43. Replies
    190
    Views
    17,782

    Is there such a thing as a COV subscription for...

    Is there such a thing as a COV subscription for property reliability or do subscriptions only work for present value? Don't think I've ever thought about that before.

    824189
  44. Replies
    25
    Views
    1,020

    And it appears based on the responses here that...

    And it appears based on the responses here that there are more fundamental things that need to be addressed before the product is accepted.
  45. Replies
    6
    Views
    430

    ALC never used capacitors in the past I'm aware...

    ALC never used capacitors in the past I'm aware of before Optiflex. The modules either had batteries or they didn't have anything to lose because they were remotely controlled like T or U series zone...
  46. Replies
    46
    Views
    2,320

    ALC will repair ANYTHING they have made, just...

    ALC will repair ANYTHING they have made, just send it in and prices are reasonable. This is especially important for things they do not make anymore. You can send in a 25 year old controller and if...
  47. Replies
    11
    Views
    545

    I believe the point/device limitation is...

    I believe the point/device limitation is universal for native drivers like CCN.

    I believe if you have one of the older "demo" jaces in your dealership it can run the CCN driver as evaluation.
  48. Replies
    190
    Views
    17,782

    I ran into the point not available issue again....

    I ran into the point not available issue again. Point is submitted and I don't see anything else I need to do, these screenshots taken while it is in this state. I read the point explicitly as...
  49. Replies
    25
    Views
    1,020

    More likely to daisy chain ethernet. Nobody...

    More likely to daisy chain ethernet.

    Nobody is going to pay a premium to get wireless controllers, and add wireless access points, AND then deal with the wireless glitch support issues. My...
  50. Replies
    19
    Views
    3,553

    Please do not spam multiple threads with the same...

    Please do not spam multiple threads with the same request.