Search:

Type: Posts; User: lwarren

Page 1 of 20 1 2 3 4

Search: Search took 0.04 seconds.

  1. Replies
    1
    Views
    167

    Did you try running the Venom migration utility?...

    Did you try running the Venom migration utility? The Venom jars are separate from the spyder tool. Do you have the venom jars?
  2. I have not used this in a long time. I will need...

    I have not used this in a long time. I will need to fix it to make it work in N4. Look in my profile and send me an email and I will try to get to tomorrow.
  3. Replies
    1
    Views
    226

    Not sure what Venom version you are working with,...

    Not sure what Venom version you are working with, but I emailed you the latest AX 3.8 docs I had.
  4. Replies
    5
    Views
    322

    You can use the program service to add metadata...

    You can use the program service to add metadata to the History Configs. I typically just use the Metadata browser (right click on config in your station and select views>metadata browser. This is a...
  5. Replies
    8
    Views
    289

    Thanks, I will give that a try when I am back...

    Thanks, I will give that a try when I am back onsite.
  6. Replies
    8
    Views
    289

    Don't see a "transfer" menu. Only place I can...

    Don't see a "transfer" menu. Only place I can find anything download related is under tools>trunk utilities, but most of the download options are grayed out.

    Thanks for the input anyways.
  7. Replies
    8
    Views
    289

    So when I did the upload it asked me if I wanted...

    So when I did the upload it asked me if I wanted to upgrade, I said no but it wouldnt let me edit the device instance. So I selected upload again and said yes to the upgrade prompt. I was then able...
  8. Replies
    8
    Views
    289

    Thanks, I did see where to change it in the...

    Thanks, I did see where to change it in the define hardware>network settings but it was grayed out because I did not upload it. So once I change it I should just be able to hit the commission button...
  9. Replies
    8
    Views
    289

    Change Device Instance On JCI VMA1620?

    I am bringing a bunch of JCI VMA's into Tridium. I need to change the device instance on a few of these controllers but when I try to change it, I get a write access denied.

    The system still has...
  10. I have seen Windows or other firewalls on a...

    I have seen Windows or other firewalls on a supervisor pc block the jace connections if an exception wasnt added.
  11. What is AV1 and AV2?

    What is AV1 and AV2?
  12. Replies
    3
    Views
    238

    Go to your config facets and add a precision key...

    Go to your config facets and add a precision key with a value of 1.
  13. Replies
    5
    Views
    386

    You won't have anything in there until you start...

    You won't have anything in there until you start saving stuff to it unless you import an existing library.
  14. Replies
    12
    Views
    581

    I had problems with these controllers on a recent...

    I had problems with these controllers on a recent job. Every time the power was turned off to a unit the bacnet settings would revert to default, baud rate and MAC address.
  15. Replies
    8
    Views
    510

    3.8 on a Jace 200 is your likely problem.

    3.8 on a Jace 200 is your likely problem.
  16. I was thinking the Telaire 8100 sensors we put in...

    I was thinking the Telaire 8100 sensors we put in the presidential library that we did were NIST because the NARA holding rooms required and extremely tight temp and humidity tolerance, but I looked...
  17. Replies
    3
    Views
    265

    By default when an XL10VAV is added, the default...

    By default when an XL10VAV is added, the default setpoints are 82.400° and 60.800°. Just write to the setpoint and change it to .000°. You can also just set the precision on the facets to 0.
  18. You can just make the max flow setpoints 1 CFM...

    You can just make the max flow setpoints 1 CFM higher than the min flow setpoints.
  19. Replies
    6
    Views
    854

    Javier, I have no experience with the...

    Javier,

    I have no experience with the software. I have only pulled the gateways and connected directly to the board via modbus and brought them in via a Jace.
  20. Replies
    2
    Views
    403

    Is this a Jace with the Data Recovery Service...

    Is this a Jace with the Data Recovery Service enabled? If so do yourself a favor and get a battery if you dont have one and disable the data recovery service on any jaces you have.
  21. Replies
    9
    Views
    1,145

    Honeywell could screw up a one man rock fight.

    Honeywell could screw up a one man rock fight.
  22. Replies
    6
    Views
    460

    I created a document about 5 years ago on how to...

    I created a document about 5 years ago on how to use a Loytec LIP with a jace. If you send me your email I will send it to you.
  23. Replies
    23
    Views
    1,378

    If you are installing 3.8.401 you can uses...

    If you are installing 3.8.401 you can uses Webstart instead of a browser. About the only problem you might run into is modules (third party) that might exist in the existing Supervisor install.

    I...
  24. Replies
    2
    Views
    356

    A Discrete Totalizer Extension from...

    A Discrete Totalizer Extension from KitContro>ControlPalette>Extensions. Set the change of state count transition from Both to Active
  25. [QUOTE=bolt950rider;25593451]Correct, 14.6 is...

    [QUOTE=bolt950rider;25593451]Correct, 14.6 is N4.6.

    Tridium N4.6+ no longer supports legacy jaces. What are you using?

    N4.4, I have not gone to 4.6 yet.
  26. Not sure if FX version 14.6 is the same as...

    Not sure if FX version 14.6 is the same as Tridium version 4.6, but if so I have heard that you cannot use 4.6 with older jaces only the 8000.
  27. Replies
    4
    Views
    908

    Here are some responses from the Niagara Forum on...

    Here are some responses from the Niagara Forum on this;

    This message indicates that the transmit queue in the native MSTP state machine has been exceeded. In most cases, this occurs when...
  28. Replies
    1
    Views
    624

    Reliable Controls MACH air VAV

    Does anyone have a manual for these older Reliable VAV controllers they can send me?
  29. Replies
    13
    Views
    955

    Do you have the out of the OR block linked to...

    Do you have the out of the OR block linked to something? If not the value will show null in debug.
  30. Replies
    13
    Views
    955

    You can only add objects to the spyder wire sheet...

    You can only add objects to the spyder wire sheet from the spyder tool or venom tools. There is a runtime block in the spyder tool that will accumulate time.
  31. Replies
    15
    Views
    2,460

    What version of N4? There were some bacnet issues...

    What version of N4? There were some bacnet issues with early versions of N4. As stated by Orion there should not be an issue with IP and mstp ports enabled.
  32. Replies
    13
    Views
    955

    Yes, you can download them from the Honeywell...

    Yes, you can download them from the Honeywell Buildings Forum.
  33. Replies
    6
    Views
    854

    The gateways are junk, you will Certainly be...

    The gateways are junk, you will Certainly be better off just hooking up directly and bringing the points in via modbus. Send me an email and I will send you the register list I have when I did this a...
  34. When the station is running it creates a lock...

    When the station is running it creates a lock file. Open task manager and see if you have any station.exe files running. You can also try to stop and restart the Niagara Daemon.
  35. Replies
    7
    Views
    1,166

    You should be able to do this with the VykonPro...

    You should be able to do this with the VykonPro module if you have it. Open the report folder in VykonPro and drag out theAlarmQueryToCsv. Open the property sheet and replace the Alarm Query field...
  36. Replies
    1
    Views
    430

    That looks like a 10K Type 3 sensor.

    That looks like a 10K Type 3 sensor.
  37. Replies
    5
    Views
    663

    Send me your email

    Send me your email
  38. Replies
    5
    Views
    663

    AscLon is a Honeywell module used for the...

    AscLon is a Honeywell module used for the Honeywell Stryker controllers. Looks like you don't have that module locally.
  39. Replies
    1
    Views
    345

    Im guessing you have a TR71 Sylk ZIO. On the...

    Im guessing you have a TR71 Sylk ZIO. On the catagory and parameter selection click the add catagory and name it Setpoint and save. Then click add parameter and for parameter type select Network...
  40. Replies
    24
    Views
    4,203

    I have never had a problem with it. Just download...

    I have never had a problem with it. Just download the JNLP file and run it. Maybe if you didnt have admin privileges that might cause a problem.
  41. Replies
    24
    Views
    4,203

    If you use Webstart you should not be required to...

    If you use Webstart you should not be required to install the security policy files. If you still use the browser instead then you will have to install them.
  42. Replies
    24
    Views
    4,203

    Firefox version 52 was released with the NPAPI...

    Firefox version 52 was released with the NPAPI Java plugins disabled. There is a workaround to enable the plugins. When Firefox 53 is released the plugins will be permanently disabled.
  43. Replies
    15
    Views
    1,206

    It sounds like your Bacnet comms is not enabled...

    It sounds like your Bacnet comms is not enabled or you didn't change the local bacnet device object ID from the default of -1.
  44. Why not just use an And block and link the...

    Why not just use an And block and link the command to one slot and the DP status logic to the second slot. If command 1 is on and DP status is true pump 1 is on. Same thing for pump 2.
  45. Replies
    10
    Views
    1,743

    I never found a good formula for 410, I hade to...

    I never found a good formula for 410, I hade to create a table.
  46. Replies
    10
    Views
    1,743

    So I am assuming you have a pressure transducers...

    So I am assuming you have a pressure transducers and temps sensors on the suction and liquid lines.
    You would need to know the saturation temp for R410 at any given pressure and the liquid line...
  47. Replies
    15
    Views
    1,206

    Do not, I repeat do not load the spyder tool on...

    Do not, I repeat do not load the spyder tool on that Jace 300. You will regret it.
  48. Replies
    4
    Views
    917

    There is one in the Honeywell Venom Apps.

    There is one in the Honeywell Venom Apps.
  49. Replies
    5
    Views
    1,548

    You should be able to discover them as they are...

    You should be able to discover them as they are once you set your Lon network on the Jace to the domain they are on.

    Use the identify function like I explained in the previous post to see what...
  50. Replies
    5
    Views
    1,548

    If the XL500 controllers have the CBUS\ Lon com...

    If the XL500 controllers have the CBUS\ Lon com module you are still going to have a problem bringing them in. You would need the project files and the CARE software to create the points in the XL500...
Results 1 to 50 of 1000