Search:

Type: Posts; User: icy78

Page 1 of 20 1 2 3 4

Search: Search took 0.05 seconds.

  1. Replies
    11
    Views
    909

    Lots of trane units like that also. But they're...

    Lots of trane units like that also. But they're all package units too.

    Sent from my SM-G950U using Tapatalk
  2. Replies
    11
    Views
    909

    2) 2stage resi 5 ton units. Now you have 4...

    2) 2stage resi 5 ton units.
    Now you have 4 stages.
    66% of first unit, then
    100% of first unit then
    100% of 1st unit plus 66% of 2nd unit then
    100% of both.
    So of total.
    33% say 3.3 tons
    50%...
  3. Replies
    3
    Views
    290

    You need to apply for pro status to get that sort...

    You need to apply for pro status to get that sort of help here .
    I can't remember how to do that but if you go to the homepage it's on there I'm pretty sure.

    Sent from my SM-G950U using Tapatalk
  4. Replies
    10
    Views
    451

    The draft inducer on at 80% unit is only there...

    The draft inducer on at 80% unit is only there overcome the resistance of the heat exchanger and place the combustion gases in the flu. At which point the natural draft negative draft takes over. If...
  5. Replies
    10
    Views
    451

    Possibly too much draft too. Underfired is...

    Possibly too much draft too. Underfired is possible.

    Sent from my SM-G950U using Tapatalk
  6. Replies
    10
    Views
    451

    Rusty burners and flue are typical of venting...

    Rusty burners and flue are typical of venting issues and or insufficient combustion air.

    Sent from my SM-G950U using Tapatalk
  7. Replies
    7
    Views
    517

    I think you may have to apply for pro status...

    I think you may have to apply for pro status first.[emoji848]

    Sent from my SM-G950U using Tapatalk
  8. Replies
    52
    Views
    1,577

    Even going electric, it seems that 5000$ for a...

    Even going electric, it seems that 5000$ for a solar setup is cost prohibitive.
    Could put 5k of insulation on that heater and never look back LOL.

    Sent from my SM-G950U using Tapatalk
  9. I just have that bit in a ONE NOTE page. I...

    I just have that bit in a ONE NOTE page.
    I believe it's from the Reliatel manual tho.

    Sent from my SM-G950U using Tapatalk
  10. Here you...

    Here you go.https://uploads.tapatalk-cdn.com/20201024/f416272380463c34a6940bb8e576a75f.jpg

    Sent from my SM-G950U using Tapatalk
  11. Replies
    54
    Views
    1,159

    No, I ment actually "allowing" too much oil to...

    No, I ment actually "allowing" too much oil to leave the crankcase due to ring wear.
    I've only seen it a couple times. Both had oil glasses and good piping, which was helpful.
    Checking the...
  12. Replies
    54
    Views
    1,159

    Sounds like maybe one of your recips may be...

    Sounds like maybe one of your recips may be pumping too much oil.
    Too much wear. But was that caused by poor oil return or flood back? Chicken or the egg.

    Sent from my SM-G950U using Tapatalk
  13. Replies
    54
    Views
    1,159

    In reference to oil migration as you put it, do...

    In reference to oil migration as you put it, do you actually mean oil return or lack thereof?

    Sent from my SM-G950U using Tapatalk
  14. I cant remember for sure but I thought Seresco...

    I cant remember for sure but I thought Seresco had some trouble shooting procedure for those. Possibly.

    Sent from my SM-G950U using Tapatalk
  15. Thread: Unsteady CO

    by icy78
    Replies
    8
    Views
    466

    Lo nox inserts? Sent from my SM-G950U using...

    Lo nox inserts?

    Sent from my SM-G950U using Tapatalk
  16. Replies
    18
    Views
    678

    I ordered a bag. Might have them tonight. ...

    I ordered a bag.
    Might have them tonight.

    Sent from my SM-G950U using Tapatalk
  17. Replies
    18
    Views
    678

    @rundawg . What do you think of the new silicone...

    @rundawg .
    What do you think of the new silicone plugs from NCI?


    Sent from my SM-G950U using Tapatalk
  18. Replies
    11
    Views
    900

    Color of flame doesnt tell you how its burning....

    Color of flame doesnt tell you how its burning.
    And, wielding of an analyzer, doesn't mean the appliance gets set up correctly., if the "wielder" can't correctly interpret the readings.

    Sent...
  19. Replies
    16
    Views
    1,526

    Following. Sent from my SM-G950U using Tapatalk

    Following.

    Sent from my SM-G950U using Tapatalk
  20. Replies
    18
    Views
    581

    [QUOTE=anthonyac1;25938071]Yes, glycol level...

    Yes, glycol level first.
    I thought the level changed when the other tank was brought on line. My bad.

    However, still unclear if it worked before as you found it. BUT, now that theyve added...
  21. Replies
    18
    Views
    581

    Quote. ...But now it stopped cooling once they...

    Quote.
    ...But now it stopped cooling once they opened another isolation valve to add another tank. ......End quote.

    I'd would start there.


    Sent from my SM-G950U using Tapatalk
  22. Replies
    8
    Views
    408

    If you use vinegar judiciously, it is a great...

    If you use vinegar judiciously, it is a great cleaner and disinfectant. If you use it like some of the testing labs , it can destroy many things.
    It appears they use straight white vinegar in...
  23. Replies
    11
    Views
    900

    Good that you're doing that. Last week, out of...

    Good that you're doing that.
    Last week, out of 10 package units I found 5 burning OK. The others needed lo-nox inserts removing , or were over fired, or 1 was way underfired.

    Interesting that 2...
  24. Thread: TXV Stuck Open?

    by icy78
    Replies
    15
    Views
    611

    I tried the dime thing once but it definitely was...

    I tried the dime thing once but it definitely was flooding back and I couldn't leave it like that. So I used shim material and tried a couple THINnesses lol and it worked out well for overnight.
    ...
  25. Replies
    3
    Views
    1,066

    Still shouldn't blow the relief. Sounds like the...

    Still shouldn't blow the relief.
    Sounds like the expansion capacity is too small.
    (Also, the tank pressure should be 4-5 psi higher than the static pressure, to give enough pressure at the highest...
  26. Replies
    8
    Views
    952

    This is true. I was thinking of the "higher" hp...

    This is true.
    I was thinking of the "higher" hp motors. Not the 1/4 and under. Not had issues with those.
    I've had a few failures on ac units at ⅓hp. That's what made me also start installing...
  27. Replies
    8
    Views
    952

    If I'm stuck with only a cheesy screw-on pressure...

    If I'm stuck with only a cheesy screw-on pressure switch, I usually use it as a control for a fan cycle relay. (that I would add.)

    As @ehsx says. Stand-a-lone, they're ok for safety but Penn...
  28. Replies
    23
    Views
    838

    Well shoot! I thought you were still out and...

    Well shoot! I thought you were still out and about.
    Come out of retirement @stump! Too many good guys retired/retiring.[emoji53]




    Sent from my SM-G950U using Tapatalk
  29. Replies
    23
    Views
    838

    Well I like to measure as much as I can. Example....

    Well I like to measure as much as I can. Example.
    Today had a boiler short cycling.
    Found secondary loop pump running at 45hz off off differencial pressure switch. Measuring by curve and triple...
  30. Replies
    23
    Views
    838

    I put a gauge on a circ whenever I can. 1 gauge...

    I put a gauge on a circ whenever I can. 1 gauge with piping to inlet and outlet and isolation valves. Or at least a way to easily tap into the system for flow varification, using Pete's plugs or...
  31. I asked about combustion analysis before I saw...

    I asked about combustion analysis before I saw how rapid the "misfire" is.
    It will.probably be poor, due to the constant recombustion.
    Oh! I just thought of something. It's a modulating furnace!...
  32. Runner tube clean? Orifice size is correct?...

    Runner tube clean? Orifice size is correct? Combustion report?
    What is a tempstar "mod?"
    What is "good" gas pressure?
    Post M# and S#.

    EDIT..just saw video. Pretty good one![emoji106]
    Check...
  33. Replies
    26
    Views
    1,015

    Yup, and you give up looking for it, and later...

    Yup, and you give up looking for it, and later you knee down to work on a lower section and your knee finds what your eyes could not!

    Sent from my SM-G950U using Tapatalk
  34. Thread: Suspicious

    by icy78
    Replies
    16
    Views
    828

    Yeah I signed up for that a while back. It did...

    Yeah I signed up for that a while back. It did take a few weeks.
    Not sure how much I would pay for the magazine, but it is interesting.

    Sent from my SM-G950U using Tapatalk
  35. Replies
    433
    Views
    15,064

    Good on you Matt! Hang in there. BTW your listed...

    Good on you Matt! Hang in there.
    BTW your listed interests cracked me up. I had you pegged (I thought) as a completely different type of guy.[emoji846]

    Sent from my SM-G950U using Tapatalk
  36. Thread: Suspicious

    by icy78
    Replies
    16
    Views
    828

    Suspicious

    Anyone else get this?
    Do I open it? (I'm curious) What say you?

    Sent from my SM-G950U using Tapatalk
    https://uploads.tapatalk-cdn.com/20200909/ed5d1aac9b9e75a22937141c67037cc5.jpg
  37. Replies
    18
    Views
    913

    Well, I'm actually agreeing with you that OEM is...

    Well, I'm actually agreeing with you that OEM is the way to go.

    Sent from my SM-G950U using Tapatalk
  38. Replies
    28
    Views
    1,808

    Do all the easy things first. In particular make...

    Do all the easy things first. In particular make sure that the contacts are clean and the screws are tight and the wires are landed on the right terminals. you can compare it to the other boiler.
    ...
  39. Replies
    18
    Views
    913

    I have a couple of customers who go aftermarket...

    I have a couple of customers who go aftermarket motors on Trane voyagers and Trane RTAA. They change Motors every two years lol

    Sent from my SM-G950U using Tapatalk
  40. Replies
    28
    Views
    1,808

    I'm not being personal[emoji2] It's just that...

    I'm not being personal[emoji2]
    It's just that there was no mention of flame.

    Sent from my SM-G950U using Tapatalk
  41. Replies
    28
    Views
    1,808

    Got gas? Sent from my SM-G950U using Tapatalk

    Got gas?

    Sent from my SM-G950U using Tapatalk
  42. Replies
    28
    Views
    880

    I carried 6 analogs for a few years. Really handy...

    I carried 6 analogs for a few years. Really handy for rack work. 3 of them only had the low side guage and 2 hoses.
    Now its blutooth FP, and an sman 380 for recording purposes. Testo 550 and a...
  43. Thread: inverter trip

    by icy78
    Replies
    11
    Views
    490

    Not following the 60 watt light bulb thing. Am...

    Not following the 60 watt light bulb thing.
    Am interested tho. Can you elaborate?

    Sent from my SM-G950U using Tapatalk
  44. Replies
    10
    Views
    508

    If you do in fact slow the compressor motor down...

    If you do in fact slow the compressor motor down with some type of speed control. Then most likely you will not get the pressure difference across the expansion valve that you need for correct...
  45. Replies
    9
    Views
    782

    And the winner is ......yours truly. Really my...

    And the winner is ......yours truly.
    Really my boy is the winner.
    I hope he gets into it and becomes a tech of some type.

    Sent from my SM-G950U using Tapatalk
  46. Replies
    7
    Views
    394

    Hahaha gotta love it. I saw one once where...

    Hahaha gotta love it.
    I saw one once where someone said the heck with getting that pump in there. They set it on the roof and piped out to it!

    Sent from my SM-G950U using Tapatalk
  47. Replies
    41
    Views
    1,230

    I didnt know that about PAG. [emoji106] Sent...

    I didnt know that about PAG. [emoji106]

    Sent from my SM-G950U using Tapatalk
  48. Replies
    41
    Views
    1,230

    760000 is atmospheric pressure. Each inch ,or...

    760000 is atmospheric pressure.
    Each inch ,or 25400 microns is subtracted from that 760000. So 1" is 760000 -25400.
    29.902" subtracted from 760000 is
    (29.902 x 25400=759510)

    760000 -...
  49. Replies
    41
    Views
    1,230

    PAG oil is also very hygroscopic. Sent from my...

    PAG oil is also very hygroscopic.

    Sent from my SM-G950U using Tapatalk
  50. Replies
    41
    Views
    1,230

    I subtracted the 711000 from 760000. We shoot...

    I subtracted the 711000 from 760000.
    We shoot for 500 microns holding below 1000 on a used system.
    Micron guages show a lower and lower vacuum. "0" being perfect.

    Compressed air would put...
Results 1 to 50 of 1000