Search:

Type: Posts; User: control$

Page 1 of 12 1 2 3 4

Search: Search took 0.05 seconds.

  1. Nudl, Signal...or if ya still have 386 with...

    Nudl, Signal...or if ya still have 386 with QNx....host.
  2. XPSI can not upload a GCM.

    XPSI can not upload a GCM.
  3. Replies
    44
    Views
    1,579

    It's impossible to make anything else out of it....

    It's impossible to make anything else out of it. Please read the title of this thread.
  4. Replies
    44
    Views
    1,579

    Lon is dead..get over it.

    Lon is dead..get over it.
  5. Thread: Controls Tech

    by control$
    Replies
    21
    Views
    862

    You sound like a good egg. Don't wait around for...

    You sound like a good egg. Don't wait around for training, start now. I wish Youtube was around in 1993! As I always tell someone new "I'll assume you know what I'm talking about until you stop me."...
  6. Replies
    44
    Views
    1,579

    Someone's got to explain to me what the...

    Someone's got to explain to me what the advantages actually are. I agree with power meters and even lighting. But FCU's and VAV"s???? It sounds like a smart sales pitch to a dumb customer.
  7. But as bacnet said, they do have a few WSHP...

    But as bacnet said, they do have a few WSHP programs. Looking at the Carrier WSHP logic, they sure do load it up with a bunch of cr@ck as compaired to a ALC program! I would just modify the existing...
  8. Replies
    19
    Views
    798

    I would bet you can. I'll have to Bacscope it and...

    I would bet you can. I'll have to Bacscope it and see what the raw bacnet info is. Had to do that with other manufactures over the years. If I ever get that kinda free time on a job...or better yet I...
  9. Replies
    19
    Views
    798

    I can't rap my head around why it would need an...

    I can't rap my head around why it would need an external control...to do what it is designed to do.
    So I guess I can't help. But it can be done.
  10. Replies
    19
    Views
    798

    Let's back up a bit. What is it your looking to...

    Let's back up a bit. What is it your looking to do?
  11. Replies
    9
    Views
    590

    The reality is some places just don't spend...

    The reality is some places just don't spend money. 20+ years for controls is ok and for me common..finding parts and people who can still work on them might be a problem. I always suggest ebay.
  12. Replies
    17
    Views
    697

    You boys must have been on the cutting edge. The...

    You boys must have been on the cutting edge. The first viewbuilder file I saw was only 2 years ago.
  13. Replies
    17
    Views
    697

    What is the FB name?

    What is the FB name?
  14. Replies
    17
    Views
    697

    They put folders into folders. The import rarely...

    They put folders into folders. The import rarely works correctly with these graphics. Hope I wrong!
  15. Replies
    17
    Views
    697

    Liebert just stuck to the pre-viewbuilder way of...

    Liebert just stuck to the pre-viewbuilder way of making graphics. Look under the Graphics folder, you'll need good old MS Frontpage. ALC had a plug in for that back in the day.
    They do have...
  16. Replies
    4
    Views
    428

    Click the question mark on the top right hand...

    Click the question mark on the top right hand corner of the screen. That'll give you all the basics and enough info to be dangerous. If it's new, it's under warranty. Pick the brains of the service...
  17. Replies
    25
    Views
    1,111

    WebCTRL just works with Viconics. Also I have a...

    WebCTRL just works with Viconics. Also I have a few sites under a BASRT and it's works great.You do loose some WebCTRL features, but the price is right.
  18. Replies
    25
    Views
    1,111

    You buy it and it's yours. They do have a few...

    You buy it and it's yours. They do have a few flavors depending on what you need.

    WebCTRL Standard - 200 points and no available add on's.
    WebCTRL Advantage - 500 point.
    WebCTRL Premium - No...
  19. Replies
    12
    Views
    552

    Why remove the head end? It will work just fine...

    Why remove the head end? It will work just fine without it, but you'll lose all your WebCTRL tools.Leave it in place and do your thing.
  20. - Thick skin. It will always be your fault, get...

    - Thick skin. It will always be your fault, get use to it. IT problems, mechanical problems, electrical faults, lack of maintenance, operators errors...yep..your problems.
    - The best piece of...
  21. Replies
    22
    Views
    1,031

    You shouldn't have an issue.

    You shouldn't have an issue.
  22. Replies
    22
    Views
    1,031

    Do you mean function 3 and 4? They do.

    Do you mean function 3 and 4? They do.
  23. Replies
    22
    Views
    1,031

    Do a modest and you'll get the program name and...

    Do a modest and you'll get the program name and device instance. Liebert's where pretty canned, so chances are someone here has it. Then recreate in Sitebuilder.
  24. I find the control end of the training is pretty...

    I find the control end of the training is pretty poor here in the states. I got lucky since when I started in '93 since I had a solid background in HVAC, And I was one of the few people who where...
  25. Replies
    22
    Views
    1,031

    Man, way off topic. Guess you knew Shalabh?

    Man, way off topic. Guess you knew Shalabh?
  26. Replies
    16
    Views
    1,412

    Bacnet points are free.

    Bacnet points are free.
  27. Not to hijack the thread..but how many of us get...

    Not to hijack the thread..but how many of us get to go home when things aren't going right at a critical site? Anything over (8)hr is OT.
    A fixed salary is unacceptable in the field.
  28. Replies
    5
    Views
    326

    The SE can now accept multi programs. You'll need...

    The SE can now accept multi programs. You'll need to update the driver.
  29. Replies
    12
    Views
    753

    I lived that dream about 5 years ago with Carel....

    I lived that dream about 5 years ago with Carel. I had around 100 some odd units giving me fits and taking down the networks. It turned out they set all the COV's to "0". The network traffic was...
  30. Replies
    17
    Views
    1,238

    The old Uline ALC controls used a 4 wire bus with...

    The old Uline ALC controls used a 4 wire bus with 14g 24vac on one pair and MS/TP 22/2 cap on the other. Works just fine in HVAC.
  31. Replies
    8
    Views
    536

    The Open UPC card is already bacnet MS/TP. Just...

    The Open UPC card is already bacnet MS/TP. Just give it an address and discover your points.
  32. Replies
    108
    Views
    6,955

    That's pretty slick for the price.

    That's pretty slick for the price.
  33. Replies
    4
    Views
    292

    The LGR's I've see get weird after 30 or so...

    The LGR's I've see get weird after 30 or so subnets. Make me wonder how well the auto bbmd works after a few dozen. But we should never outgrow 500!
  34. Replies
    4
    Views
    292

    From the technical instructions, BBMD...

    From the technical instructions,
    BBMD Entries—the number of entries in the BBMD table (500 maximum)
  35. Replies
    14
    Views
    1,260

    I don't think it's the board. Those Bacnet Pid's...

    I don't think it's the board. Those Bacnet Pid's are memory hogs. Funny Carrier only uses the Bacnet PID? Does it work with only one? The latest driver is drv_ucopen_std_6-02-018.driver.

    Don't...
  36. Thread: ALC OptiFlex

    by control$
    Replies
    15
    Views
    1,053

    I've done enough site with strictly MS/TP....

    I've done enough site with strictly MS/TP. Basically slower version of bacnet Arcnet is not proprietary, but nobody is using it. Why? It's an ASHRA standard.
    ALC new controls seem to be catching up,...
  37. Thread: ALC OptiFlex

    by control$
    Replies
    15
    Views
    1,053

    Ditto. The new stuff really looks good.

    Ditto. The new stuff really looks good.
  38. Thread: ALC OptiFlex

    by control$
    Replies
    15
    Views
    1,053

    Agreed! It needs a 4-20ma input! How about a dc...

    Agreed! It needs a 4-20ma input! How about a dc power supply! Engineers just assume it's a cheap replacement for the legacy S6104's until I stick them with real bill to complete.
  39. Replies
    76
    Views
    6,618

    Sounds too much like Initech....now where's my...

    Sounds too much like Initech....now where's my stapler?
  40. Replies
    2
    Views
    605

    Man what mess...Only take the mystery calls on...

    Man what mess...Only take the mystery calls on T&M!
  41. Replies
    76
    Views
    6,618

    I second that! Creston is the worst. I was forced...

    I second that! Creston is the worst. I was forced to integrate ar a billionaires house...terrible!
  42. Replies
    15
    Views
    936

    As other said, go with the Danfoss, ABB or...

    As other said, go with the Danfoss, ABB or Yaskawa. You might be able to find a good small HP used ACH550 or similar on ebay to play with. In any event, all the programming, graphics have already...
  43. Replies
    39
    Views
    2,108

    Another good reason not to buy them..more Chinese...

    Another good reason not to buy them..more Chinese and Chicom junk!

    Factory Sites:
    Taipei:No.168, Liancheng Rd., Zhonghe Dist., New Taipei City 235, Taiwan (R.O.C.)
    China:No.12, Shuang-Fu Rd.,...
  44. Replies
    10
    Views
    633

    How ever you go, just have one pid loop sending...

    How ever you go, just have one pid loop sending out all the ao's that controlling the pressure. Nothing worse then having 10 units fighting each other.
  45. They got some samples? I'm really getting...

    They got some samples? I'm really getting clobbered since EnergyReports is going away. Advanced Reporting will never be as good, and I don't have the time to recreate all those graphics!
  46. That's going to be an impossible question to...

    That's going to be an impossible question to answer. Most of my existing programming is never going to be touched after an upgrade. So you might be running WebCTRL 7.0. But the original logic was...
  47. Replies
    18
    Views
    2,917

    Check your mail.

    Check your mail.
  48. Thread: TAC MN-CIM

    by control$
    Replies
    8
    Views
    636

    Send me an email!

    Send me an email!
  49. Thread: TAC MN-CIM

    by control$
    Replies
    8
    Views
    636

    804224 Guess it's at least 15 years since I...

    804224

    Guess it's at least 15 years since I last ran into one.
  50. Replies
    18
    Views
    2,917

    Your first post and you have your hand out? .......

    Your first post and you have your hand out? .... :gah: Put you email into your profile! Do you have the superset license? That being said ....yes I do. But I would imagine most ALC dealers have...