Search:

Type: Posts; User: numbawunfela

Page 1 of 20 1 2 3 4

Search: Search took 0.05 seconds.

  1. Put a UPS on the JACEs. Really, they do not...

    Put a UPS on the JACEs.
    Really, they do not like bad power. I have never seen what you are describing, but I have seen other odd things when a JACE comes back from a power hit.
  2. Replies
    2
    Views
    63

    Make sure to like the post from the guy who...

    Make sure to like the post from the guy who answered your question. :D
  3. Good catch JCIMan, I did not even notice they...

    Good catch JCIMan, I did not even notice they were doing DAT control with a single stage of cooling. That is pretty much impossible.
    Need to control to space temp Mr Duneland.
  4. You can try to make the compressor run longer,...

    You can try to make the compressor run longer, but it will result in lower space temp, and cold clammy feeling. Not better. You need to change the mechanical side. Try posting this in the commercial...
  5. Replies
    3
    Views
    210

    I had a site with tstats. People started to play...

    I had a site with tstats. People started to play with them, so they had me add covers. People poked through the covers, so I added lockout combination codes to the stats... they called me back and...
  6. So you deleted and re-added them and it made them...

    So you deleted and re-added them and it made them happy? When you re-added them did you use the resource file or did you add them manually?
    Off hand these all looked to be outputs as well. Mostly...
  7. Replies
    3
    Views
    210

    Its not in the Audit logs?

    Its not in the Audit logs?
  8. DX on Niagara N2 Driver - Read fault: Controller Reset

    I have a DX on an N2 trunk on a JACE running the IBMN2 Driver that is running a chiller plant. I have some points that will pop up in Fault Orange with the message "Read fault: controller reset" on...
  9. Replies
    5
    Views
    541

    Nice article

    Nice article
  10. Replies
    39
    Views
    4,018

    If you use the quote button it puts the quote in...

    If you use the quote button it puts the quote in a box that makes it clear that it is a quote.... for what it is worth...
  11. Replies
    39
    Views
    4,018

    I dunno if that is the real fix, but it actually...

    I dunno if that is the real fix, but it actually sounds about right.
    And so cheap too! The eleventy thousand dollar MAP tool fixed with a 12 dollar Amazon Bluetooth dongle. Also sounds about right.
  12. Replies
    11
    Views
    363

    You would need to have SCT first. Without a...

    You would need to have SCT first. Without a server you would need to have your own. That is a hurdle of its own.
  13. Replies
    11
    Views
    363

    GGT graphics are usually on the server. When you...

    GGT graphics are usually on the server. When you do an SCT backup, they are in there. You can use GGT to extract the graphics from either the live system or the SCT archive.
    GGT is like most things...
  14. I would ask a Moderator to move this to the tech...

    I would ask a Moderator to move this to the tech to tech chat commercial mechanical forum.
    It sounds for anything that the chiller has a reversing valve that needs to be energized to run in...
  15. Replies
    192
    Views
    17,885

    It depends on what you get, but I would...

    It depends on what you get, but I would definitely think so.
    Especially when mapping is less than reliable from the tables provided by a manufacturer, it would seem as though having packets captured...
  16. Replies
    5
    Views
    432

    I thought the mods were gonna hafta crack down on...

    I thought the mods were gonna hafta crack down on the language....

    :D
  17. And the LDV5 drivers worked for me on 32 and 64...

    And the LDV5 drivers worked for me on 32 and 64 bit workbenches. In case it matters.
  18. I got it to work. I used the LDV5 drivers, ran a...

    I got it to work. I used the LDV5 drivers, ran a LON station on the laptop, made sure the LDV side was set up to talk on COM1 (same as the JACE station) and I moved the trunk over to my FT-10 adapter...
  19. In Wireshark, you will see the devices respond to...

    In Wireshark, you will see the devices respond to requests from other devices. So you might see BacNet IP from the JACE...if it is set up to send that to someone somewhere for some reason.
    I like...
  20. Seems like it. The only way to know is to try it.

    Seems like it. The only way to know is to try it.
  21. N2 protocol does not support point discovery. You...

    N2 protocol does not support point discovery. You add the .prn file to the controller as a resource file. Then when you 'discover' points it magically works.
    When the PCV is on bacnet it discovers...
  22. I have had JACE 8000s on 1 site with crap power...

    I have had JACE 8000s on 1 site with crap power that will display similar symptoms after a power blip. Then I reboot them nice and slow, and they come back ok.
    Also, if someone sets the IP address...
  23. Replies
    5
    Views
    461

    Perhaps the controller is not the issue but the...

    Perhaps the controller is not the issue but the wiring between is? If you tell something to stop and it wont... then maybe it is in hand.
  24. Replies
    8
    Views
    570

    It is worth a try. The description they give is...

    It is worth a try. The description they give is rather specific and detailed, lending credibility. And it would not surprise me that Johnson would make the BTCVT 'unsupported' by simply excluding the...
  25. Replies
    4
    Views
    453

    Welcome back to the dark side

    Welcome back to the dark side
  26. Replies
    22
    Views
    742

    If that is on the BPP docs somewhere I can search...

    If that is on the BPP docs somewhere I can search there for it. I will need to try this out. It looks like it is entered in a command prompt? likely with elevated privileges....
    Thanks a lot for...
  27. Replies
    22
    Views
    742

    I remember taking a class in Milwaukee with a...

    I remember taking a class in Milwaukee with a software developer for JCI. He said basically there is no reason to check for the daylight savings time patch and setting windows to various settings,...
  28. Replies
    10
    Views
    742

    I dunno about the license upgraded to Desigo. I...

    I dunno about the license upgraded to Desigo. I know Desigo does not use the USB key, so I am pretty sure it is possible to find an unneeded one somewhere.
    I do know that Insight has a process to...
  29. Replies
    22
    Views
    742

    I just ripped out an NAE at rev 2.0 last year.......

    I just ripped out an NAE at rev 2.0 last year.... ya never know....
  30. Replies
    22
    Views
    742

    Yeah, this is where it gets touchy and must be...

    Yeah, this is where it gets touchy and must be done just so....
    JCIMan, is that script on the BPP? I never looked that close....
  31. Replies
    17
    Views
    708

    I think, then, that the best way to get a driver...

    I think, then, that the best way to get a driver that works would to buy the IT lackeys coffee and have them allow it. The security settings may be to 'exclude anything not on this list' or similar....
  32. Replies
    17
    Views
    708

    I believe Entune is a corporate net nanny that...

    I believe Entune is a corporate net nanny that allows the IT lackeys to decide what you can and cannot do... is that right?
  33. Replies
    17
    Views
    708

    Yes, but I am assuming the machine is no more,...

    Yes, but I am assuming the machine is no more, but it is still physically laying around. If so you could scrap the HDD and dongle from it.
  34. Replies
    10
    Views
    742

    Insight is tied to a USB key, so I would assume...

    Insight is tied to a USB key, so I would assume that application will not do you much good unless you have a key and the knowledge of how to bind it to a particular key.
  35. Replies
    17
    Views
    708

    You can upload supervisory logic from the BCM,...

    You can upload supervisory logic from the BCM, using an alerton server to read it in Visio. But, if I am not mistaken, the place to get the database of controller names, DevIDs, MACs and the lost of...
  36. Replies
    10
    Views
    562

    No, I will not translate that for you.... :D You...

    No, I will not translate that for you.... :D
    You may want to ask for the English version.
  37. Replies
    17
    Views
    708

    That is extraordinarily sucky. Alerton lives by...

    That is extraordinarily sucky. Alerton lives by the database in the supervisory computer.
  38. Replies
    10
    Views
    582

    Correction: the site the picture came from. It...

    Correction: the site the picture came from. It was sent to me. I cropped it, but did not obfuscate it sufficiently it seems.
    Small world! You been there apparently. If you did the ALC work it was...
  39. Replies
    28
    Views
    1,219

    One can export points from SCT to excel. Also one...

    One can export points from SCT to excel. Also one can make a tailored summary of what you want in Johnson, and then export that to excel as well.
    ALC has a spot where you can check each point, mark...
  40. Replies
    10
    Views
    582

    Who is Steve L, and how would I anger him? Maybe...

    Who is Steve L, and how would I anger him?
    Maybe I will buy him a beer and make friends....
  41. Replies
    10
    Views
    582

    Woops, I thought I posted the pic of the bacnet...

    Woops, I thought I posted the pic of the bacnet objects tab.
    Thanks Balibe. I thought so but in lieu of trying it out and having it suck, I wanted to ask. Greatly appreciated.
  42. Replies
    10
    Views
    582

    Please elaborate.

    Please elaborate.
  43. Replies
    10
    Views
    582

    ALC exposed to BacNet

    I always thought that exposing points to BacNet required a controller download. But then I saw this screen and got excited.
    If I intend to go to all the controllers and move the jumper from Arc156...
  44. Replies
    22
    Views
    742

    Thanks JCIMan! I am trying to be good about...

    Thanks JCIMan!
    I am trying to be good about getting out my laptop after hours....
  45. Replies
    22
    Views
    742

    I am also pretty sure that if you follow the SCT...

    I am also pretty sure that if you follow the SCT install guide, it tells you where to get the pieces. And I am 100% sure the BPP has everything you need to get all the included JCI programs on it...
  46. Replies
    22
    Views
    742

    It is in the OEM > Microsoft folder.... if...

    It is in the OEM > Microsoft folder.... if memory serves
  47. Replies
    22
    Views
    742

    Awesome! But he needs the SQL, not JAVA... waaa...

    Awesome! But he needs the SQL, not JAVA... waaa waaa.... :D
  48. Replies
    8
    Views
    570

    If the MAP sucks JCI should.... fix it? Heck no!...

    If the MAP sucks JCI should.... fix it? Heck no! Eliminate the alternative and force the poor huddled masses to the suckfest.
  49. Replies
    8
    Views
    609

    You may need to do all numerics on the...

    You may need to do all numerics on the controllers where these live and prune it down if all else fails....
  50. Replies
    22
    Views
    742

    If that BPP is the one with 4 on it, I would use...

    If that BPP is the one with 4 on it, I would use that. If it is the BPP with 4, you will also have an install doc for SCT. Look it up there.
    The FSC SDB has a compatibility spreadsheet telling...
Results 1 to 50 of 1000