Search:

Type: Posts; User: MaxBurn

Page 1 of 20 1 2 3 4

Search: Search took 0.06 seconds.

  1. Replies
    5
    Views
    179

    There is a state that the Daikin can be in that...

    There is a state that the Daikin can be in that you can see the device but it has no points. Meaning they did half of the setup in turning on bacnet but must also go turn on each point one at a time...
  2. Thread: My Home

    by MaxBurn
    Replies
    18
    Views
    1,141

    Interesting on the ERV, you have any monitoring...

    Interesting on the ERV, you have any monitoring on it? Is it a wheel or just air to air?
  3. Replies
    6
    Views
    175

    I tied the jace right into the CCN serial network.

    I tied the jace right into the CCN serial network.
  4. This has been sold, thanks.

    This has been sold, thanks.
  5. Replies
    5
    Views
    157

    That was mentioned as a sticking point in class...

    That was mentioned as a sticking point in class and I don't think I understand why this is an issue but they mentioned a tool to view states. Question was why isn't it going into cooling/heating etc...
  6. Replies
    6
    Views
    175

    It is ...

    It is

    https://www.carrier.com/commercial/en/us/products/controls/carrier-comfort-network/33cspremlk-01-r/#carousel-example-generic

    Do you have a jace licensed as a demo tool? I think you can...
  7. Replies
    5
    Views
    157

    Have you had any training with PCT? I've never...

    Have you had any training with PCT? I've never had to use it at work but I've been shown it once in a hands on setting and I got the impression if you used it all the time it would not be bad at all.
  8. Replies
    6
    Views
    175

    Shouldn't be bad. If it's a bunch of similar unit...

    Shouldn't be bad. If it's a bunch of similar unit types it will likely be fine. I did a bunch of premierlinks a while back and worst part was their schedule...
  9. Thread: No Access

    by MaxBurn
    Replies
    9
    Views
    448

    Guess he didn't realize which side opened?

    Guess he didn't realize which side opened?
  10. Take it straight into the jace, easiest. ...

    Take it straight into the jace, easiest.

    Otherwise Intesis has a new device on the market that seems to work well https://www.intesisbox.com/en/lonworks-bacnet-server-ibox-bac-lon/gateway/
  11. Replies
    15
    Views
    329

    That's all generally my role. Our situations...

    That's all generally my role. Our situations generally fall into one of three categories.

    1. Customer has no IT staff and network is a mess; we push for our hosting here or have a server on site...
  12. Replies
    15
    Views
    329

    We used to use Teamviewer but dumped it due to...

    We used to use Teamviewer but dumped it due to security and user maintenance concerns. Seems well justified;...
  13. Replies
    37
    Views
    1,227

    The fail over with no power was brought up and...

    The fail over with no power was brought up and they cited the cable distance issue. Then they brought up the Cisco ring fail over module AND/OR the home run to each important controller method....
  14. Replies
    37
    Views
    1,227

    Yes, no BACnet routers, all IP connections. They...

    Yes, no BACnet routers, all IP connections. They partnered with Cisco on a redundant link switch so you can wire a whole loop and if anything is cut it will close the loop and you lose nothing. The...
  15. Replies
    37
    Views
    1,227

    No, more of the ALC style where the server is the...

    No, more of the ALC style where the server is the front end and the modules themselves in the field have no operator interaction.

    My point was it's still using Tridium as the front end and that's...
  16. Replies
    5
    Views
    1,215

    It's there, just a bad angle. Big flex that goes...

    It's there, just a bad angle. Big flex that goes around the corner.



    No, this was our panel. Think there was another panel right next to it so the wire was easy to pull. But hey the wire...
  17. Replies
    17
    Views
    464

    Is SiteScan using viewbuilder files now? They...

    Is SiteScan using viewbuilder files now? They never did when I was there, it was all custom java stuff they hand coded. It was interesting because a lot of it was dynamic, floorplans built themselves...
  18. Replies
    37
    Views
    1,227

    Just had a hands on intro into JCI Ethernet based...

    Just had a hands on intro into JCI Ethernet based controllers and it was interesting. Bunch of Ethernet controllers in the field, skip the jace and pull them straight into OWS. Way too many people...
  19. Replies
    17
    Views
    464

    Depends on what you are trying to do but for...

    Depends on what you are trying to do but for floorplans etc look at adding their edit graphic, liebert had some slick abilities to make changes to the floorplan graphics right through the web...
  20. Replies
    5
    Views
    179

    Thays highly likely, I've run into that plenty....

    Thays highly likely, I've run into that plenty. Why not call them back so they can finish their job?
  21. Replies
    2
    Views
    162

    Check your vendor special stuff like...

    Check your vendor special stuff like lynxkitcontrol or maybe niagara community module?
  22. Replies
    17
    Views
    464

    Liebert made their own graphics and they weren't...

    Liebert made their own graphics and they weren't made in viewbuilder when I was working on the system, so that confuses things a bit. Unit bezel is also a liebert term meaning this is the equipment...
  23. Replies
    12
    Views
    998

    I like how carrier is on it in sharpie.

    I like how carrier is on it in sharpie.
  24. Replies
    9
    Views
    345

    Does your front end have bindings all the way...

    Does your front end have bindings all the way down to the last router that is providing the MS/TP segment this AAON is on? I generally find that's where the issue is, if that router doesn't show...
  25. Replies
    2
    Views
    183

    No idea though I've used that module in N4 and...

    No idea though I've used that module in N4 and had no trouble with it.
  26. Replies
    1
    Views
    185

    Without adding another router you could add a...

    Without adding another router you could add a repeater there.
  27. Replies
    9
    Views
    345

    Results with a third party scanner? This is a...

    Results with a third party scanner?

    This is a protonode like device with a network port right? Plug in and see how the device ID and other bacnet info in the web page is set up.
  28. Can that list be cleared or is this a designed in...

    Can that list be cleared or is this a designed in planned obsolescence thing?
  29. Replies
    18
    Views
    599

    Seems to have been worth the wait. They got a...

    Seems to have been worth the wait. They got a asd.jar version 3.7.111.2 which seems very close to the ibmsasd.jar 3.7.112.1 I have now. 3.7 picked it up fine too. Loading that new module required me...
  30. Replies
    6
    Views
    254

    No backups in techs workbench or customers...

    No backups in techs workbench or customers supervisor?
  31. Replies
    18
    Views
    599

    Same outfit, think it's maxline. Same license...

    Same outfit, think it's maxline. Same license they gave me for the ibmsasd.jar worked on the asd.jar.
  32. Replies
    18
    Views
    599

    Yeah that was it, worked through that with...

    Yeah that was it, worked through that with support. Basically it looked like this;

    1. Extract the asd.jar and open meta-inf/module.xml with a text editor.
    2. Look for vendorVersion=. In this...
  33. Replies
    18
    Views
    599

    Same exact problem under 3.5. Must be something...

    Same exact problem under 3.5. Must be something I'm missing or doing wrong?

    809277
  34. Replies
    18
    Views
    599

    I've got the ibmsAsd.jar for 3.7 and 3.8 with a...

    I've got the ibmsAsd.jar for 3.7 and 3.8 with a license key to use it on the replacement jace but the station backup I'm using is looking for the asd.jar. Station starts and runs on my laptop in 3.8...
  35. Replies
    18
    Views
    599

    They are? Damn, I will have to look around there....

    They are? Damn, I will have to look around there. Any pointers as to where they are on that site?
  36. Replies
    18
    Views
    599

    Ah, apparently this old jace was from 3.7 and of...

    Ah, apparently this old jace was from 3.7 and of course the asd.jar I have here doesn't appear to work in 3.7, does work in 3.8 though.

    Anyone have asd.jar appropriate for 3.7?
  37. Replies
    25
    Views
    857

    It exists but as it requires cooperation between...

    It exists but as it requires cooperation between the Carrier and ALC dealers it seems to be rare. There isn't a lot of information on it available to a customer directly to make them aware of it, and...
  38. Replies
    9
    Views
    436

    This is again the facility owner perspective vs...

    This is again the facility owner perspective vs what I call the IT centrist perspective. IT understands upgrades and keeping ahead of obsolescence. Facility owners have a much longer term of thinking...
  39. Replies
    25
    Views
    857

    iVue and WebCTRL working together is called...

    iVue and WebCTRL working together is called superset, search that term and you will find some discussions on it. It requires an agreement between the WebCTRL and Carrier dealers to make it happen so...
  40. Sticky: Haven't watched it yet but have you seen anywhere...

    Haven't watched it yet but have you seen anywhere what type of certificates are used for SC? The white paper posted doesn't mention that at all. I know in talks I've seen unique keys for each SC...
  41. Replies
    25
    Views
    857

    Good info, thanks. What about holiday and...

    Good info, thanks. What about holiday and override schedule priority on these? If I have to put too many limitations on district scheduling people that sort of negates a huge selling point for the...
  42. Replies
    25
    Views
    857

    What model number stats are you talking about...

    What model number stats are you talking about here?
  43. Replies
    3
    Views
    216

    Is there a MSV describing controlling setpoint...

    Is there a MSV describing controlling setpoint source?
  44. Conventional thermostat or BACnet is all we have...

    Conventional thermostat or BACnet is all we have ever done for these. Why reinvent the wheel?
  45. Replies
    25
    Views
    857

    The WebCTRL software itself can create a bacnet...

    The WebCTRL software itself can create a bacnet modeled program to view and make simple point changes to 3rd party devices but this isn't a typical integration as you can't automate anything. That...
  46. Replies
    9
    Views
    1,390

    Access wise that's a problem. Running wise looks...

    Access wise that's a problem. Running wise looks like there is plenty of airflow there so it might not impact the unit that much?
  47. Replies
    3
    Views
    157

    Reasonably sure you are dealing with all unsigned...

    Reasonably sure you are dealing with all unsigned 16bit registers; UINT. Battery current most likely signed; SINT.
  48. Replies
    3
    Views
    157

    Float is a 32bit register so there's likely an...

    Float is a 32bit register so there's likely an address conflict somewhere. Most modbus registers are 16bit, so a float takes the one you selected and the next one. Newer drivers seem to handle this...
  49. Agreed, this is a very wide field with many...

    Agreed, this is a very wide field with many different areas. If you found one thing and got really good at that this is a good way to stand out.
  50. Replies
    25
    Views
    857

    No additional cost to use it on tech or shop...

    No additional cost to use it on tech or shop computers in support of that system either, it's a site license.

    The down side is they have territories and the guys you aren't thrilled with have a...
Results 1 to 50 of 1000