  1. Replies
    6
    Views
    318

    Some heat pump RTUs have conventional terminals....

    Some heat pump RTUs have conventional terminals. W1 fires heat pump in heating, Y1 in cooling, no O/B terminal. Possibly this is what you have. Is it working how you have it set up?

    I would set...
  2. Replies
    56
    Views
    2,033

    All right...some one is going to have to call...

    All right...some one is going to have to call John Tomczyk ::DD:
  3. Thread: Buying tools

    by Red Man
    Replies
    16
    Views
    799

    I’m union. The company buys all the tools and...

    I’m union. The company buys all the tools and they are company tools so we cannot take them when we leave. We have accounts with the local supply houses and a hardware store, so for minor stuff I...
  4. Replies
    10
    Views
    714

    One of my coworkers who did a lot of PMs was...

    One of my coworkers who did a lot of PMs was always finding cracks in Carrier heat exchangers. Carrier sent us an email stating that they were only “cosmetic cracks” and wouldn’t be warranty’d unless...
  5. Could be a number of things. If you like the...

    Could be a number of things. If you like the company you’re using, ask for a more experienced tech. Otherwise you need to find someone that knows what they’re doing.
  6. Maybe the new owners will fix the like button...

    Maybe the new owners will fix the like button :whistle: :angel:
  7. :cheers:

    :cheers:
  8. Are you asking if ice on distributor tunes is...

    Are you asking if ice on distributor tunes is normal? It is normal.
  9. I’m definitely in the camp of sub cooling is what...

    I’m definitely in the camp of sub cooling is what it is with a receiver...I typically see 2-5 degrees. Maybe your comment was sarcastic? In this situation, since the head pressure is elevated so...
  10. 65 psi R22 saturation temp is 37.5. Hard to...

    65 psi R22 saturation temp is 37.5. Hard to believe it’s cooling the box at that saturation temp, maybe keeping it in the low 40s. Also you have no superheat. I’d expect to find high subcooling....
  11. Did you measure sub cooling?

    Did you measure sub cooling?
  12. Replies
    75
    Views
    2,840

    Unions can offer that kinda pay. $75K???...Our...

    Unions can offer that kinda pay. $75K???...Our industry can do better than that. An experienced tech should easily be clearing $100K.
  13. Replies
    7
    Views
    556

    We have a bunch of Genie brand ones, they’re...

    We have a bunch of Genie brand ones, they’re pretty decent.
  14. Replies
    75
    Views
    2,840

    I do a fair amount of start ups...over half of...

    I do a fair amount of start ups...over half of the equipment has something wrong from the factory. As far as service calls, it’s mostly failed parts. I see some improperly installed stuff but it’s...
  15. Replies
    28
    Views
    1,773

    I’ve only used Appion and Inficon. The Appion G5...

    I’ve only used Appion and Inficon. The Appion G5 twin is far superior and I’ve been very pleased with it.
  16. Replies
    32
    Views
    2,085

    So this is a site with lots of unit heaters and...

    So this is a site with lots of unit heaters and only five have problems. These five are in different buildings. The problem is not common to them all. One possibility is they failed one at a time and...
  17. Replies
    38
    Views
    2,070

    I’ve worked on worse.

    I’ve worked on worse.
  18. Replies
    4
    Views
    373

    Imperial tools are built to last, Diversitech not...

    Imperial tools are built to last, Diversitech not so much.
  19. Burner clean? Igniter positioned properly and...

    Burner clean? Igniter positioned properly and clean? Proper pilot pressure?
  20. Replies
    15
    Views
    1,762

    I replaced a Carel suction temp sensor last week...

    I replaced a Carel suction temp sensor last week connected to an exv controller...reading 288 degrees. One of my coworkers replaced one on a different circuit on that system a few weeks ago. He spoke...
  21. Replies
    8
    Views
    943

    No, .1 or .2 ohms is not a big deal.

    No, .1 or .2 ohms is not a big deal.
  22. Replies
    22
    Views
    1,206

    I work on a -40 walk in. It uses 404A and two...

    I work on a -40 walk in. It uses 404A and two stage Bitzer compressors. Suction runs a slight vacuum when approaching set point. Itís in a plasma donation facility with locations around the country....
  23. Replies
    40
    Views
    3,886

    You’re static pressure at start up should...

    You’re static pressure at start up should correlate with ambient conditions. Based on your pressures either the evap or condenser is in 100-130 degree ambient. Sounds like high load, especially now...
  24. Replies
    40
    Views
    3,886

    True, but gotta get the hgb under control first...

    True, but gotta get the hgb under control first to diagnose that. Hgb shouldn’t be maintaining an above normal suction pressure.
  25. Replies
    40
    Views
    3,886

    High suction doesn’t indicate a restriction....

    High suction doesn’t indicate a restriction. Sounds to me like high load or a hot gas bypass problem.
  26. Thread: Freezer Drain

    by Red Man
    Replies
    25
    Views
    1,139

    I’ve run on the inside of copper drains before....

    I’ve run on the inside of copper drains before. On one job, a large warehouse freezer, I’ve ran two through and hooked up one. That way if one fails, the maintenance guys can hook up the other one.
  27. Replies
    9
    Views
    526

    How hard is it to clean the lint out of the coils?

    How hard is it to clean the lint out of the coils?
  28. Replies
    40
    Views
    3,886

    How much superheat when the pressures are high,...

    How much superheat when the pressures are high, where are you measuring it? Just to confirm, you have verified that hot gas bypass is not raising the suction pressure...if so, how have you verified...
  29. Thread: Freezer Drain

    by Red Man
    Replies
    25
    Views
    1,139

    We typically use 120V Raychem self regulating...

    We typically use 120V Raychem self regulating heat trace. We stock rolls of it at the shop and termination kits so it can be cut to length. We have it on a separate circuit from the evap. Use copper...
  30. Replies
    91
    Views
    8,657

    What’s the deal with the tv?

    What’s the deal with the tv?
  31. Replies
    91
    Views
    8,657

    If I’m doing service I put stuff away after each...

    If I’m doing service I put stuff away after each call and bill the customer. If I’m on an install I organize and restock once the install is done and bill for my time. I don’t like organizing my van...
  32. Replies
    3
    Views
    665

    You need the BACnet module that connects to the...

    You need the BACnet module that connects to the microtech controller.
  33. Replies
    20
    Views
    1,055

    Just pump it down. There shouldn’t be any need to...

    Just pump it down. There shouldn’t be any need to recover the charge.
  34. Replies
    7
    Views
    556

    Plumbers putty would work.

    Plumbers putty would work.
  35. Thread: Have you ever?

    by Red Man
    Replies
    49
    Views
    2,845

    I completely agree, there’s absolutely no excuse...

    I completely agree, there’s absolutely no excuse for standing by silently while someone does something dangerous.
  36. Replies
    16
    Views
    1,419

    You can always back it off slowly. If there’s a...

    You can always back it off slowly. If there’s a schrader it should stop hissing before you have it unscrewed all the way.
  37. Did you keep water flowing through the barrel...

    Did you keep water flowing through the barrel while recovering the charge? If not, the refrigerant boiling off could certainly freeze the barrel.
  38. Megohms to ground probably wouldn’t trip a...

    Megohms to ground probably wouldn’t trip a breaker immediately kilohms certainly could. OP...what meter are you using to check resistance to ground? Hopefully you’re not just using the continuity...
  39. When you say the compressor is not shorted, did...

    When you say the compressor is not shorted, did you check windings and to ground?
  40. I completely agree with everyone. An accounting...

    I completely agree with everyone. An accounting degree would be a waste of time. Just hire an accountant. A mechanical engineering degree would be beneficial for sure. The owner of the company I work...
  41. Do you have the tools to recover and weigh in a...

    Do you have the tools to recover and weigh in a factory charge? I’d top it off, but topping off a charge is a bit of an art form. There’s a lot of factors to consider. If you have to ask how to do...
  42. Replies
    47
    Views
    1,742

    Certain types of fans will have an increase in...

    Certain types of fans will have an increase in amp draw with an increase of return air static pressure. A squirrel cage blower wheel will not. Whether this is possible or not, depends on what type of...
  43. Replies
    47
    Views
    1,742

    That really doesn’t answer any of my questions...

    That really doesn’t answer any of my questions :gah:
  44. Replies
    47
    Views
    1,742

    What type of blower wheel does this unit have? Is...

    What type of blower wheel does this unit have? Is the VFD set at fixed speeds, or is it modulating? How is a motor drawing 25 amps blowing a 30 amp fuse? What’s the max current setting in the VFD?
  45. Replies
    25
    Views
    1,217

    Yup...I’d still give it a shot though. Typically...

    Yup...I’d still give it a shot though. Typically when a powerhead fails the valve shuts.
  46. Replies
    25
    Views
    1,217

    I usually use a rebuild kit, but if the supply...

    I usually use a rebuild kit, but if the supply house just has a new valve I’d definitely rob the guts from it. Rebuilding the valve will almost always fix it, very rarely is the problem with the...
  47. Replies
    25
    Views
    1,217

    Can you just rebuild the TXV? That’s usually my...

    Can you just rebuild the TXV? That’s usually my first choice.
  48. If my choices are only a suction service valve...

    If my choices are only a suction service valve and a discharge service valve, I choose the discharge valve.
  49. I agree on the charging. Metering in eight pounds...

    I agree on the charging. Metering in eight pounds into the suction line with the system off is a bad idea.
  50. Not necessarily, but it’s a bit unusual.

    Not necessarily, but it’s a bit unusual.
Results 1 to 50 of 1000