    Looks like you need a crank case heater. I've...

    Looks like you need a crank case heater. I've seen that on a WMC when doing igv motor. I believe that there's a plug underneath the insulation on the cavity for oil drain too. I had DTC tell me that...
  2. Replies
    11
    Views
    440

    The hz on one was at 59 while the other was 60....

    The hz on one was at 59 while the other was 60. Prv pot was reading 0-37ish on both. I will check the heat transfer paste and sensor all the way down. What does the cr8 led represent? Instability in...
  3. Replies
    11
    Views
    440

    I understand what you're saying. My chiller is...

    I understand what you're saying. My chiller is running at 50-60% with a 1° approach on both the condenser and evap barrel.
  4. Replies
    11
    Views
    440

    It has an old codepak panel, VSD, no liquid...

    It has an old codepak panel, VSD, no liquid level actuator. The return temps are stable. The other chiller is doing it to which obviously means it has something in common.
  5. Replies
    11
    Views
    440

    Design is 1000 gpm. 11.4ft. I realize that it...

    Design is 1000 gpm. 11.4ft. I realize that it seems low.
  6. Replies
    11
    Views
    440

    York YT Codepak PRV hunting

    I came up on the chiller today set to 41.5°.
    Its modulating from 43-40. Prv is opening and closing. The pulse of the PRV is around 5-7 seconds which seems long to me. Is there a way to slow it down....
  7. Replies
    9
    Views
    762

    What is your suction superheat while this is...

    What is your suction superheat while this is happening? I believe the drain valve is opening to maintain your suction superheat. Maybe your over feeding because your suction transducer or temp sensor...
  8. Replies
    13
    Views
    1,835

    Some alarms are internal to the compressor. To...

    Some alarms are internal to the compressor. To retrieve them you need the turbocor software. To reset a turbocor lockout, kill power to the compressor until the green light goes on on the i/o board...
  9. Replies
    11
    Views
    1,140

    My shop switched to LPS1. It's a grease less...

    My shop switched to LPS1. It's a grease less lubricant. It doesn't smell bad either.
  10. Replies
    4
    Views
    478

    It's odd to have low discharge superheat and not...

    It's odd to have low discharge superheat and not low suction superheat. Chev is right, verify the sensors but also make sure that your vapor injection is not flooding either. The economizer shouldn't...
  11. Replies
    9
    Views
    725

    Will do. Thanks Chev

    Will do. Thanks Chev
  12. Replies
    9
    Views
    725

    The answer is no. But, it shouldn't matter what...

    The answer is no. But, it shouldn't matter what my meter reads, it should only matters what the chiller sees. I will check though. Thanks
  13. Replies
    9
    Views
    725

    65% for 10 minutes. It does it long after the 10...

    65% for 10 minutes. It does it long after the 10 minutes is over. The pressures and temps mirror the other chiller. Log sheets look good.
  14. Replies
    9
    Views
    725

    I think its software. The optiview shows that...

    I think its software. The optiview shows that it's around 85% when it's going into high motor current.
  15. Replies
    9
    Views
    725

    York YTJ motor- high current limit

    M# YTJ1A4C3- CKJ
    S# GCLM 072086
    Message is motor- high current limit.
    Chiller has a VSD. Local current limit is set to 100%. It comes out of start up demand limit after 10 minutes for 65%. I dont...
  16. Carrier 19DK external oil filter upgrade

    I'm going to change from the OEM type that's in the pump to an external cartridge type. I'm wondering if I need to do anything to the regulator. The filter will be downstream of the regulator. Does...
  17. Replies
    6
    Views
    1,927

    I replaced 2 condenser fan motors on one circuit....

    I replaced 2 condenser fan motors on one circuit. I have not been back since. The building is only 1/4 occupied, so they don't want to spend money for me to look any further. I don't like that the...
  18. Replies
    6
    Views
    1,927

    Thanks for your help everyone. This was my 2nd...

    Thanks for your help everyone. This was my 2nd post and I've been here for maybe 1 year
  19. Replies
    6
    Views
    1,927

    Trane RTAA155 Compressor Overload

    M# RTAA1554X001A3D0ABF
    S# U98H02430

    Has clear language display.
    Both comps are tripping on overload. I think someone changed the overload setting in the service settings. Its currently set to 0....