  1. Replies
    8
    Views
    831

    The information I have is Network Service Tool...

    The information I have is Network Service Tool and Comfort View can be used. But any software downloads is done via Carrier ProView service tool which is a new program and you would need to register...
  2. Replies
    8
    Views
    831

    You need to connect your service tool to the...

    You need to connect your service tool to the touch pilot middle 3 pin socket underneath , the plug you remove you will need to connect to the same plug via a cable with a female 3 pin plug.
    All...
  3. Replies
    10
    Views
    914

    oil_sp1 is while running oil_sp2 = 15 secs...

    oil_sp1 is while running
    oil_sp2 = 15 secs after start is mainly used for low ambients below 2c
    oil_sp2 = 45 secs after start would be the normal oil pressure trip point on start up.
    Oil...
  4. Replies
    10
    Views
    914

    You need to look at oil pressure on start up. You...

    You need to look at oil pressure on start up. You mention sometimes it alarms late in the day so the alarm history shows different times of the day.
    Oil Pressure Alarm Trip conditions see below
    ...
  5. Thread: 30hxc

    by Gibbo
    Replies
    11
    Views
    1,083

    As mentioned previously the O ring can be...

    As mentioned previously the O ring can be replaced by sliding the motor casing back. Of course it begs the question what the condition of the other O rings on the compressor might be. But from...
  6. Did you press "Save" after each "Attach" can't...

    Did you press "Save" after each "Attach" can't think of any other reason at the minute why it didn't retain the settings will have a think over the weekend and get back to you before Monday.
    Gibbo
  7. Brett No problem glad it all worked out ok....

    Brett
    No problem glad it all worked out ok.
    Gibbo
  8. Brett Same procedure as you did for fans but now...

    Brett
    Same procedure as you did for fans but now set_drive =3 for variable pump. Remember to switch off fan vsd's while attaching pump vsd.
    Glad to help.

    Gibbo
  9. Apologies I was looking at a 30 RB, Look in ...

    Apologies I was looking at a 30 RB,
    Look in Maintenance / DRV_CTRL menu you will see the "attach" at the bottom. It's either set_drv = 1 for A or 2 for B
    All drives should be switched off except...
  10. Depends on number of circuits if only 1 circuit...

    Depends on number of circuits if only 1 circuit or 2 circuits if 2 then you will need to attach the drive to the correct circuit you should find this in service configuration. Your software is ok so...
  11. Think it's only the Danfoss VSD that requires the...

    Think it's only the Danfoss VSD that requires the attaching procedure.
    Schneider is just plug and play. Just verify the config is similar.

    Gibbo
  12. Replies
    8
    Views
    844

    Smart View is an option on Version 5 and can...

    Smart View is an option on Version 5 and can still be used with the current servicetool. It I'll be fitted on Version 6 as standard but will need the new servicetool about to be rolled out.
  13. Replies
    8
    Views
    844

    Smart View is the controls name. Will be the same...

    Smart View is the controls name. Will be the same in the US out of Charlotte.
    Gibbo
  14. Replies
    8
    Views
    844

    It's the new touchpilot with Smart View now being...

    It's the new touchpilot with Smart View now being used across various new units out of Carrier Montluel France.
    Gibbo
  15. Thread: 30hxc T026-027

    by Gibbo
    Replies
    8
    Views
    877

    The EXV position is under 60% operation can be...

    The EXV position is under 60% operation can be anywhere between 40% and 60% normally being towards the 40% end. Over 60% would be classed as low on refrigerant. All these checks including subcool...
  16. What alarms are you getting ? the...

    What alarms are you getting ? the "eto.carrier.com" site will only show Flotronic 2 controls for the HR you could try the 30 HZ chiller manual which is basically a 30 HS chiller but pro dialog...
  17. There are 2 versions of pro dialog HXC a black...

    There are 2 versions of pro dialog HXC a black display phase 2 or cream display phase 3.Try the Carrier website for manuals and wiring diagrams
    eto.carrier.com/lit.asp

    Gibbo
  18. There is one possibility you could try the...

    There is one possibility you could try the following
    1)Configure the circuit you want to run as lead A =1 or B =2 lead circuit will load up to 100%
    2)Configure for Demand Limit switch control = 1...
  19. Your fault code 20 is for a Flotronic 2 chiller...

    Your fault code 20 is for a Flotronic 2 chiller his fault code 20 is for a Flotronic 1 chiller.

    Gibbo
  20. Can't say I have seen that fault before would...

    Can't say I have seen that fault before would think it's either a main board problem or software issue. Do you have a controls manual for it there is a section on troubleshooting the main board...
  21. Replies
    10
    Views
    1,638

    As previously mentioned the refrigerant charge...

    As previously mentioned the refrigerant charge seems high to me.
  22. Replies
    10
    Views
    1,638

    Also be aware microchannel coils don't do...

    Also be aware microchannel coils don't do pumpdowns again it will trip on high pressure.
    Gibbo
  23. Thread: Clivet chillers

    by Gibbo
    Replies
    18
    Views
    1,736

    The number C511082 you gave us is for the EXV...

    The number C511082 you gave us is for the EXV board both the EXV and probe are connected to this board. It maybe a EXV board comms failure or no power to the board. So I would start there first then...
  24. Thread: Clivet chillers

    by Gibbo
    Replies
    18
    Views
    1,736

    All the chiller alarms I have begin with E...

    All the chiller alarms I have begin with E followed by 3 digits can't see that alarm code C511082.
    As mentioned a model number might help..
  25. Thread: Clivet chillers

    by Gibbo
    Replies
    18
    Views
    1,736

    Who told your client it needed a new expansion...

    Who told your client it needed a new expansion valve.
    Very rare for both EXV and EXV board needing to be replaced, usually when the initial tech isn't too sure of what's causing the problem he may...
  26. Replies
    4
    Views
    690

    It should be ok, when you say it works what makes...

    It should be ok, when you say it works what makes you think so. Only when the chiller is running and the EXV' are controlling the superheat at 5c will you really know. You may want to check that the...
  27. Replies
    4
    Views
    690

    Which chiller are they for.

    Which chiller are they for.
  28. Replies
    4
    Views
    690

    Find it hard to believe Carrier Service could not...

    Find it hard to believe Carrier Service could not download software to both EXV boards.
    Gibbo
  29. Replies
    3
    Views
    1,785

    A 30 LA chiller won't register here as it's a Oz...

    A 30 LA chiller won't register here as it's a Oz built chiller I believe. Your controls sound like it's a Flotronic 2. You need to get hold of the controls manual for it or any Flo 2 controls manual....
  30. Replies
    4
    Views
    760

    The oil level switch is fitted at the bottom...

    The oil level switch is fitted at the bottom right of the oil seperator the oil level switch is a small brass cyclinder shape with plug on top.
    Regarding the water pump are you saying the output to...
  31. Replies
    4
    Views
    760

    Alarm 54 is low oil level possibly may be just...

    Alarm 54 is low oil level possibly may be just the switch also check oil level.
    Alarm 75 is water flow as your pump does not run you need to fix that problem.

    Gibbo
  32. Replies
    10
    Views
    1,282

    The alarm is in version 5. Suspect it's a case of...

    The alarm is in version 5. Suspect it's a case of the compressor not starting after a command to start. No pressure differential seen between Suction and Discharge pressure.
    Gibbo
  33. Replies
    4
    Views
    1,675

    Regarding flow switches assuming they are the...

    Regarding flow switches assuming they are the thermal dispersion type If it is just water then its not a problem if glycol then they need to be calibrated through a tool supplied from Carrier.
    ...
  34. Replies
    11
    Views
    1,408

    I would just plug it. More concerned with why it...

    I would just plug it. More concerned with why it has 100% glycol in system.
  35. Replies
    17
    Views
    4,920

    Your DP looks very high if this is on start up...

    Your DP looks very high if this is on start up and trips in 15 secs check your DP transducer. Could be air in system.
  36. Replies
    8
    Views
    2,181

    Is it possible you have got water inside the plug...

    Is it possible you have got water inside the plug connection on the flow switch. You could try checking it and maybe dry it out with air gun. Failing that just replace the flow switch.
  37. Replies
    6
    Views
    1,940

    Ethernet is Bacnet direct connection from...

    Ethernet is Bacnet direct connection from customer
    CCN is Service tool connection or for master slave connection between 2 chillers
    Len. is for downloading software to the touch pilot / Bacnet ...
  38. Replies
    6
    Views
    1,940

    The ethernet connection is for you to connect...

    The ethernet connection is for you to connect Your Bacnet connection.direct.
  39. Replies
    6
    Views
    1,940

    Bacnet is the preferred option not sure Modbus...

    Bacnet is the preferred option not sure Modbus is an option.its built into the back of the new touch displays it doesn't come as standard it's ordered along with the chiller, you connect to the...
  40. Replies
    25
    Views
    8,349

    No issues with Danfoss compressors or EXV's. We...

    No issues with Danfoss compressors or EXV's. We did have an issue with high oil levels on B circuits causing low sst can't remember the which size chiller was affected. As to Copeland compressors...
  41. Replies
    79
    Views
    24,012

    What type of coils are they microchannel or...

    What type of coils are they microchannel or copper aluminium.
    If microchannel someone has posted on another site about issues with the O rings leaking where discharge and liquid lines join the...
  42. Replies
    15
    Views
    2,512

    Do I get a prize Dallas.

    Do I get a prize Dallas.
  43. Replies
    15
    Views
    2,512

    It looks like the main board is a PSIO, have seen...

    It looks like the main board is a PSIO, have seen this problem before on one of the first 30GX chillers. It's most likely the PSIO which is the black rectangular board in the panel. Carrier should...
  44. . Apologies No 2 was built on the 25/7/11. ...

    .

    Apologies No 2 was built on the 25/7/11.

    Gibbo
  45. Chiller 1 Nominal Cool Capacity is 1202 kw built...

    Chiller 1 Nominal Cool Capacity is 1202 kw built 12/9/11.
    Chiller 2 Nominal Cool Capacity is 1002 kw
    built 1/9/11.

    Depending on options fitted the KW capacity can be slightly lower or higher by...
  46. For the French factory spare parts catalogue go...

    For the French factory spare parts catalogue go to
    www.carrier-ercd.com.
    Gibbo
  47. I have a factory spare parts catalogue dated 2013...

    I have a factory spare parts catalogue dated 2013 and also. googling the part number. There is a factory spare parts database which shows if the part number has been superceded with a new part...
  48. 32GB401-044C is rated at 90 tons it has been...

    32GB401-044C is rated at 90 tons it has been superceded by 32GB402-604C.
    Gibbo
  49. The 32GB402-624C is rated for 120 tons which for...

    The 32GB402-624C is rated for 120 tons which for your application makes it way oversize. The controller would attempt to try to control the superheat but you are likely to experience problems doing...
  50. . The EXV part number for med brine was...

    .

    The EXV part number for med brine was 32GB401-034C
    this has been Changed to 32GB402-594-C this valve is rated for 75 tons
    EXV part number for Low Brine was 32GB402-014C this has been changed...