    At the time, there was no single sign on. To your...

    At the time, there was no single sign on. To your average sales person or estimator who lives in Tridium world, this comes off as a strong implication that the ECY can act as a supervisor to other...
  2. Replies
    12
    Views
    814

    They never come out and explicitly say it is a...

    They never come out and explicitly say it is a supervisory device, but they strongly, strongly imply it. This is the first video I saw about ECY line.

    https://youtu.be/XeM8yjQn8N0?t=64

    "Small...
  3. Replies
    12
    Views
    814

    To be fair, Distech has been pushing this...

    To be fair, Distech has been pushing this narrative since day 1 with the ECY line.
  4. Replies
    12
    Views
    814

    You cannot program MSTP controllers without using...

    You cannot program MSTP controllers without using Niagara. If you are planing to use the ECY to display data from the 103s, you will need an EC-NET station to connect (initially) to the 103s to...
  5. Replies
    226
    Views
    40,972

    I ordered 6 of them. Build quality seems good.

    I ordered 6 of them. Build quality seems good.
  6. Replies
    14
    Views
    445

    I will definitely share. I am pretty sure the...

    I will definitely share. I am pretty sure the file itself is not encrypted because I am amble to see bits of other files when I load it into Notepad++. I am tempted to upload it to the internet and...
  7. Replies
    14
    Views
    445

    I can mount the SD Card just fine using...

    I can mount the SD Card just fine using DiskInternals in windows. The issue I am really having is this 3GB file appears to hold the station and every other file in the JACE (PX, program files, etc)....
  8. Replies
    14
    Views
    445

    You can see the FAT32 partition in windows, but...

    You can see the FAT32 partition in windows, but it wonít natively read the Unix partitions.
  9. Replies
    14
    Views
    445

    Maybe, but I was hoping to get access to all of...

    Maybe, but I was hoping to get access to all of the px files, gfx files, images, etc. Workbench can blow away the passphrase on the bog, so i figured that could get me everything I wanted.
  10. Replies
    14
    Views
    445

    Mounting SD Card Froma JAce

    Is there any way to pull a station from an SD card from a JACE via a PC? There seems to be 3 partitions, one is FAT and the other two are QNX6. The QNX partitions only have one large file each with...
  11. Replies
    17
    Views
    1,340

    I got the unit to accept commands, but then then...

    I got the unit to accept commands, but then then it decided to just go haywire and the fan was constantly changing speeds. The owner gave up and it now runs 24/7 in standalone mode. Until someone...
  12. Replies
    226
    Views
    40,972

    Thinking about ordering some of these to offload...

    Thinking about ordering some of these to offload the CPU from doing the heavy lifting for MSTP on a JACE running close to the limit. Any reason to give some of these a go?
  13. Replies
    12
    Views
    414

    Yes, it is the intel product.

    Yes, it is the intel product.
  14. Replies
    12
    Views
    414

    I just need to know which m controller is which...

    I just need to know which m controller is which RTU or VAV. I donít care about any of the program logic.
  15. Replies
    12
    Views
    414

    Carrier.

    Carrier.
  16. Replies
    12
    Views
    414

    My issue is that I don't know which unit is...

    My issue is that I don't know which unit is associated with which device ID. I can see a bunch of devices on the comm bus, but the only way to tell which one is which is to go kill power and see what...
  17. Replies
    12
    Views
    414

    i-Vu database

    I was handed a building that has a dead i-Vu front end. The NUC won't power on, but I pulled the drive and am able to navigate the filesystem. I found some of the floorplans other images. Is there...
  18. Replies
    7
    Views
    391

    I'm sure this is in reference to the other thread...

    I'm sure this is in reference to the other thread he posted about losing comm over over the owners IP network.
  19. It is probably on another subnet, it will not be...

    It is probably on another subnet, it will not be discoverable unless you have BBMD setup correctly.
  20. Daikin Mircotech III RTU Controller Exhuast Fan Not Running

    I have 3 identical Daikin VAV RTUs with Mircotech III controllers. They were all humming along nicely for 6 months, and then one of the units sopped running the ehuast fan in the middle of the day...
  21. Lighting panels at library are not a critical...

    Lighting panels at library are not a critical application. Spending money on two JACEs is a giant waste of money. You should be using programmable controllers to control the lighting. Any decent...
  22. Replies
    11
    Views
    597

    You don't. You shouldn't be using a JACE to read...

    You don't. You shouldn't be using a JACE to read IO like this. You need to use a programmable controller. You really need to use the right tool for the job, otherwise you are just making a mess for...
  23. There is no difference except some controller...

    There is no difference except some controller brands require you use their JACE or buy an expensive license.
  24. Replies
    6
    Views
    762

    ACI has always been really solid. They are really...

    ACI has always been really solid. They are really good about crossing other sensors and coming up with solutions for controllers looking for specific ranges.
  25. Replies
    6
    Views
    762

    We use and sell ACI. Not sure how competitive...

    We use and sell ACI. Not sure how competitive they are to BAPI or not. For just a sensor, pretty inexpensive. For units with displays, they offer the TUC2 sensors which look nice.
    ...
  26. As numbawunfela said, Distech still does...

    As numbawunfela said, Distech still does Lonworks. It is about 10% of our sales. Viconics is still offer them as well. I have seen buses with 80+ devices that run fine, just playing with fire if you...
  27. Itís been a while since Iíve done it, but...

    Itís been a while since Iíve done it, but essentially yes. The JACE will be a BACnet/IP device and the points in your export table will be discoverable by another BACnet device, just like any other.
  28. BBMD is functionality required for BACnet/IP to...

    BBMD is functionality required for BACnet/IP to communicate across different subnets. This is now what you want. In the JACE, you can use the Export Table in the under your local device to link to...
  29. Do you have your IP port pointed at the correct...

    Do you have your IP port pointed at the correct network interface for your computer?
  30. Replies
    2
    Views
    294

    Do you have the Distech support pack? If not, you...

    Do you have the Distech support pack? If not, you should order it. It is a licensed feature on a non-Distech JACE. It allows you to right click on the controller and have the Disetch modules do all...
  31. I have seen a few other Brands like TAC that were...

    I have seen a few other Brands like TAC that were locked as well.



    The contractor sold them a locked down piece of garbage. Things like brand locked JACEs are what gives end users a negative...
  32. I would strongly consider throwing out any...

    I would strongly consider throwing out any contractor who tries to install a locked down JACE. It speaks to their business practices, even if they agree to remove the restriction on your site.
  33. Replies
    6
    Views
    522

    I got some information from someone who has some...

    I got some information from someone who has some unofficial info from Tridium. Unofficially they are acknowledging the driver is flaky above 4.7+. The fix is to an additional restart on the station...
  34. Replies
    6
    Views
    522

    It does show that COM2 is assigned to the CCN...

    It does show that COM2 is assigned to the CCN network and the CCN network itself isn't showing fault. The activity lights show an occasional transmit, but nothing else.
  35. Replies
    6
    Views
    522

    Niagara 4.10 and CCN

    Are there any known issues with CCN on 4.10? I upgraded a system from 4.7 and now none of the CCN devices are online? I confirmed they were all communicating before hand. The CCN network is...
  36. Sell them a 5 year SMA plus add on an additional...

    Sell them a 5 year SMA plus add on an additional 5 years if you want to be safe. No fees for 10 years.
  37. In addition to this, each device will need a...

    In addition to this, each device will need a unique device instance.
  38. Replies
    7
    Views
    567

    If the owner isn't connecting from outside the...

    If the owner isn't connecting from outside the subent on their LAN, you can just change the gateway and point it to the cellular modem.
  39. Replies
    12
    Views
    490

    Is the software pirated? Is it malware? Was it...

    Is the software pirated? Is it malware? Was it used to commit a crime?
  40. Replies
    1
    Views
    388

    Ziehl-Abegg ECM Control

    Have a unit with a Ziehl-Abegg ECM motor on a blower. The motor has terminals for 0-10, but is configured for modbus with the card linked below. Unit wonít respond to 0-10, so must be overridden by...
  41. I buy Distech as both a contractor and as an OEM....

    I buy Distech as both a contractor and as an OEM. Our OEM usage is maybe a thousand controllers per year while our contracting usage is well over a million dollars. As a contractor, I love when I see...
  42. Replies
    219
    Views
    128,622

    Just saw an email from them letting everyone know...

    Just saw an email from them letting everyone know they are going to be canceling what appears to most if not all VFD orders and will not be accepting any new orders.
  43. Replies
    3
    Views
    628

    The JACE needs to have a Distech license. The...

    The JACE needs to have a Distech license. The license if pretty cheap for 5 devices.
  44. Replies
    17
    Views
    1,340

    It is an Intellipak. Not sure if there was a...

    It is an Intellipak. Not sure if there was a display in the unit, but I fill take a look.
  45. I had not heard of it until you mentioned it...

    I had not heard of it until you mentioned it here. Looking at the literature, it would seem like a "building" is a JACE unless you get the supervisor option which will connect to 3 JACES. An...
  46. Replies
    17
    Views
    1,340

    Trane Unit Wont Accept BAS Control

    I have a new packaged Trane unit that BI1 (System Control Status) is reporting as "Stand Alone Control". I have set BO1 (System Control Command) to "BAS Control" and am not getting BI1 to change via...
  47. Distech sells UUKL versions of their controllers...

    Distech sells UUKL versions of their controllers which makes me wonder if their is any difference in production or testing.
  48. This is correct. I did one and there was an issue...

    This is correct. I did one and there was an issue with the Fire Alarm system that was supposed to initiate the sequence and it drug on for months. There is no way to put enough money in a job like...
  49. Replies
    2
    Views
    468

    Got it. Thanks!

    Got it. Thanks!
  50. Replies
    2
    Views
    468

    Honeywell 4.10 Modules

    Anyone have the Honeywell 4.10 modules and would be willing to share? Need to update a JACE to 4.10 since Microsoft is blocking older versions of TLS.