    Circuit 1 was running fine before the software...

    Circuit 1 was running fine before the software upgrade.
    Just thought I would throw that out there too!


    Sent from my iPhone using Tapatalk
  2. Replies
    7
    Views
    595

    I replaced both suction temperature sensors after...

    I replaced both suction temperature sensors after the software upgrade because they were both out, by a lot.
    I confirmed pressure and temperature sensors/transducers.
    Tomorrow I am going to weigh...
  3. Replies
    7
    Views
    595

    CGAM new fault-Loss of Charge

    I posted earlier about a CGAM I had to change an EXV on, I had to do a software upgrade to have the new EXV communicate as per Trane.
    After that I had both of the suction temperature sensors fail,...
  4. Replies
    5
    Views
    396

    Yes they are the fast acting. When I called...

    Yes they are the fast acting.
    When I called Trane they thought it was another temperature sensor and they said there is over 12,000 on back order in all of North America.
    Had to send the apprentice...
  5. Replies
    5
    Views
    396

    Thanks guys! After digging in deeper, it is the...

    Thanks guys!
    After digging in deeper, it is the sensors.
    It was just strange to me after a software update it started.
  6. Replies
    5
    Views
    396

    CGAM software update, new faults

    So I have an older CGAM that needed a new EXV (circ 2), circuit 1 was running and maintaining for the most part, after installing the new EXV and molded plug I tried to unbind and bind the new molded...