Search:

Type: Posts; User: The Reaper

Page 1 of 20 1 2 3 4

Search: Search took 0.04 seconds.

  1. Replies
    14
    Views
    195

    They are under the cover of the CGM. They are...

    They are under the cover of the CGM. They are just above the input terminal blocks. Last week, I upgraded a DX9100 that used a 4-20 pressure sensor that was powered off of the 15VDC onboard. I could...
  2. Replies
    14
    Views
    195

    Make sure you set the jumper correctly for the...

    Make sure you set the jumper correctly for the corresponding input if it's 4-20. Had that one bite me last week with a CGM.
  3. Why not just drop a label over the buttons with a...

    Why not just drop a label over the buttons with a colored background to hide them. I'm not aware of any other way.
  4. Thread: GX-9100

    by The Reaper
    Replies
    4
    Views
    639

    http://support.controls.johnsoncontrols.com/?cid=7...

    http://support.controls.johnsoncontrols.com/?cid=74&c=12&cpc=v7dS6AKprgyf54GU44uK3RC2#tab:homeTab:crumb:8:artId:34776:src:article

    I think this is your problem
  5. Replies
    5
    Views
    392

    Man! Sounds like you're almost as old as I am!...

    Man! Sounds like you're almost as old as I am! Used a bunch of those palm pilots. Right now I run a Windows 2000 VM with S2 convertor. Works great. Running a full PMI install on the same VM
  6. Replies
    5
    Views
    349

    Thanks man!

    Thanks man!
  7. Replies
    14
    Views
    787

    Found this on the JCI help site: Be careful...

    Found this on the JCI help site:

    Be careful when applying a max write time to points, especially controller hardware BOs and AOs. It has been found that if you have a point mapped with a max write...
  8. Replies
    5
    Views
    349

    Thanks for the quick reply! Unfortunately I can't...

    Thanks for the quick reply! Unfortunately I can't access the unit. The roof access is not finished yet. Is there a way I can change the IP settings through the IP connection. There was nothing in the...
  9. Replies
    14
    Views
    787

    How frequently does it happen? Can you disconnect...

    How frequently does it happen? Can you disconnect communications and see if it stops?
  10. Replies
    5
    Views
    349

    Trane RTU BACnet IP

    I have a site that has a Trane makeup air unit that is connected BACnet IP. I can access it through a browser but not through the Jace. The subnet on the Jace is 255.255.255.0 and the unit is...
  11. Replies
    14
    Views
    787

    Check your tuning policy. Make sure it's set to...

    Check your tuning policy. Make sure it's set to the default policy.
  12. Replies
    11
    Views
    747

    What a dope I am! I ended up not having a role...

    What a dope I am! I ended up not having a role assigned to my station to supervisor password! Thanks for all the replies!
  13. Replies
    11
    Views
    747

    I did a ping ans it pings fine. Then I did a scan...

    I did a ping ans it pings fine. Then I did a scan with nmap and it shows 4911 and 5011 open. I'm stumped! The user account info is good and the Super is online in the Jaces Niagara Network but still...
  14. Replies
    11
    Views
    747

    Will do. Thanks! I'll post results.

    Will do. Thanks! I'll post results.
  15. Replies
    3
    Views
    3,847

    Boiler Room Controls Before and After

    A recent boiler room controls upgrade. Ripped out 2 old JCI UNT111's and an NAE that was left dead on the wall. Rewired all high voltage to boilers and pumps .
  16. Replies
    11
    Views
    747

    I haven't tried a ping but the Supervisor is...

    I haven't tried a ping but the Supervisor is online consistently in the Jace's Niagara Network. I'll try when I'm back onsite.
  17. Replies
    11
    Views
    747

    Yes. No schedules show up to import. Also, I made...

    Yes. No schedules show up to import. Also, I made some various global points and I cannot see them either when I do a point discover. The Supervisor is on a VM.
  18. Replies
    11
    Views
    747

    Yes, the schedules are in the Supervisor. I can't...

    Yes, the schedules are in the Supervisor. I can't discover them in the Jaces.
  19. Replies
    11
    Views
    747

    Supervisor Scheduling

    I have 2 Jaces being brought into a Supervisor. All points pulled in fine but I can't discover any points or schedules from the Jace side to the Supervisor. I'm trying to map in my Supervisor...
  20. Replies
    4
    Views
    560

    I tried it with Chrome and Firefox

    I tried it with Chrome and Firefox
  21. Replies
    4
    Views
    560

    Thanks Digo!

    Thanks Digo!
  22. Replies
    4
    Views
    560

    N4 Supervisor Graphics Error

    I just put a new Supervisor online to 7 Jaces. They are all Honeywell 4.10. The Supervisor is on a VM provided by the customer's IT. When I try to make a browser connection, I get this error (see...
  23. Replies
    13
    Views
    650

    From memory, I seem to remember a few sites I...

    From memory, I seem to remember a few sites I took care of that shared points between NCM's. I believe it is possible to have a program in 1 NCM trigger points in another one.
  24. Replies
    13
    Views
    650

    Could the processes be buried inside another one?...

    Could the processes be buried inside another one? Can you send me the GPL folder? I have a PMI workstation on a VM.
  25. Replies
    2
    Views
    910

    N4 Supervisor Schedules

    I'm putting in a supervisor and pulling in 8 N4 Jaces. When I pull in the existing schedules, it looks like I cannot edit them, just view only. Is there a way that I can modify Jace schedules from...
  26. That was it! My password was 11 characters....

    That was it! My password was 11 characters. Thanks!
  27. Thanks guys. I did try multiple browsers and...

    Thanks guys. I did try multiple browsers and machines. Waiting for CC tech support to respond.
  28. Contemporary Controls BASRT-B BACnet IP/mstp Router

    I went to set up this router today and ran across an issue that's got me stumped. Direct connection with laptop and ethernet cable, I log in with the default creds and it says I need to change the...
  29. Replies
    11
    Views
    1,855

    I would get a BACnet trunk out to the TUX and...

    I would get a BACnet trunk out to the TUX and replace it. Too much of a hassle to get the program out of the APEX unless they still have the workstation and it's functioning. The IBEX line has been...
  30. Replies
    11
    Views
    1,855

    This is all I have that references a TUX-450....

    This is all I have that references a TUX-450. From what I remember, there is no DDC in the controller memory. All control comes from the APEX.
  31. Replies
    8
    Views
    1,127

    So simple, yet effective! I'm going to delete...

    So simple, yet effective! I'm going to delete what I did and use that. Thanks!
  32. Replies
    8
    Views
    1,127

    Thanks! I'll give it a shot

    Thanks! I'll give it a shot
  33. Replies
    8
    Views
    1,127

    We are using a numeric switch to manipulate the...

    We are using a numeric switch to manipulate the setpoint then the false slot of the switch is set to null so it returns to normal when the timer expires. This is for an Automated Demand Response from...
  34. Replies
    8
    Views
    1,127

    Analog Value Ramp in Tridium

    I have to do a timed override on a setpoint in N4 and when It gets released, the customer wants it to ramp back to the normal value over a period of time instead of just switching back. Is this...
  35. Replies
    20
    Views
    1,949

    If it works, I'll put your picture as the home...

    If it works, I'll put your picture as the home page on the Jace!
  36. Replies
    20
    Views
    1,949

    The customer has a killer WiFi network that they...

    The customer has a killer WiFi network that they will let me use. If I put the Jace on their ethernet and port over the WiFi devices, would that bypass the limitations? Sounds like what Numbawunfela...
  37. Replies
    20
    Views
    1,949

    Thanks for all the replies! I'll post updates if...

    Thanks for all the replies! I'll post updates if I come up with a solution.
  38. Replies
    20
    Views
    1,949

    Jace WiFi Device Limit

    Does anyone know how many WiFi devices I can bring into an N4 Jace? I have a site that needs to disable electric baseboard in 115 rooms. They will not allow us to run wires and would like a wireless...
  39. Replies
    2
    Views
    606

    Thanks!

    Thanks!
  40. Replies
    2
    Views
    606

    Jace 8000 SMA Notification

    Anyone know how to get rid of the SMA expiration notification on the login page? TIA
  41. Replies
    1
    Views
    1,184

    Honeywell Spyder Issue

    I'm running WEBstation-N4 4.6.96.28 and I'm adding Spyders to a Jace that never had them. My Spyder Tool is 7.2.15. I can't see the honeywellSpyderTool module to install it into the Jace under...
  42. Replies
    2
    Views
    443

    Take the .dist file from the backup and change...

    Take the .dist file from the backup and change the extension to .zip then extract it. That should give you all your graphics.
  43. Thread: Bql Query?

    by The Reaper
    Replies
    4
    Views
    574

    Add a slot path like AHU Name to your query.

    Add a slot path like AHU Name to your query.
  44. Replies
    4
    Views
    2,496

    It seems to only happen when it's a station that...

    It seems to only happen when it's a station that I didn't create. I ended up rebuilding it on my PC and the problem went away.
  45. Thread: BQL Query

    by The Reaper
    Replies
    6
    Views
    1,042

    Sorry Orion for the misspell! I wasn't wearing my...

    Sorry Orion for the misspell! I wasn't wearing my glasses!
  46. Thread: BQL Query

    by The Reaper
    Replies
    6
    Views
    1,042

    Thanks Qrion! The slotPath was where I went wrong.

    Thanks Qrion! The slotPath was where I went wrong.
  47. Thread: BQL Query

    by The Reaper
    Replies
    6
    Views
    1,042

    BQL Query

    I have a job where I have 80 vav boxes on 2 different AHU's. They are named VAV1-1 for AHU-1 and VAV2-1 for AHU2 ect...
    I'm fairly new to BQL and I need to grab zone temp and reheat position into a...
  48. Replies
    10
    Views
    1,452

    Put your email in your profile please. Or just...

    Put your email in your profile please. Or just shoot me an email.
  49. Replies
    4
    Views
    2,496

    Finally got it working. Had to manually run the...

    Finally got it working. Had to manually run the daemon from the console. When I try to transfer a station to my local host so I can run it on my PC, I get this error. Any ideas?

    Transfer failed....
  50. Replies
    4
    Views
    2,496

    Siemens Workbench Platform Daemon

    My Siemens Workbench 4.7 platform daemon is stuck in startup and will not run. When I run the daemon from the start menu it says installed successfully but I cannot transfer a station to the local...
Results 1 to 50 of 1000