Search:

Type: Posts; User: bigguy158

Page 1 of 20 1 2 3 4

Search: Search took 0.04 seconds.

  1. Replies
    9
    Views
    1,057

    We might get some product. If I do I’ll post...

    We might get some product. If I do I’ll post pics.

    I have more info to share this weekend.


    Sent from my iPad using Tapatalk
  2. Thread: Trane SI/IP

    by bigguy158
    Replies
    1
    Views
    235

    Trane SI/IP

    Found a VAV in SI units wondering if there is a way to change units in the BACnet object?

    We looked and didn’t see anything under it.

    Hospital is an hour + away from anyone and this particular...
  3. Replies
    9
    Views
    1,057

    I met with the jci easyIO product guy today. He...

    I met with the jci easyIO product guy today. He confirmed they re-engineered the product line in the last few years. Meaning no more leaky caps. This was partly done so they used the same components...
  4. Replies
    14
    Views
    253

    24vdc + goes to transducer positive Transducer...

    24vdc + goes to transducer positive
    Transducer output to CGM input
    CGM input common goes to 24vdc common


    Sent from my iPad using Tapatalk
  5. Replies
    3
    Views
    319

    Hint Boolean points can be connected to an...

    Hint Boolean points can be connected to an addition block and it will spit out 0 through 4 depending on stages running.


    Sent from my iPad using Tapatalk
  6. Replies
    4
    Views
    278

    Only use https? Try other browsers? Try a...

    Only use https?
    Try other browsers?
    Try a different user?


    Sent from my iPad using Tapatalk
  7. Replies
    2
    Views
    378

    If you have 10vdc and are scaling it to 500 psi...

    If you have 10vdc and are scaling it to 500 psi wouldn’t you multiple the VDC by 50?

    So if your sensor is outputting 5VDC x 50 = 250 psi.

    Make sense?


    Sent from my iPhone using Tapatalk
  8. Yep that was the tool for them. Does it still use...

    Yep that was the tool for them. Does it still use Visio or just reuses the blocks in the (what ever it’s called this week) struxcture.


    Sent from my iPad using Tapatalk
  9. Replies
    20
    Views
    655

    Just do a return/exhaust temp and call it a day....

    Just do a return/exhaust temp and call it a day. Same thing as a MRI room with faraday cage.


    Sent from my iPad using Tapatalk
  10. When yo say TAC/IA block programming are you...

    When yo say TAC/IA block programming are you referencing workplace tech tool?


    Sent from my iPad using Tapatalk
  11. This actually made me want to do a full blown AHU...

    This actually made me want to do a full blown AHU with SA bus. (With hardwired safeties) I wonder how long until jci bring out the actuators? SA bus has now been around for 17 Years. You’d think...
  12. Why don't controllers just come with all configurable outputs and universal inputs?

    Sorry have to correct you here. The SA bus has room sensors, probe temp sensors (4” and 8”), CO2 sensors, VFDs, and York chillers. Notice no averaging sensor?
    ...
  13. I never understood why a 16 BI controller and not...

    I never understood why a 16 BI controller and not a 16 UI.

    Other than the plastic cover the FX/MS lines are merged they have identical components.


    Sent from my iPad using Tapatalk
  14. Replies
    1
    Views
    155

    Make sure the trane modbus comm is plugged into...

    Make sure the trane modbus comm is plugged into correctly. Then power cycle the unit. (make sure BCI loses power) I believe if things are wired correctly the BCI will then pull in the points.

    ...
  15. I had one yesterday that was existing. Had to get...

    I had one yesterday that was existing. Had to get into it and edit the BBMD table. There was a bdt.ini file that I need to download/upload through a command prompt. Really protonode? Is this the best...
  16. OP has not posted since 2013. Sent from my...

    OP has not posted since 2013.


    Sent from my iPhone using Tapatalk
  17. Replies
    31
    Views
    9,223

    Test it and see. Siemens sometimes does not use...

    Test it and see. Siemens sometimes does not use port 47808. They will use 47809 or 47810. Just an fyi.


    Sent from my iPad using Tapatalk
  18. @orion242 can help you methinks. Sent from...

    @orion242 can help you methinks.


    Sent from my iPad using Tapatalk
  19. Replies
    6
    Views
    408

    Replace the POS metacyst NAE with a Jace....

    Replace the POS metacyst NAE with a Jace. #fixedit


    Sent from my iPad using Tapatalk
  20. Stability says go big… ...

    Stability says go big…

    https://www.oldworlddistributors.com/550-watt-heavy-duty-soldering-iron.html

    https://uploads.tapatalk-cdn.com/20220915/06429103ce363c5cd1b3cec6b2a59e6d.jpg

    Or do you...
  21. Replies
    6
    Views
    408

    They are all set points that need to be written...

    They are all set points that need to be written to the 3113 property. However metasys just does a confirmed cov write in the background so the point does not get written to over and over again.

    ...
  22. Replies
    6
    Views
    408

    It doesn’t work in metasys because the metasys...

    It doesn’t work in metasys because the metasys views it as a generic bacnet device instead of a JCI device. JCI is doing some proprietary bacnet stuff in the background to do what they do with those...
  23. Replies
    47
    Views
    1,655

    https://www.roadrunnermedia.com/features There...

    https://www.roadrunnermedia.com/features

    There is a number on the technology companies website. But I get the impression they are not the ones selling the ads?

    Road Runner Media, Inc. 28562 Oso...
  24. Looks like your end points are correct. ...

    Looks like your end points are correct.

    https://www.bapihvac.com/rtd-overview/#1552066592515-abd6c1e5-13a8

    Yeah I second Digo 1ks on NRIO/NDIO are no bueno. You can add filtering to the point...
  25. I guess to really answer your question I’d like...

    I guess to really answer your question I’d like the BAPI part number and your resistance table you are using or at least it’s two end points.


    Sent from my iPad using Tapatalk
  26. We just had a bad input on a NRIO module as well....

    We just had a bad input on a NRIO module as well.


    Sent from my iPhone using Tapatalk
  27. Change your CCT release back to 10.3/6.2 main...

    Change your CCT release back to 10.3/6.2 main code. It’s up top on the bar on the left side drop downs.


    Sent from my iPad using Tapatalk
  28. Replies
    4
    Views
    741

    I typically see that error if either the server...

    I typically see that error if either the server IP is coming in DHCP instead of static or if the server name has changed. Double check your settings and compare to known good jace?


    Sent from my...
  29. I like ACI. ...

    I like ACI.

    https://www.workaci.com/content/gp0-100g-20-p


    Sent from my iPad using Tapatalk
  30. Replies
    20
    Views
    1,392

    Sticker. I did not crack the unit open. Sent...

    Sticker. I did not crack the unit open.


    Sent from my iPad using Tapatalk
  31. Replies
    20
    Views
    1,392

    Allegedly Someone else canceled their order and...

    Allegedly Someone else canceled their order and we were next on the list. The job we ordered them on was finished (with ciper 50s) but I wasn’t going to turn down product.


    Sent from my iPad...
  32. Replies
    20
    Views
    1,392

    CIPer 30 expansion modules were made in early...

    CIPer 30 expansion modules were made in early August of 2022.
    CIPer 30s we’re from October of 21.


    Sent from my iPhone using Tapatalk
  33. Replies
    6
    Views
    378

    So if your replacing the entire valve, belimo or...

    So if your replacing the entire valve, belimo or whoever will provide you with an actuator that has enough torque to drive the valve they supply. You just need to get the sizing correct.
  34. Replies
    20
    Views
    1,392

    Classic spyders I’m guessing? Sent from my...

    Classic spyders I’m guessing?


    Sent from my iPad using Tapatalk
  35. Replies
    20
    Views
    1,392

    Short answer we planned ahead and also offered...

    Short answer we planned ahead and also offered alternatives.

    On the good news front I ordered 4 CIPer 30s and IO modules last November and was notified we will receive them this week.

    I’m...
  36. Replies
    5
    Views
    629

    Did you start with the Niagara hardening guide? ...

    Did you start with the Niagara hardening guide?

    https://www.tridium.com/content/dam/tridium/en/documents/document-lists/Niagara%204%20Hardening%20Guide_2019.pdf


    Sent from my iPhone using...
  37. Replies
    4
    Views
    2,922

    You need to manually change them. Sent from...

    You need to manually change them.


    Sent from my iPhone using Tapatalk
  38. Start switching from port 47808 to a different...

    Start switching from port 47808 to a different one for an easy fix?


    Sent from my iPad using Tapatalk
  39. Correct Sent from my iPhone using Tapatalk

    Correct


    Sent from my iPhone using Tapatalk
  40. CIPer would need the laptop locally if on the...

    CIPer would need the laptop locally if on the secondary port. Unsure of the distech device.


    Sent from my iPad using Tapatalk
  41. Replies
    2
    Views
    639

    I’m not shilling for them but he is easy to work...

    I’m not shilling for them but he is easy to work with and relatively inexpensive.

    http://bascustomgraphics.com/VRV_Systems.html


    Sent from my iPad using Tapatalk
  42. Replies
    12
    Views
    4,838

    There is a Niagara developer class you can take...

    There is a Niagara developer class you can take too.


    Sent from my iPad using Tapatalk
  43. Thread: CCT 14 Issue

    by bigguy158
    Replies
    6
    Views
    532

    When Johnson originally put PCT and CCT together...

    When Johnson originally put PCT and CCT together in CCT 13, they had an oops mistake that allowed us contractors to access both FEC and PCG Controllers. They fixed that mistake with CCT 14 and...
  44. Replies
    20
    Views
    1,392

    They’re making the classics but long lead times....

    They’re making the classics but long lead times. 5s will be restarting production “soon”.


    Sent from my iPhone using Tapatalk
  45. Replies
    8
    Views
    313

    Yes. Emerson had a firmware issue in 2020. It...

    Yes. Emerson had a firmware issue in 2020. It sounds like your drive is 20 years old?


    Sent from my iPhone using Tapatalk
  46. Replies
    32
    Views
    1,117

    You can self sign at N4.9. I’m not certain N4.10...

    You can self sign at N4.9. I’m not certain N4.10 and above. Maybe Orion can answer that.

    https://know.innon.com/how-to-self-sign-a-module-for-niagara-4.9

    You’re asking some very interesting...
  47. Replies
    32
    Views
    1,117

    Never heard of gmaps. Looks like the module is at...

    Never heard of gmaps. Looks like the module is at N4.4. As of N4.9 and above modules needed to be signed. I’m guessing the module is not and it’s throwing the error.
    ...
  48. Replies
    10
    Views
    445

    I wouldn’t call 60 VAVs one one trunk excessive,...

    I wouldn’t call 60 VAVs one one trunk excessive, but one thing I like about tridium is how many comm trunk connections you can have. If you feel it matters go with two. Depends on future use of space...
  49. Replies
    10
    Views
    445

    My company is on board the CIPer 30 train....

    My company is on board the CIPer 30 train. Meaning using the JACE as a plant controller. However if you do this the JACE should not do anything else. Remove the 60 vavs from the station and move to...
  50. JCI controllers perform well at .25”/wc. I...

    JCI controllers perform well at .25”/wc. I haven’t gone lower than that. Plus with pressure switches I would stay above .5”/wc.


    Sent from my iPad using Tapatalk
Results 1 to 50 of 1000