Search:

Type: Posts; User: icy78

Page 1 of 20 1 2 3 4

Search: Search took 0.04 seconds.

  1. Replies
    16
    Views
    249

    Raise the CO to 14-16f and set CI at 37-38f. So...

    Raise the CO to 14-16f and set CI at 37-38f.
    So 14 psi and 33.5 psi.

    Sent from my SM-G950U using Tapatalk
  2. To me, a brief look at your numbers shows that...

    To me, a brief look at your numbers shows that you're under fired.
    You could check your orifice sizes and I would also check and make sure that you pull lo-nox inserts out. Then run your...
  3. Replies
    28
    Views
    734

    Ask them why. If it's to protect the...

    Ask them why.
    If it's to protect the compressor....I'd opine that they dont really understand what we've been discussing.

    If it's to keep the evap from having lower pressure than the water side,...
  4. Replies
    28
    Views
    734

    Running in a vacuum causes scroll failure or I...

    Running in a vacuum causes scroll failure or I should say scroll compressor failure, by causing a short at the fuseite connections.
    Is that because there's no cooling effect and the Heat at...
  5. Replies
    9
    Views
    303

    It's always a tough sell telling people that youd...

    It's always a tough sell telling people that youd like to install a tee for combustion air from inside .
    Then you go through the whole battle of, well ....doesn't that reduce the efficiency? ...
  6. Replies
    28
    Views
    734

    There is nothing specific about how long a scroll...

    There is nothing specific about how long a scroll will last running in a vacuum. It would depend greatly on the strength of the vacuum to. The AE bulletin simply say not to run a scroll in a deep...
  7. Replies
    50
    Views
    1,263

    I don't know guys, I'm still thinking that if you...

    I don't know guys, I'm still thinking that if you had swapped pumps two and a half weeks ago you would have known right then if it was a pump problem or a system/ electrical problem.

    It is weird...
  8. Replies
    28
    Views
    734

    What's it in? Seen a few scrolls with bypass...

    What's it in?
    Seen a few scrolls with bypass timers for cold weather.
    Heatcraft uses em. 2 minute bypassI think .

    Sent from my SM-G950U using Tapatalk
  9. Replies
    15
    Views
    638

    My ladder blew down once. Now, I have a bungie on...

    My ladder blew down once. Now, I have a bungie on the top of my ladder all the time. It lightly stretches between a loose, burly ziptie on the 3rd rung down, and the same on the 6th rung down....
  10. Replies
    9
    Views
    439

    Curious. How did you happen to have that refer...

    Curious. How did you happen to have that refer identifier?
    Not a common tool I think.

    Sent from my SM-G950U using Tapatalk
  11. Replies
    9
    Views
    439

    With that 134a txv it may have 134a in already...

    With that 134a txv it may have 134a in already then?
    Some one changed the txv.
    The velocity in close coupled cases will allow you to run 134a with no oil change.
    At least I've found that to be...
  12. Replies
    9
    Views
    439

    401a (mp39) is very common around here. It works...

    401a (mp39) is very common around here. It works well.
    That's pretty old system there, so can you go with 409a? Or hotshot maybe, so you can stick with mineral oil?
    Otherwise switch to 134a. Be...
  13. Replies
    3
    Views
    240

    LOL! Sent from my SM-G950U using Tapatalk

    LOL!

    Sent from my SM-G950U using Tapatalk
  14. Replies
    3
    Views
    240

    [emoji106]What will you be learning? Sent from...

    [emoji106]What will you be learning?

    Sent from my SM-G950U using Tapatalk
  15. Replies
    50
    Views
    1,263

    Did you try switching the pumps or is that not...

    Did you try switching the pumps or is that not feasible here?

    Sent from my SM-G950U using Tapatalk
  16. Replies
    50
    Views
    1,263

    Switch the pumps. What happens? Does it follow...

    Switch the pumps. What happens? Does it follow the questionable pump?

    Sent from my SM-G950U using Tapatalk
  17. Thread: Trane aud issue

    by icy78
    Replies
    7
    Views
    296

    Trane will refer you to your local service...

    Trane will refer you to your local service provider.

    Sent from my SM-G950U using Tapatalk
  18. Replies
    31
    Views
    640

    Curious...where is this cavitation possibly...

    Curious...where is this cavitation possibly happening? In the coil after the 2-way? Flashing from the sudden pressure drop?

    How does vena contracta function in a small pipe?

    What is 'recovery...
  19. Replies
    56
    Views
    1,962

    225 is too close. That's 300 at the valve. Oil...

    225 is too close. That's 300 at the valve. Oil cooking territory.
    I dont like over 200 either. VERY rarely do I leave something running at over 200f DLT.
    Rarely do I see over 195 on the stuff I...
  20. That's a tiny MUA. Probably everyone was...

    That's a tiny MUA.
    Probably everyone was thinking at least 6-12000 cfm.
    Also, are you sure it doesnt use some return air?
    Altho 1500 18 is only about 80cfm per apartment, so it's probably sized...
  21. IMO, you need a good tech, who can also think...

    IMO, you need a good tech, who can also think like a mechanical engineer.
    Or a good mechanical engineer, who has a tech who can make the ME's design work properly.

    Sent from my SM-G950U using...
  22. It needs to be looked at by someone who can "see"...

    It needs to be looked at by someone who can "see" the whole building picture. Mechanical as well.
    Small MUA savings realized by lower MUA cfm and temperature may become big building $ losses in a...
  23. Replies
    56
    Views
    1,962

    Haha! Maybe I ment , Coogs, has tons of info....

    Haha! Maybe I ment , Coogs, has tons of info.
    Thanks[emoji3][emoji106]

    Sent from my SM-G950U using Tapatalk
  24. Replies
    56
    Views
    1,962

    Googs has tons of info too. John Tomczak can...

    Googs has tons of info too.
    John Tomczak can explain it well.
    You should know about it and measure it. IMO.


    Sent from my SM-G950U using Tapatalk
  25. Replies
    19
    Views
    1,012

    That thing is probably 2 stage? It might be under...

    That thing is probably 2 stage? It might be under fired and causing condensation and rust.

    Or the return air is too cold or too much outside air making the return are too cold. Or it's a...
  26. Replies
    20
    Views
    615

    Back drafts can happen sometime/anytime, during...

    Back drafts can happen sometime/anytime, during the 99.99999% that you're not standing there.

    The nature of drafthoods/draft, dictates that.

    Lazer thermometers are only as accurate as the...
  27. Replies
    2
    Views
    268

    A guy I sort of know went. 2 days, hands on, 1...

    A guy I sort of know went. 2 days, hands on, 1 day of intelligen. (About 6 hours he said.)
    I've done 1 Intelligen system. Pretty nice.
    He said you learn some really handy tricks you may not know...
  28. Replies
    20
    Views
    615

    How was the downdraft issue corrected? Sent...

    How was the downdraft issue corrected?

    Sent from my SM-G950U using Tapatalk
  29. Replies
    2
    Views
    268

    Heatcraft intelligen

    Anybody here take the Heatcraft 2 day class on QRC/BEACON/INTELLIGEN?

    Is the test after only on Intelligen, or Beacon and QRC also?

    Sent from my SM-G950U using Tapatalk
  30. Replies
    20
    Views
    615

    What rundawg said. Sent from my SM-G950U using...

    What rundawg said.

    Sent from my SM-G950U using Tapatalk
  31. Replies
    20
    Views
    615

    Great points! Also, were all other appliances...

    Great points!

    Also, were all other appliances gas valves off at clocking time?

    And, it's hard to be accurate with single point readings.

    Sent from my SM-G950U using Tapatalk
  32. Replies
    20
    Views
    615

    You should try getting a reading at the first...

    You should try getting a reading at the first grille. Or after a few duct turns. Mix the air a bit.

    Sorry kdean1, we posted at the same time. I agree, do the things that you said.

    Sent from my...
  33. Replies
    19
    Views
    1,012

    I don't think they go bad without being subjected...

    I don't think they go bad without being subjected to abnormally high heat though. It may not be enough to trip it for a few years but enough to weaken it.
    So there would still be an underlying...
  34. Replies
    11
    Views
    758

    I'm betting on a flowcheck issue. Have a look...

    I'm betting on a flowcheck issue.
    Have a look inside it.

    Sent from my SM-G950U using Tapatalk
  35. Replies
    10
    Views
    450

    Tons of iron and manganese. Boiler no like. ...

    Tons of iron and manganese.
    Boiler no like.

    Sent from my SM-G950U using Tapatalk
  36. Replies
    19
    Views
    1,012

    Possible Burner misalignment. Sent from my...

    Possible Burner misalignment.

    Sent from my SM-G950U using Tapatalk
  37. Replies
    8
    Views
    595

    ^^^^ X2, sounds like you're doing a board...

    ^^^^
    X2, sounds like you're doing a board reset.
    Run the cooling and look for issues.

    Sent from my SM-G950U using Tapatalk
  38. Replies
    4
    Views
    354

    That's no fun Terry! Getting New tools IS...

    That's no fun Terry!
    Getting New tools IS fun![emoji846]

    Sent from my SM-G950U using Tapatalk
  39. Replies
    9
    Views
    398

    When it shuts off is it also shutting some type...

    When it shuts off is it also shutting some type of solenoid on the glycol or Water.... whatever is in the floor, and is that what's causing a noise?

    Sent from my SM-G950U using Tapatalk
  40. Replies
    9
    Views
    409

    What is the application? What Chiller is it? It's...

    What is the application? What Chiller is it? It's possible that there are numerous settings to change.
    And as pecmsg said, it may be operating far outside its design.

    Sent from my SM-G950U using...
  41. Replies
    20
    Views
    784

    Give it a few years PHM. There will be a list...

    Give it a few years PHM. There will be a list like that for Trump. (like there is for every president).

    They all have to play the same game , they all have to bow to the same lords ,and some of...
  42. Replies
    7
    Views
    582

    Turns out it's not quite linear. But very close....

    Turns out it's not quite linear. But very close. Using slip percentage of motor. About 2.2% for 1800rpm motor with 1760rpm label.
    40 1800 =2.2%
    30 hz =50% of 60hz =17602=880
    880- 2.2%=861

    So...
  43. Thread: Fun

    by icy78
    Replies
    13
    Views
    1,200

    If your customers are artists, they probably have...

    If your customers are artists, they probably have shows around your furnace and hydronic work!
    It's a beautiful thing!

    Sent from my SM-G950U using Tapatalk
  44. Replies
    7
    Views
    582

    Ah interesting. Can you explain? It's not...

    Ah interesting. Can you explain?
    It's not linear, or is it?
    30hz is rpm of 60?

    Sent from my SM-G950U using Tapatalk
  45. Replies
    7
    Views
    582

    Bluetooth tach with a homemade bracket . clamp...

    Bluetooth tach with a homemade bracket .
    clamp it on close the door take your reading.

    Sent from my SM-G950U using Tapatalk
  46. Thread: Mixing of oils.

    by icy78
    Replies
    14
    Views
    1,057

    Just did an 06E from 22 to 407C. Carlisle wants ...

    Just did an 06E from 22 to 407C.
    Carlisle wants 30% POE.
    RTU 50ton. Theres only mineral oil in there right now. Returning like a champ. But, I disabled it now till next spring. Want to watch it...
  47. Replies
    24
    Views
    1,539

    Hmmm. Good point. But if the unit stages the...

    Hmmm. Good point.

    But if the unit stages the compressors/unloaded to meet supply air STPT too aggressively...itll still be too low cfm.

    Dont know if its done in Carrier algorithm or BAS .
    ...
  48. Replies
    24
    Views
    1,539

    Yes, I calibrated the static sensor but ended up...

    Yes, I calibrated the static sensor but ended up with a new one. It at least worked, but still off by 0.4".
    Found in config that someone selected 0-3 " sensor range. But these are 0-5". Changed that...
  49. Replies
    26
    Views
    1,271

    Thanks pagey! I mis-remembered...

    Thanks pagey!
    I mis-remembered again[emoji53][emoji846]

    Sent from my SM-G950U using Tapatalk
  50. Thread: Simple 80%er

    by icy78
    Replies
    15
    Views
    1,215

    What draft did you measure? What were the...

    What draft did you measure?
    What were the combustion numbers?
    Sent from my SM-G950U using Tapatalk
Results 1 to 50 of 1000
Page 1 of 20 1 2 3 4