    at 1740 nominal tons, my guess is that you have...

    at 1740 nominal tons, my guess is that you have around 3500 lbs of R123. at 0 psig (82.08F sat) you have about 290 gallons of liquid refrigerant and 9 gallons of oil...it does not take much...
  2. Thread: Trane heater

    by jayguy
    Replies
    18
    Views
    3,564

    1. what is the oil level when the chiller is off...

    1. what is the oil level when the chiller is off and the heaters are on?
    2. what temperature is the oil sump when the chiller is off and the heaters are on?