  1. Thread: No Ground?!?

    by FieldGen3
    Replies
    8
    Views
    895

    Yea Iíll call and see what they say. I measured...

    Yea Iíll call and see what they say. I measured 650 ohms between the switch terminals and the toggle so 0.18 amps of current that I took. It probably wouldnít have tripped a breaker but given an...
  2. Thread: No Ground?!?

    by FieldGen3
    Replies
    8
    Views
    895

    I'm pretty sure it came this way. I remember when...

    I'm pretty sure it came this way. I remember when the unit was purchased and as far as I know I'm the only one who's worked on it. To follow up, the short was in the drain valve bypass switch itself....
  3. Thread: No Ground?!?

    by FieldGen3
    Replies
    8
    Views
    895

    The pressure switch box is not bonded... it would...

    The pressure switch box is not bonded... it would be if they used metal conduit. The pressure switch box is mounted to a brass manifold via the pressure switches themselves which are not metal.
  4. Thread: No Ground?!?

    by FieldGen3
    Replies
    8
    Views
    895

    Sorry for the small image... here's the original...

    Sorry for the small image... here's the original

    I'm looking for a ground wire in there because had there been one I wouldn't have been shocked when using the drain bypass switch. That was before...
  5. Thread: No Ground?!?

    by FieldGen3
    Replies
    8
    Views
    895

    No Ground?!?

    Why is there no Ground wire in the pressure switch box of Market Forge M36G Boiler?
  6. Replies
    8
    Views
    1,432

    Thank you everyone for the input. Looks like...

    Thank you everyone for the input. Looks like there is a consensus on Cleveland. I am concerned about the high failure of the actuator that ECtofix mentioned. I had to replace the one on the Groen and...
  7. Replies
    8
    Views
    1,432

    Tilt skillets: What's your favorite brand?

    Replacing a Groen NHFP(E)-4. Wondering what brand I should suggest from a maintenance and service point of view.
  8. Replies
    2
    Views
    3,680

    Thanks, that makes sense. This building does a...

    Thanks, that makes sense. This building does a lot of generator testing.
  9. Replies
    2
    Views
    3,680

    Hobart hl200 alarm codes

    Looking for a link or PDF of the alarm codes for Hobart mixer model hl200, serial 31-1431-718, ml 134457. Complaint was flashing LU. Unit was unplugged when I arrived. Unit works fine now and I never...
  10. Replies
    5
    Views
    1,275

    Just because I was in an extra special ticked off...

    Just because I was in an extra special ticked off mood I told my boss I wouldn't start it up until he had one of the electricians change the gfi outlet to a non gfi and install a ground fault...
  11. Replies
    5
    Views
    1,275

    Ice is a right, not a privilege!

    I can't stand office workers. Lazy, fat, a-holes that spend the majority of their day complaining about something.

    -"I'm too hot but the girl in the cube next to me is too cold. Can you turn up...
  12. Replies
    10
    Views
    3,844

    Yea I'm using part 47, and it's all in the right...

    Yea I'm using part 47, and it's all in the right direction. Looking closer at the newer version they changed part 47 "rod-hub" to part 29 "lever-drive" and part 43 "slider-rod" is now part 31 "arm...
  13. Replies
    10
    Views
    3,844

    Hobart CLPS86E conveyor drive problems

    Hobart CLPS86E
    Serial 85-1073933
    ML 138176

    A little history... This machine burnt the conveyor drive motor. My best guess of what happened was a snowball effect starting with the screw and...
  14. Replies
    21
    Views
    2,633

    Was it a turbo-air? I saw one like that once. I...

    Was it a turbo-air? I saw one like that once. I hated that unit.
  15. Replies
    29
    Views
    3,715

    How do I get a master crimper license? Seems like...

    How do I get a master crimper license? Seems like a sweet gig.
  16. Replies
    34
    Views
    2,519

    Flux coated

    Flux coated
  17. Replies
    7
    Views
    1,154

    Hoshi dcm270-bah needs auger and evap

    Inspecting this ice machine and I could feel the play in the upper bearing, no need for pin gauge. Removed the auger and at first glance it looked ok. I shine a light down the evap and low and behold...
  18. Replies
    0
    Views
    474

    Hoshi dcm270-bah needs auger and evap

    Inspecting this ice machine and I could feel the play in the upper bearing, no need for pin gauge. Removed the auger and at first glance it looked ok. I shine a light down the evap and low and behold...
  19. Replies
    34
    Views
    2,519

    45%

    45%
  20. Replies
    29
    Views
    3,715

    Thanks, this is what I was looking for.

    Thanks, this is what I was looking for.
  21. Replies
    29
    Views
    3,715

    This is exactly what I need them for, failed...

    This is exactly what I need them for, failed start components. I need a cheaper way to adapt a 3 N 1. The quick lugs are too expensive. I could butt splice the 1" lead from the overload, but I...
  22. Replies
    29
    Views
    3,715

    I run into the round pins more often but I'll...

    I run into the round pins more often but I'll take take either or both of you got them.
  23. Replies
    29
    Views
    3,715

    Crimp on terminals for fractional HP

    I'm looking for the solderless terminal connectors that will fit compressor terminals. I'm currently using the brass terminal repair kits, but it seems like overkill. Part number or link appreciated.
  24. Replies
    15
    Views
    2,938

    To answer some of the other questions, you do...

    To answer some of the other questions, you do need a water seal if you plan to pull the auger. I had the same model with 1/16" of scale. I soaked the auger in a bucket of cleaner overnight and that...
  25. Replies
    14
    Views
    2,515

    This unit is so not worth re-engineering with...

    This unit is so not worth re-engineering with txv' and or solenoids. I'm on ball with the recover and recharge. It'll have to wait until Monday though. Merry Christmas everyone.
  26. Replies
    14
    Views
    2,515

    Air entering condenser is 72, SH 37. New...

    Air entering condenser is 72, SH 37. New complaint but to be honest I don't know if anything has changed. The user happened to come in that morning to stock product during defrost. The thermometer on...
  27. Replies
    14
    Views
    2,515

    The only evap fan is running the right direction,...

    The only evap fan is running the right direction, no ice on coil, good airflow imo.
  28. Replies
    14
    Views
    2,515

    Flood back during off cycle?

    Turbo air M# TOM-40MB S#TMM4017Y011 (open air cooler 404a cap tube)
    Product barely keeping temp, 40 - 41 and creeps to 45 during defrost. This was the only real complaint.

    5 mins into cycle......
  29. Replies
    5
    Views
    1,810

    Thanks for the replies. I'll recommend Cleveland...

    Thanks for the replies. I'll recommend Cleveland for the new equipment.
  30. Replies
    5
    Views
    1,810

    Steamer recommendation

    I'm looking to replace a 200,000 BTU's/hr input, natural gas steamer with a kettle take off. I want to have a separate kettle and steamer. What's your opinion on the different brands from a...
  31. Replies
    0
    Views
    572

    True TR2RRT-2S-2S

    Looking for a wiring diagram. Anybody have one?
  32. Replies
    3
    Views
    2,510

    Thanks for the suggestion. Yea I have been to...

    Thanks for the suggestion. Yea I have been to Alto shaam site and even called them to ask what they use. The tech support lady couldn't give me an exact part number but we were on the same page as...
  33. Replies
    3
    Views
    2,510

    Hose help please

    Hey guys, I need help finding a flexible water supply hose for a new Alto-Shaam CTP7-20E install. My lines will be 3/4" copper and the fitting on the machine is 3/4" MGHT stainless. Manufacturer...
  34. Thread: WTF Randell

    by FieldGen3
    Replies
    28
    Views
    4,706

    Agreed... Been running a few days now with no...

    Agreed... Been running a few days now with no problems.
  35. Thread: WTF Randell

    by FieldGen3
    Replies
    28
    Views
    4,706

    Update: based on the feedback I think this unit...

    Update: based on the feedback I think this unit was some sort of custom install. There are quick connects to separate the drop in cold pan (I called it a cold rail before) Yes the cold pan was...
  36. Thread: WTF Randell

    by FieldGen3
    Replies
    28
    Views
    4,706

    This unit has a cold rail.

    This unit has a cold rail.
  37. Thread: WTF Randell

    by FieldGen3
    Replies
    28
    Views
    4,706

    Heck if I know, but I'm guessing it is still at...

    Heck if I know, but I'm guessing it is still at the factory
  38. Thread: WTF Randell

    by FieldGen3
    Replies
    28
    Views
    4,706

    WTF Randell

    Salad bar cooler no worky. "Oh you're here to fix that thing? I've worked here for two years and it's never worked." Out of gas, schrader bubbles, tighten, vac and charge. It worky now. Only now it...
  39. Replies
    3
    Views
    2,479

    The temp control is definitely a knob and yes it...

    The temp control is definitely a knob and yes it is soldered directly to the control panel board. I think you answered my question I was just hoping it was a $20 chip vs a $2k+ board.
  40. Replies
    3
    Views
    2,479

    First time on Groen CC20-E

    We have a Groen Model# CC20-E Serial# C8948MS with an unresponsive cook temp control. I ran the diagnostics and when I get to the part where I have to turn the temp control knob one click at a time...
  41. Replies
    9
    Views
    1,393

    We have six like units in service. Typically if...

    We have six like units in service. Typically if one goes down and needs an extensive repair we swap the head out with a spare for as little down time as possible. Considering the parts removed I'm...
  42. Replies
    9
    Views
    1,393

    It would be rebuilt as a spare and it would...

    It would be rebuilt as a spare and it would definitely get new refrigerant when it is put back into service, but I would have a harder time ensuring multiple drier changes once it was. Maybe I can...
  43. Replies
    9
    Views
    1,393

    Resurrecting Ice-o-Matic

    We have an old ice-o-matic that was abandoned sitting in the back of our shop. I think it's an ICE1007HR, 404a, 208 3PH. It's been sitting there for 6+ months with the evaporator, txv and drier...
  44. Replies
    32
    Views
    9,484

    If a puller isn't available and turning the shaft...

    If a puller isn't available and turning the shaft doesn't free it, I try pushing the blade towards the motor and then sanding the area was the hub met the shaft.
  45. Replies
    23
    Views
    4,103

    Has anybody had luck using an ETC in this...

    Has anybody had luck using an ETC in this application? Jamb the sensor in the coil, set-point 18, diff 19. You might be able to experiment with the set-points and find a sweet spot.
  46. Replies
    12
    Views
    2,270

    Doesn't it suck in a bunch of air while you do...

    Doesn't it suck in a bunch of air while you do that? Even if you run the vacuum longer after the switch why not avoid introducing non-condensables by making the switch while still positive? Or you...
  47. Replies
    12
    Views
    2,270

    How are you removing your liquid line hose while...

    How are you removing your liquid line hose while the unit is under vacuum?
  48. Thread: condenser

    by FieldGen3
    Replies
    2
    Views
    964

    http://www.cpsproducts.com/images/products/xs/MT69...

    http://www.cpsproducts.com/images/products/xs/MT69_CPS-molecular-transformator-recovery_31.jpg

    Made me think of this... But google disagrees
  49. Replies
    133
    Views
    16,766

    Thanks for all the feedback. I agree that...

    Thanks for all the feedback. I agree that subcooling as a charging method on systems with a receiver is useless.
  50. Replies
    4
    Views
    5,064

    I need a rig that can fit in the bottom section...

    I need a rig that can fit in the bottom section of a rack and hoist out a 2 hp semi with only 2 foot clearance or less.