Search:

Type: Posts; User: black_syphilis

Page 1 of 5 1 2 3 4

Search: Search took 0.09 seconds.

  1. Replies
    4
    Views
    174

    Yes it's the same. I'm waiting Lon integration...

    Yes it's the same.
    I'm waiting Lon integration document from technical support since 4 days...
  2. Replies
    4
    Views
    174

    Gentec sell Kameleon to Cristal Controls but...

    Gentec sell Kameleon to Cristal Controls but Cristal Controls doesn't know LON model. :beat:
  3. Replies
    4
    Views
    174

    Gentec Lon integration

    Hi,

    On site I have Gentex lighting panel Kameleon K8.
    I need to integrate through LON in Niagara AX.

    For example there is some function (scRecall, scLearn, etc) but not information about this....
  4. Replies
    25
    Views
    1,047

    I'm totally agree with you, hardware is not the...

    I'm totally agree with you, hardware is not the best ever but it's working and EasyIO continue to improve it.
    I understand EasyIO controller is not bullet proof like a DX9100 :patriot: but it's not...
  5. Replies
    25
    Views
    1,047

    Yes EasyIO hardware need improve but what can we...

    Yes EasyIO hardware need improve but what can we do? Just cry to EasyIO and with time products will be more and more awesome! I used first model of FG model and it was really baad but now it's a...
  6. Replies
    25
    Views
    1,047

    Yes it's possible to remove sedona password,...

    Yes it's possible to remove sedona password, manipulation is not userfriendly but if integrator change ALL default password so it's more complexe. It's between velvet rope barrier and steel wall.
    ...
  7. Replies
    25
    Views
    1,047

    Password? Talking about web access or sedona...

    Password? Talking about web access or sedona program? Both of case you can reset them
  8. Replies
    25
    Views
    1,047

    EasyIO is open but not too open so it's not...

    EasyIO is open but not too open so it's not possible to work in low level.
    I'm using EasyIO products since 5-6 years.

    I know where EasyIO need improve but I need feedback from other integrator....
  9. Replies
    25
    Views
    1,047

    EasyIO new features

    Hi,

    We are working to improve EasyIO controller features!
    Like many people knows controllers like FS model are really powerful but EasyIO doesn't use all this power.
    We want to use this power...
  10. Replies
    1
    Views
    294

    Hi, You need to send an email to technical...

    Hi,

    You need to send an email to technical support psotechsupport(at)jci.com, they will send you a link to JCI Sharepoint.
  11. Do you see these values in network? Sound like...

    Do you see these values in network? Sound like point are in error (comm, stale)
  12. Replies
    4
    Views
    345

    or you can write a program to change flags and...

    or you can write a program to change flags and execute it through px button
  13. Replies
    4
    Views
    345

    You can use BatchConfigFlagsTool from...

    You can use BatchConfigFlagsTool from vykonProUtil to hide and unhide slots but no idea to use it through button on px
  14. Replies
    2
    Views
    335

    No success. I uninstall SET, follow instruction...

    No success.
    I uninstall SET, follow instruction from pnet-DrT to delete crypkey. Try to reinstall SET but always license check failure.
    Weird think, under ProgramData/CrypKey I haven't licenses...
  15. Replies
    11
    Views
    400

    Sometime I have some controllers lost time. I...

    Sometime I have some controllers lost time.
    I looking for a solution to send time through a button on px, I don't want operators play under bacnet network interface.
    Through local device it's a...
  16. Replies
    11
    Views
    400

    No way to send to all bacnet device without...

    No way to send to all bacnet device without enter all device in time sync recipients? I have many device to synchronize
  17. Replies
    11
    Views
    400

    Niagara BACnet auto TSync

    Hi,

    Is there a way to send periodically a time sync to BACnet device? Or create a button on px to send time sync?

    Thanks
  18. Replies
    2
    Views
    347

    Hi, you have CSV driver to parse CSV files or...

    Hi,

    you have CSV driver to parse CSV files or you can program it if you know java
  19. Replies
    2
    Views
    335

    Trend SET install

    Hi,

    I installed SET 7.60 on fresh new computer under W10 x64 (no VM) but I can't launch it, on SET splash screen I have these information

    https://i.imgur.com/vuOHdjj.png...
  20. I confirm, you need ILC Spyder or Honeywell...

    I confirm, you need ILC Spyder or Honeywell license to program Spyder and like said Orion, I hope for you there is Spyder backup, first time I uploaded Spyder and saw program I puke on my laptop.
  21. Replies
    0
    Views
    196

    Delta Controls variable transfer

    Hi,

    I need to transfer variable from eBCON to DSC

    In my xfer program I have these variable
    'XFER SY_VE1 BP_H1 ETAT' = '30000.SY_VE1 BP_H1 DEM'
    'XFER SY_VE1 BP_H2 ETAT' = '30000.SY_VE1 BP_H2...
  22. Replies
    2
    Views
    433

    Not sure is the good place to ask hack question...

    Not sure is the good place to ask hack question :whistle:
    I hacked SET and 963 crypkey few years ago (just for fun :angel:). With SET >7 Trend update crypkey and my code is obsolete. I checked and...
  23. Replies
    4
    Views
    496

    Application: 3.40 firmware: 189697 Yes Vykon...

    Application: 3.40
    firmware: 189697

    Yes Vykon 4.9
  24. Replies
    4
    Views
    496

    All is good on my side with Delta controllers ...

    All is good on my side with Delta controllers (3.4)
  25. Replies
    72
    Views
    25,034

    Did you install vykon service?

    Did you install vykon service?
  26. Replies
    0
    Views
    202

    KMD backup problem

    Hi,

    I have KMD network (KMD-5831 and KMD-7001), I'm using KMC Connect.
    When I try to make a backup I have this error for all controllers

    https://i.imgur.com/xUja97e.png

    I don't find where...
  27. Replies
    11
    Views
    849

    and your DFM-440 using linknet protocol but it...

    and your DFM-440 using linknet protocol but it will be transparent during your integration, all I/O variables are in your DSC
  28. Replies
    11
    Views
    849

    E = Ethernet version without E = MSTP

    E = Ethernet version
    without E = MSTP
  29. Replies
    11
    Views
    849

    All Delta controllers are BACnet native so you...

    All Delta controllers are BACnet native so you can integrate with Niagara for example, also I recommend to keep DSM-RTR.
  30. Replies
    15
    Views
    986

    I put 50 threads! I create different tuning...

    I put 50 threads! I create different tuning policies and bysi time is around 82% and continue to increase slowly

    https://i.imgur.com/lagcowL.png

    https://i.imgur.com/Ezxz0bl.png

    I can't...
  31. Replies
    3
    Views
    251

    Can you send Application Director output

    Can you send Application Director output
  32. Replies
    15
    Views
    986

    I have just one network card, I can't have...

    I have just one network card, I can't have another ipPort for other BACnet port.
  33. Replies
    15
    Views
    986

    It's a supervisor not a Jace. All MSTP device are...

    It's a supervisor not a Jace. All MSTP device are through router (delta and contemporary)
  34. Replies
    15
    Views
    986

    I adjust rate to 2min and put 10 threads, after a...

    I adjust rate to 2min and put 10 threads, after a restart busy time is always near of 100% and point count is always very high.
    Which tuning policies parameters recommand me for setpoint and input ?...
  35. Replies
    15
    Views
    986

    N4.8 BACnet slow pool

    Hi,

    I have supervisor 4.8 with 147 BACnet device (Delta, Distech, EasyIO). Polling is really slow like more 30min to refresh value.
    This is my configuration

    https://i.imgur.com/NlMcEZL.png...
  36. Replies
    7
    Views
    627

    So we can put a resistor in parallel, what kind...

    So we can put a resistor in parallel, what kind of resistor, minimum 1W I think and resistance?
  37. Replies
    7
    Views
    627

    We tried with relay and it's working fine. So...

    We tried with relay and it's working fine.
    So triac module need to be replace?
  38. Replies
    7
    Views
    627

    We are using DO1

    We are using DO1
  39. Replies
    7
    Views
    627

    Duct heater control problem

    Hi,

    I have some ECB-VAV (x18), they are controller duct heater Thermolec D21-PSSR in 24V pulse (edge is cut).
    I have probelm with 4 of them, I send 100% and triac starting to pulse but if I send...
  40. Replies
    2
    Views
    250

    Perfect thank you

    Perfect thank you
  41. Replies
    2
    Views
    250

    Trend SET license transfer

    Hi,

    I try to transfer SET license using Transfer function, but I have this error message
    https://i.imgur.com/2jOf9Wi.png

    Any idea?

    Thanks
  42. [N4.8] Distech point discover error

    Hi,

    I have ECB controllers under N4 supervisor.
    All device are under bcpBacnetNetwork, when I try to make a point discover I have an many error

    https://i.imgur.com/BYymnPq.png

    But through...
  43. Replies
    1
    Views
    286

    N4 schedule batch modification

    Hi,

    I need to modify many schedule with same hours, I tried to change them with programService but don't find correct slot to change (effective slot)?

    Anyone have an idea?

    Thanks
  44. Replies
    1
    Views
    267

    Problem found. Need to put some files under...

    Problem found.

    Need to put some files under Bcp folder
  45. Replies
    1
    Views
    267

    N4 Distech error log

    Hi,

    I have a jace (4.8) and Distech devices (MSTP).
    I have this error when I discover and try to add points


    WARNING [13:47:08 22-May-20 EDT][bacnet] Unable to load Bacnet Object Types from...
  46. Replies
    24
    Views
    2,940

    JSON Toolkit with 4.8 :cheers: Amazing news!...

    JSON Toolkit with 4.8 :cheers:
    Amazing news!
    I'll try right now:putergreet:
  47. Replies
    0
    Views
    278

    N4.8 multi station saving bug

    Hi,

    I'm running a Jace 4.8 and there is a bug with automatic saving station

    https://imgur.com/ufdZhIS.png

    https://i.imgur.com/44mBVtG.png

    To resolve this problem I must disable...
  48. Replies
    7
    Views
    600

    Under your BACnet network, you have a TSynch...

    Under your BACnet network, you have a TSynch button
  49. :couch:

    :couch:
  50. Replies
    7
    Views
    600

    HI, you need to send time sync through your...

    HI,

    you need to send time sync through your workbench
Results 1 to 50 of 238