  1. Replies
    5
    Views
    414

    It definitely is integrated as they are generator...

    It definitely is integrated as they are generator points. There's definitely something odd going on here in general. They are COV trends. The only reason these are changing state and reporting is...
  2. Replies
    3
    Views
    215

    If it's a PDF I use bluebeam if it's a .dwg I use...

    If it's a PDF I use bluebeam if it's a .dwg I use AutoCAD. There are a lot of free programs out there to do the same. I just have access to the paid ones.

    Sent from my Pixel 5 using Tapatalk
  3. Replies
    5
    Views
    414

    The point is failed. There's a flowchart after...

    The point is failed. There's a flowchart after that. Could be loose wires, a bad sensor, the panel losing comms, etc. Next is troubleshooting.

    Sent from my Pixel 5 using Tapatalk
  4. Replies
    7
    Views
    467

    Actually you don't need a panel, the server can...

    Actually you don't need a panel, the server can do it itself, but it's pretty unreliable with the points then being a pull.

    Sent from my Pixel 5 using Tapatalk
  5. Replies
    7
    Views
    467

    Crosstrunk is absolutely in Desigo, and you...

    Crosstrunk is absolutely in Desigo, and you should always push points between trunks. Probably will have to create virtual points, set them equal in PPCL and then push them.

    Sent from my Pixel...
  6. Replies
    7
    Views
    467

    Is Crosstrunk on? Sent from my Pixel 5 using...

    Is Crosstrunk on?

    Sent from my Pixel 5 using Tapatalk
  7. Not sure why you think it's crazier. Desigo CC...

    Not sure why you think it's crazier. Desigo CC and Datamate Advanced bind the ports they use to the application. Most applications do this. So if one application binds that particular port on an...
  8. Nope, only one management station can use the...

    Nope, only one management station can use the ports of an AEM. So if you want both DMA and DCC connected at the same time you need 2.

    Sent from my Pixel 5 using Tapatalk
  9. Incorrect, both can be on the same machine. You...

    Incorrect, both can be on the same machine. You just need a 2nd AEM if you have P2 BLNs

    Sent from my Pixel 5 using Tapatalk
  10. Well the transformer is in the bottom left and it...

    Well the transformer is in the bottom left and it does come up to the module common and ground terminals. So there's that.

    Sent from my Pixel 5 using Tapatalk
  11. Look for dma or job editor Sent from my Pixel...

    Look for dma or job editor

    Sent from my Pixel 5 using Tapatalk
  12. Yep, that's why I said follow the diagram. I...

    Yep, that's why I said follow the diagram. I also almost guarantee that this isn't done on the PCB and has to be physically wired together.

    Sent from my Pixel 5 using Tapatalk
  13. This is basic electrical practices. If you don't...

    This is basic electrical practices. If you don't have the same ground reference, you have improper voltages. If you don't bond your transformers, you're asking for things to not work, and fail.
    ...
  14. You would very likely have a floating neutral on...

    You would very likely have a floating neutral on the DDC devices. I've seen it cause everything from temperatures being off to actuators that don't fully open or close. I've also seen it do nothing...
  15. Go to the upper right drop down and select about...

    Go to the upper right drop down and select about pagehttps://uploads.tapatalk-cdn.com/20210506/0d33633846820e5933353ea152eda65d.jpg

    Sent from my Pixel 5 using Tapatalk
  16. Yes it does. It's Insight on steroids, but with...

    Yes it does. It's Insight on steroids, but with no graphics, or commander.

    Sent from my Pixel 5 using Tapatalk
  17. If you can find it, it will work. It is...

    If you can find it, it will work. It is absolutely a controlled program though. It has the exact same EULA as Insight.

    Sent from my Pixel 5 using Tapatalk
  18. Long story short, if it's not Desigo 4.2 or newer...

    Long story short, if it's not Desigo 4.2 or newer you are wasting your time. Prior to that, it was expected that Datamate Advanced or Insight was supposed to be installed for things like that.
    ...
  19. I'd call Daikin. While they are slow to get back...

    I'd call Daikin. While they are slow to get back to you, they are usually very helpful and stay with it until you're satisfied.

    Sent from my Pixel 5 using Tapatalk
  20. Replies
    13
    Views
    586

    I'd have a dozen or so years Industrial PLC...

    I'd have a dozen or so years Industrial PLC experience. It would cost $2000 to replace that with something way better. That PLC is garbage.

    Sent from my Pixel 5 using Tapatalk
  21. Replies
    8
    Views
    482

    This is much easier to do with DCC than it was...

    This is much easier to do with DCC than it was with Insight.

    Sent from my Pixel 5 using Tapatalk
  22. Replies
    8
    Views
    482

    If they don't have the information, tell them to...

    If they don't have the information, tell them to look in their knowledge base.

    Sent from my Pixel 5 using Tapatalk
  23. Replies
    8
    Views
    482

    Nothing is simpler anywhere else. It's just...

    Nothing is simpler anywhere else. It's just simpler because that's what you've learned.

    Siemens has always just trended points at a minute by minute interval and analyzed data with Excel or...
  24. Replies
    2
    Views
    332

    I've done a dozen boilers with Lochinvar...

    I've done a dozen boilers with Lochinvar controls. Unfortunately, you have to do the conversion yourself. That's straight from Lochinvar as well. You can change the HMI to Fahrenheit, however. ...
  25. You can have descriptive names if you add the...

    You can have descriptive names if you add the DXRs under an FLN. It solves both problems.

    Sent from my Pixel 5 using Tapatalk
  26. That's what you're supposed to do. Just make an...

    That's what you're supposed to do. Just make an FLN as IP routed under a Bacnet panel. Preferably the panel controlling the AHU for those DXRs

    Sent from my Pixel 5 using Tapatalk
  27. I always add the Bacnet IP devices as a separate...

    I always add the Bacnet IP devices as a separate FLN under a panel in system profile as IP (routed). That is actually a best practice. I'll take a screenshot later and upload it. I would also add...
  28. Or you could be condescending to try to win as...

    Or you could be condescending to try to win as well [emoji12]

    Sent from my Pixel 5 using Tapatalk
  29. Of course this is all dependent on having duct...

    Of course this is all dependent on having duct static pressure sensors 2/3 of the way down the duct. We have tremendous success with this current control on most of our units primarily because we...
  30. So if all the rooms go to minimum damper position...

    So if all the rooms go to minimum damper position and the static pressure stays the same, what do the VFDs do? Ramp down, and use less energy. This other method is over complicating it and relying...
  31. I agree, the idea of a floating SP setpoint...

    I agree, the idea of a floating SP setpoint doesn't make sense. If you want to save money on a variable, you should be doing it on flow. I think the reason for this wild SP idea is because people...
  32. Why don't you just do a point log report if that...

    Why don't you just do a point log report if that panel and filter for *dmpr cmd? You can save a custom report for each or you can setup a ReNo if one of the dampers stays at 100 for too long.
    ...
  33. I'll say it again, the DXR, by design, is made to...

    I'll say it again, the DXR, by design, is made to handle the energy savings. It is not a TEC. Stuck dampers and plugged flow tubes are not the fault of a DXR. The DXR uses the adaptive control...
  34. If they do not give you answers find out if this...

    If they do not give you answers find out if this is still under warranty or an Energy performance contract or RTEM. If it is, you simply let the customer and occupants know that things have to stay...
  35. The static pressure setpoint shouldn't change. ...

    The static pressure setpoint shouldn't change. The VAVs are supposed to control the environment in the end spaces.

    I can tell you for certain that with the information that you gave, the program...
  36. AHU static is almost always supposed to be on a...

    AHU static is almost always supposed to be on a loop statement. The fact it is not is more than likely due to some engineer and commissioning agent being naive. There is also the chance that the...
  37. Replies
    8
    Views
    259

    Very likely the site had it bought in their...

    Very likely the site had it bought in their contract and it just never was installed. That's the only way. I can tell you that they had zero wiggle room on it.

    Sent from my Pixel 5 using...
  38. Replies
    8
    Views
    259

    As a customer, the branch probably can't sell you...

    As a customer, the branch probably can't sell you Comm tool. They likely have to sell you Datamate. Besides, DMA 3.16 is pretty rock solid and exactly like Comm tool.

    Sent from my Pixel 5 using...
  39. Replies
    8
    Views
    259

    This is completely incorrect. Siemens corporate...

    This is completely incorrect. Siemens corporate stopped selling Insight 3.15 licenses or upgrades in September of 2018, and after a lot of complaining allowed them for a few months again in 2019 for...
  40. Replies
    4
    Views
    274

    With the dipswitches using binary coded decimal....

    With the dipswitches using binary coded decimal.

    Sent from my Pixel 5 using Tapatalk
  41. Replies
    7
    Views
    349

    You do not have to find the State text table. ...

    You do not have to find the State text table. You can command this point on/off just the same if you have it added to the P1 FLN and the points you need unbundled. I do this everyday and will be...
  42. Replies
    2
    Views
    360

    What type of point, P2 or Bacnet? What DCC...

    What type of point, P2 or Bacnet? What DCC revision? Have you looked in the help docs?

    Sent from my Pixel 5 using Tapatalk
  43. Replies
    7
    Views
    349

    Open system profile, add the drive if it's not...

    Open system profile, add the drive if it's not already, auto unbundle the point you want to command in application 2734 (abb) app and the subpoint will be added to the panel. Use that point name in...
  44. Replies
    21
    Views
    1,074

    You need the lservrc file from the old server. ...

    You need the lservrc file from the old server.

    Sent from my Pixel 5 using Tapatalk
  45. Fish the conduit with compressed air and a...

    Fish the conduit with compressed air and a string. There's plenty of videos on it.

    Sent from my Pixel 5 using Tapatalk
  46. Replies
    2
    Views
    304

    It will set pt2 and pt3 to the value of pt1 at...

    It will set pt2 and pt3 to the value of pt1 at NONE priority.

    If you want it to be a higher priority for a P2 panel there are stock priority levels you add at the beginning.

    If it's Bacnet...
  47. If you have 1 BLN, crosstrunk is not a factor. ...

    If you have 1 BLN, crosstrunk is not a factor. It sounds like you have a Nodename table issue.

    Sent from my Pixel 5 using Tapatalk
  48. I'm not sure it's a limitation honestly. Think...

    I'm not sure it's a limitation honestly. Think of it this way, data between trunks goes from the panel, to the server through a driver, and to the other panel. It would be silly to think the...
  49. The fact that pulling points ever worked was not...

    The fact that pulling points ever worked was not an intended practice. It's always supposed to be a push. To be fair (insert Letterkenny clip) it was most likely done prior to multiple trunks being...
  50. I'm not sure what documentation you want. ...

    I'm not sure what documentation you want. There's honestly not much available I'm allowed to share with you, and at that, the internal tech docs aren't a ton of help. Best advice I can give you is...