Search:

Type: Posts; User: Balibe

Page 1 of 17 1 2 3 4

Search: Search took 0.02 seconds.

  1. Thread: CCT 13.0 by JCI

    by Balibe
    Replies
    4
    Views
    324

    V13.0 is licensed to the computer versus older...

    V13.0 is licensed to the computer versus older versions. They need to contact their local distributor to get setup ......
  2. Replies
    28
    Views
    10,278

    No .... FieldLoader is Carrier Corp only, it also...

    No .... FieldLoader is Carrier Corp only, it also requires the config files in addition to the software to update/reload a controller. You can do a factory reset at the controller to restore to...
  3. Carrier has started using communicating actuators...

    Carrier has started using communicating actuators on their VAV controllers a couple years ago. They have started adding additional damper actuators & valves to the list of options. It is a separate...
  4. Replies
    1
    Views
    168

    The odd part is the Space Temp Prime Variable...

    The odd part is the Space Temp Prime Variable (AV:2007) is reading 80.0F. This is the controlling space temp the controller is using, not the System Space Temp (AV:1902) you are writing at 76.6F or...
  5. Can't send you a private message for some reason...

    Can't send you a private message for some reason and no email listed in your profile .....
  6. I have this pdf from a 4-5 years ago (attached)...

    I have this pdf from a 4-5 years ago (attached) when I integrated two of these, the file is from 2015. It was for the Smardt 200-300 ton indoor water cooled chiller with Kiltech controls. It was...
  7. Replies
    8
    Views
    191

    An i-Vu would be a better option over N4 as you...

    An i-Vu would be a better option over N4 as you are dealing with all Carrier devices. Just the install time that will be saved with i-Vu as the the program/graphic is stored in the controllers so...
  8. Replies
    8
    Views
    191

    You do not need an XT-RB/LB with a Standard or...

    You do not need an XT-RB/LB with a Standard or Plus, you can use the USB MS/TP Adapter to bring in the Carrier devices. A lot cheaper than a XT-RB .....
  9. My v3.2 is not readable, but my v3.1 is ... if...

    My v3.2 is not readable, but my v3.1 is ... if that helps, let me know .....

    FYI .... v3.2 is still available from Carrier without having to purchase the license key again since you have that. It...
  10. The Carrier ET3 are available to order since May...

    The Carrier ET3 are available to order since May 2022, not sure the availability. Since they had to move to a new manufacture supply chain last year, I hear thru the grapevine the new supply chain is...
  11. Sorry, our CD is a copy of the original created...

    Sorry, our CD is a copy of the original created in 2010. It is no longer readable, it will not copy to a disk or create an ISO ......
  12. Replies
    6
    Views
    301

    N4/AX will not discover N2 devices points, older...

    N4/AX will not discover N2 devices points, older UNT/FX, etc and newer PCG/V configured for N2. Need to use the prn file to create your points list in N4/AX for N2 devices. In CCT/PCT you can create...
  13. I heard the ST3 is in testing phase with the new...

    I heard the ST3 is in testing phase with the new manufacture of the ET3's. Hopefully soon, need something better than the ST1 .....
  14. Thread: CCT 14 Issue

    by Balibe
    Replies
    6
    Views
    520

    AFAIK you can only have one version on the...

    AFAIK you can only have one version on the PC/laptop. Recently went thru this as we had to tech out some existing bacnet VMA's for a customer. Instead of removing the v14 install on the tech's...
  15. My office found a v3.1 & v3.2 disk yesterday...

    My office found a v3.1 & v3.2 disk yesterday afternoon. They wont get to me till Monday or Tuesday so I can see if they are still readable to make an image. Keep ya updated ......
  16. That is the latest key, replaced the purple ones....

    That is the latest key, replaced the purple ones. The CVIEW 1 inscription I believes designates a single user key, it is also on a few purple keys I have.

    v3.2 used a different database than...
  17. Hopefully hvac69 can hook ya up, I would have to...

    Hopefully hvac69 can hook ya up, I would have to dig to find a copy. As long as you have a v3+ usb key (purple or brown) you will be fine with any v3+ install. They moved away from the parallel port...
  18. Replies
    10
    Views
    430

    There were issues with older revs of v3.7 that...

    There were issues with older revs of v3.7 that would cause poor performance and lockups. Make sure you are running latest version, which is 3.7.108. Not sure if v3.7.106 fixed them all .....
  19. Replies
    11
    Views
    583

    Check with support, their modules may only be at...

    Check with support, their modules may only be at v4.9. Their version does not have to match the N4 version as long as it is compatible. N4 v4.9 was the security change with 3rd party modules. Their...
  20. Replies
    19
    Views
    719

    Downgrade the supervisor to v4.7 to support the...

    Downgrade the supervisor to v4.7 to support the older AX's. Then update the older AX's over time as you can to support v4.7+. This will get you working, v4.7 is a stable version and will probably be...
  21. Replies
    19
    Views
    719

    Looks like security issues, v4.10+ increased...

    Looks like security issues, v4.10+ increased security and I have had issues with similar messages when connecting older an AX to v4.10. Have no issues with v4.7, I have v3.7 & v3.8 into v4.7. Are you...
  22. Update ..... sorry Kele does have an 8 output...

    Update ..... sorry

    Kele does have an 8 output sequencer, knew that had a 6 but didn't realize they also have an 8. You could order this in the 821C and have them setup the outputs to your...
  23. You could use two of the Kele UCS-421. The second...

    You could use two of the Kele UCS-421. The second one will work as slave to the 4-20mA signal on the first one. The 421E will need to be field step step as you need two, which may be better if you...
  24. Replies
    7
    Views
    963

    Yes, the USB thingy now works again with N4 v4.9...

    Yes, the USB thingy now works again with N4 v4.9 or higher. I have only tested in v4.9 and it was on a Trane Comm5 network. Be sure to install the latest OpenLDV 5 Driver from Echelon to be safe.
  25. Replies
    11
    Views
    583

    The watermark only shows up when the device...

    The watermark only shows up when the device (Jace/Server/Workbench) with BASSG modules is not licensed. You mentioned you updated the supervisor, did the HostID change? The BASSG licenses are tied to...
  26. Replies
    6
    Views
    394

    The firmware never fixed the pump algo, been an...

    The firmware never fixed the pump algo, been an issue since the beginning. In the mid 90's an independent contractor wrote a best to resolve the issue. Carrier started providing it, the original best...
  27. Replies
    6
    Views
    394

    The BEST++ is not tied to the CCN database, it...

    The BEST++ is not tied to the CCN database, it resides in the controller. If you had to RamFlush/Replace the controller, the BEST++ is no longer is no longer available unless you have the previous...
  28. Replies
    4
    Views
    523

    The E-Bus or hard-wired room sensor does not...

    The E-Bus or hard-wired room sensor does not write the setpoints, it is only an offset to the setpoints. The AI:48 will show the room sensor slide offset. AI:26 & AI:27 will show the effective...
  29. Replies
    7
    Views
    575

    This can be done in the installer tab, select the...

    This can be done in the installer tab, select the router/gateway & put in the address just like scanning a new device and i-Vu will update the tables.



    With CCN ..... If a file was created by...
  30. Replies
    7
    Views
    575

    Not sure why they did it this way, it goes back...

    Not sure why they did it this way, it goes back to the 203FID's in the early/mid 80's with DOS based NST & Building Supervisor. They moved the same logic to the Comfort Controllers and CView in...
  31. Replies
    31
    Views
    1,216

    Have you checked the firmware version of the...

    Have you checked the firmware version of the TEC's? JCI has updates, you may have an outdated firmware ......
  32. Replies
    7
    Views
    442

    Hopefully your admin access still works ........

    Hopefully your admin access still works ..... reset their passwords or restore to a previous backup before the issue .....
  33. Replies
    7
    Views
    575

    Most controllers can just be re-uploaded to your...

    Most controllers can just be re-uploaded to your database to reflect current controller database in CView/NSTV. The only controller you need to delete/reupload in CView is a UC16 (not a CC1600), NSTV...
  34. Replies
    8
    Views
    472

    Also can't programs to CC6400/1600's w/ i-Vu. Yes...

    Also can't programs to CC6400/1600's w/ i-Vu. Yes you can modify the existing algo's parameters, but cannot add & remove algo's. UC's are also a PITA, after you do a configuration change, the device...
  35. Replies
    6
    Views
    567

    Been awhile but it should be RTM Zone Temp, if I...

    Been awhile but it should be RTM Zone Temp, if I remember correctly the RTM is the main module verus the RA sensor that is wired to the ECEM board.

    Check the Temperature Input Status menu for...
  36. Replies
    6
    Views
    567

    In an Intellipak I or II, the sensor source needs...

    In an Intellipak I or II, the sensor source needs to be modified in the setup at the local display. It may be set to the RA Sensor.
  37. Replies
    3
    Views
    607

    Have not implemented on an RTU yet, but have on...

    Have not implemented on an RTU yet, but have on AHU's with chilled water & dx applications. I typically program the best I can to the attached documentation but have modified to meet the actual...
  38. Replies
    6
    Views
    524

    I have not dealt with CCN in N4, but a...

    I have not dealt with CCN in N4, but a shot/suggestion at the dart board. Is there anything in the Application Director with errors? You are upgrading from 4.7 to 4.10, 4.10 now requires sign...
  39. Replies
    8
    Views
    446

    When using 3113 I set the supervisor to only...

    When using 3113 I set the supervisor to only write on a change of value so it does not constantly write the flash memory. Typically it is FX Tridium with PCG's for me, I create a new tuning policy...
  40. Replies
    14
    Views
    787

    You can look into this as I have had a similar...

    You can look into this as I have had a similar issue .....

    The outputs on PCG are traic's, not relays. If there is not enough current draw on the PCG the triac is will open and or close.

    From...
  41. Replies
    79
    Views
    2,674

    It is a date code of the control program, which...

    It is a date code of the control program, which is explained in post #26. Did I not explain that correctly earlier or did you not read??

    Not our fault you don't know have the knowledge to work...
  42. Replies
    79
    Views
    2,674

    You need at least control program...

    You need at least control program vavb*_ws_iv6-2_06_20160810, this was noted in post 26. We are now to post 61 and you are stating you need a newer version than vavb*_zn_iv6-1_06_20160222 .....


    ...
  43. Replies
    79
    Views
    2,674

    If these are as old as the OP suggested with...

    If these are as old as the OP suggested with control programs from 2014, they are probably SPT sensors and not ZS sensors. These use a different logic block, not sure if the logic block is in the...
  44. Replies
    79
    Views
    2,674

    #1 .... add a UC and monitor fan status, static...

    #1 .... add a UC and monitor fan status, static pressure and supply air temp and setup linkage.

    the time is it going to take to update the control programs in 200+ probably gonna cost ya more in...
  45. Replies
    79
    Views
    2,674

    We are just trying to help ya. Sorry we don't...

    We are just trying to help ya. Sorry we don't make these controllers so be easy on us, I deal with them on a Carrier systems and not with third-party systems. I do not install these with a...
  46. Replies
    79
    Views
    2,674

    Linkage is a something Carrier has used since...

    Linkage is a something Carrier has used since early CCN days. It is built into all PIC controllers, just a matter of setting up the parameters. Once setup it will work with no supervisor needed as...
  47. Replies
    79
    Views
    2,674

    Are you integrating these into a 3rd-party...

    Are you integrating these into a 3rd-party front-end or using an i-Vu front-end? This makes a difference as these controllers can be integrated but they need to be setup properly with i-Vu/FA to work...
  48. Replies
    7
    Views
    510

    FYI ..... AX licensing for new licenses or...

    FYI .....

    AX licensing for new licenses or modifications to existing licenses ended in July 2021. AX licensing is currently available to maintain existing licenses. The AX licensing will be...
  49. Replies
    3
    Views
    636

    You are correct, you need to know the difference....

    You are correct, you need to know the difference. The curves are different, both are 77dF @ 10k but are different as the curve deviates. Type II is 19.9k @ 50dF, type III is 18.7k @ 50dF. The...
  50. Replies
    3
    Views
    375

    i-Vu front-end? If i-Vu, I have seen this issue...

    i-Vu front-end? If i-Vu, I have seen this issue before on random CCN controllers where one will not take changes form the front-end. Try this before you go diagnosing the setup. Redownload the ccn...
Results 1 to 50 of 822