Search:

Type: Posts; User: MaxBurn

Page 1 of 20 1 2 3 4

Search: Search took 0.05 seconds.

  1. Replies
    14
    Views
    349

    Anything listed as true online or double...

    Anything listed as true online or double conversion. They will not be the cheap ones, they generally aren't quiet or super efficient either because of the loss in turning power into DC and then back...
  2. Replies
    3
    Views
    88

    Did it through workbench?

    Did it through workbench?
  3. Replies
    14
    Views
    349

    If the power is especially bad I'd insist on a...

    If the power is especially bad I'd insist on a true online UPS as well. It does double conversion and the inverter is always powering the load from the DC. Very difficult for bad things to happen to...
  4. Are there T Taps in the comm? Are those by...

    Are there T Taps in the comm? Are those by themselves at an end of line? I'd likely start at the one stat you couldn't see anything at with the NSTV error light. Lift the comm wires from that unit...
  5. Replies
    3
    Views
    158

    I don't know much about niagara comm but I think...

    I don't know much about niagara comm but I think it needs to be bidirectional.

    Modbus doesn't though, that can write out just fine, slaves don't ever reach back.
  6. Pretty much any freeze stat should do this. We...

    Pretty much any freeze stat should do this. We use JCI.
  7. Yes, I've been seeing regular connections on my...

    Yes, I've been seeing regular connections on my honeypot from that part of the world. I haven't looked at the captures in detail lately though.
  8. Replies
    8
    Views
    324

    Interesting. We now have regular old CAT6 that...

    Interesting. We now have regular old CAT6 that can do 10GB from new tricks that have been learned but granted it halves the distance it can go vs 1G.
  9. Replies
    14
    Views
    349

    There is a memory leak that fills up the disk on...

    There is a memory leak that fills up the disk on older versions, so within your supported 3.8 channel you want to upgrade it as high as you can go. I think 3.8.401 or greater is where you want to be.
  10. Replies
    2
    Views
    113

    It can be done with most of the gateways I've...

    It can be done with most of the gateways I've seen. Just seems the BMS system uses BACnet natively as that's a rich language. Not really a difference in the gateway.
  11. Replies
    7
    Views
    341

    Sounds a little dangerous for these tester tools...

    Sounds a little dangerous for these tester tools to enable functionality like this and I can't think of when I've seen a feature like that in one. They don't have the relationships between equipment...
  12. Stop thinking about the product so much and focus...

    Stop thinking about the product so much and focus on who gives you the best service for your location. Then use what they prefer to deal with in your chosen subset.
  13. Replies
    6
    Views
    317

    So depending on what the LAN setup was the new...

    So depending on what the LAN setup was the new network will likely be on a different subnet from where the controllers are. BACnet BBMD and/or Foreign Device may need to be updated.
  14. Replies
    6
    Views
    317

    I'm not familiar with Envision but in this...

    I'm not familiar with Envision but in this industry seems like most software is tied to hardware somehow. I'd say you found the issue with that USB copier, might help if you had the original key too....
  15. Replies
    168
    Views
    10,919

    Still applicable; https://xkcd.com/927/ I...

    Still applicable; https://xkcd.com/927/

    I don't see a good way to get everyone on board with one thing. Too many conflicting interests.
  16. Replies
    168
    Views
    10,919

    Seriously need to work on marketing there. We...

    Seriously need to work on marketing there. We fight in every way we can against becoming a commodity. This is a value add but in competition with what OEMs are already doing.
  17. It is set individually for each user, that's why...

    It is set individually for each user, that's why it's there.
  18. Replies
    9
    Views
    503

    I've played around with it and it works but...

    I've played around with it and it works but haven't had a calling to use the data.

    I do know from other apps that a paid weather solution gets much better data. One of those many areas they have...
  19. Replies
    3
    Views
    275

    Right, export table for exposing those points to...

    Right, export table for exposing those points to ALC.

    If you pay attention to your folder names and automatically creating the BACnet point names in the export table things can get really slick...
  20. Replies
    9
    Views
    503

    I'm sure many do. ALC can pull in several weather...

    I'm sure many do. ALC can pull in several weather sources through a paid addon and you can utilize that in about any way you want.

    What system are you dealing with?
  21. Thread: EasyIO FT04

    by MaxBurn
    Replies
    31
    Views
    2,240

    I got the email the 14th.

    I got the email the 14th.
  22. Thread: EasyIO FT04

    by MaxBurn
    Replies
    31
    Views
    2,240

    Just got this email, looks like it is obtainable...

    Just got this email, looks like it is obtainable now;
  23. What is the jar file name? I had a similar...

    What is the jar file name? I had a similar experience with the 'asd.jar' and current 'ibmsAsd.jar'. In talks with maxline they did have a newer version of the older driver name that I was able to...
  24. Replies
    3
    Views
    283

    I think all the points you need are exposed to...

    I think all the points you need are exposed to that third party driver but the likelyhood they are mapped is pretty low. You could likely pull them all in via discovery and do what you need to do...
  25. Thanks, that also explains why I couldn't find...

    Thanks, that also explains why I couldn't find anything with search.

    Edit, you wouldn't happen to have one with all the normal system alarms in it would you?
  26. Thread: NEWS

    by MaxBurn
    Replies
    27
    Views
    1,437

    Huh, my money was on Schneider.

    Huh, my money was on Schneider.
  27. Need old cmnetalerttext.properties file from ALC

    Does anyone have an old legacy alarm file that resolves the legacy alert ID's (A1, A2 etc) to the alarm text for a WebCTRL system? I believe it was named cmnetalerttext.properties, I thought it lived...
  28. Replies
    15
    Views
    1,466

    During my short time serving on a condo board I...

    During my short time serving on a condo board I learned that if you have ice dams that big you have a problem with insulation and/or attic vents which are a combination of soffit and ridge vents....
  29. Replies
    2
    Views
    361

    Both jaces need unique device ID's and MACs that...

    Both jaces need unique device ID's and MACs that do not collide on the MS/TP trunk.

    At least one needs routing turned off to avoid a circular network.

    Trunk network number is the same on both.
  30. Replies
    6
    Views
    399

    We use a USB-K to change IP in the LGR. Pretty...

    We use a USB-K to change IP in the LGR. Pretty sure you can use any RS485 dongle and attach it to the Rnet port to accomplish the same thing.

    Disconnect anything attached to Rnet port and S2...
  31. Replies
    7
    Views
    572

    I'm not sure but I don't think the NAE is a...

    I'm not sure but I don't think the NAE is a BACnet router, or maybe that feature isn't turned on. If it can't be a router I don't see that it needs to go away but you will have to add a BACnet...
  32. Replies
    2
    Views
    332

    The issue is that EnOcean is a short range...

    The issue is that EnOcean is a short range protocol, 60 feet tops generally in a building or two or three walls. So you need a bunch of receivers and a jace driver and receiver would be super...
  33. Replies
    1
    Views
    199

    Huh, that thing sure looks a lot like a EasyIO...

    Huh, that thing sure looks a lot like a EasyIO device. Check some of the EasyIO default IPs.
  34. As a lynxspring dealer are we allowed to have...

    As a lynxspring dealer are we allowed to have this? I know no one in my company has this now. Would like to have access, I know I need to email licensing every month or so to change something.
  35. Water source HP? Is there a point indicating loop...

    Water source HP? Is there a point indicating loop water good?
  36. Replies
    7
    Views
    572

    FC = Field Controller. Pretty sure it's just...

    FC = Field Controller. Pretty sure it's just MS/TP.

    https://cgproducts.johnsoncontrols.com/MET_PDF/12011034.pdf
  37. Replies
    19
    Views
    1,592

    They shipped it with the COV threshold defaulting...

    They shipped it with the COV threshold defaulting to 0? I've dealt with plenty of Carel sytle devices, plenty in greenheck and never noticed that. Good to know.

    I've seen their software to set...
  38. Replies
    3
    Views
    288

    Sounds like another one of those yes it's...

    Sounds like another one of those yes it's possible but it's going to take more time than doing it manually?

    The next generation of ALC integration will make this pretty easy though, can't wait.
  39. Replies
    16
    Views
    934

    You sound like one of those super rare master...

    You sound like one of those super rare master systems integrators. Sounds like a win with things running that smoothly.
  40. Take the file you found and send it to virus...

    Take the file you found and send it to virus total. Odds are its fine,AV just doesn't like how it arrived on your machine. Maybe have VT test the rest of the stuff you found too.
  41. You might measure OA flow but the amount of...

    You might measure OA flow but the amount of bypass flow nobody cares about.

    The VAV is a variable volume and it needs a fairly stable air pressure to be able to have time to react and control the...
  42. Did you get a docComFour.pdf with your driver? It...

    Did you get a docComFour.pdf with your driver? It won't help with specific point questions like this though. Reach out through your vendor and see if you have the latest driver and see if they can...
  43. Replies
    16
    Views
    934

    That's actually something I'd like to read more...

    That's actually something I'd like to read more on, what should you do with the supervisor? Best practices and standards etc.

    If I had a AAON VAV RTU with factory jace in it and another jace with...
  44. Replies
    16
    Views
    934

    I'm sure it is a reason why these are the sites...

    I'm sure it is a reason why these are the sites I'm seeing.

    Another thing I just thought of is if they had any turnover they might not even know they have a supervisor somewhere.
  45. Replies
    5
    Views
    441

    Is this something newer than these:...

    Is this something newer than these:
    NSTV_V2.2_ZIP.zip
    FTDIDriverV2.12.26_UTCSigned.zip

    If so I would like to get a copy.
  46. Replies
    16
    Views
    934

    No supervisor, is this normal?

    I can't tell you how many jobs we've been invited into that are a mess and consist of multiple jaces running different versions in the same building sometimes and mostly there is nothing tying the...
  47. So four times a second, is that going to overload...

    So four times a second, is that going to overload any pages that take longer than a quarter second to load?
  48. Replies
    4
    Views
    307

    Going to take a wild guess and say ux is for pix,...

    Going to take a wild guess and say ux is for pix, wb is the palettes and programs though rt contents looks more like that.

    I don't think you are supposed to do those one at a time, load all or...
  49. In ALC the schedule object has a locked value for...

    In ALC the schedule object has a locked value for occ/unocc. Can you find that property in BACnet? Also check it in iVU and see if it is locked. Not sure what you are looking at in the discovery...
  50. They should. Any way into their network they...

    They should. Any way into their network they don't control is a problem.

    When talking to IT about BACnet routers always use both words, dropping a "router" on their network will lead to some...