    The LID-1B has software in eprom, the battery...

    The LID-1B has software in eprom, the battery retains this if power is lost. With a dead battery, the eprom loses it's software. Believe they are reloadable with WinLoader, but this is Carrier only...
  2. Replies
    6
    Views
    173

    Do you know if it is a LID-1B or LID-2B? LID-1B...

    Do you know if it is a LID-1B or LID-2B? LID-1B part number should 19XB04004001 or 19XB04007701, LID-2B should be CESO130036. The LID-1B had a battery, if the battery died and the LID lost power the...
  3. Internal actuator and the AO are always active....

    Internal actuator and the AO are always active. It doesn't matter, but I would leave it set to ACT for the graphic which generates a damper instead of a VFD. Just set the AO actuators accordingly (NO...
  4. Latest Carrier drivers for Open/CCN is also...

    Latest Carrier drivers for Open/CCN is also 6.6.041.

    We do not have live logic on these controllers and cannot access the program file as they are considered factory pic's and locked down.

    I...
  5. Clipping files do not get loaded with AppLoader,...

    Clipping files do not get loaded with AppLoader, but are on the TechTools CD/USB install software. Just need to copy them to your laptop.

    Did they disconnect and remove the Act-Net actuator since...
  6. I could not get it to work with v3.8, v4.7 or...

    I could not get it to work with v3.8, v4.7 or v4.9, attempted a few weeks ago. All is good in the Lonworks Interfaces (32 Bit), but N4 will not connect to the card. If you figure it out, please post...
  7. There is no direct correlation to N2 point number...

    There is no direct correlation to N2 point number and the physical point channel. It is the point in the controller getting assigned an N2 variable. A PCV has physical UI-1 and internal AI-1 that is...
  8. Thread: Pcg points

    by Balibe
    Replies
    5
    Views
    484

    There is smoke control logic, but it tied to LT-A...

    There is smoke control logic, but it tied to LT-A (Low Temperature Alarm). Not sure why, the smoke logic does not put and priority forces on the outputs.

    There are no priority forces setup for...
  9. Thread: Pcg points

    by Balibe
    Replies
    5
    Views
    484

    PCG's are different than UNT's, depends how it...

    PCG's are different than UNT's, depends how it was programmed.

    If they selected Smoke Control Support in the Q&A it will put a force priority of 2. The point you need to toggle is EMERGENCY-MODE....
  10. Replies
    8
    Views
    640

    He is looking for PC Data Collection Tool...

    He is looking for PC Data Collection Tool (PCDCT). As far as I know it was not available outside of Carrier.

    "PCDCT, the Carrier chiller is monitored for 24-hours or more, and all parameters are...
  11. Replies
    10
    Views
    600

    You need to make the points network visible on...

    You need to make the points network visible on the Bacnet Objects tab, not the Alarm Sources. Changing it there only makes the bacnet alarm visible. Hopefully the access you are using allows you to...
  12. Thread: Batch editor

    by Balibe
    Replies
    8
    Views
    645

    Use the "slotPath" instead of "displayName", the...

    Use the "slotPath" instead of "displayName", the slotPath is fixed and can't be modified like the displayName.

    .
  13. Replies
    8
    Views
    691

    Yes you can modify, both pictures in a toggle...

    Yes you can modify, both pictures in a toggle button must be the same size. I already had this modified years ago as we had the same issue with an engineer, it is attached for you to download.

    The...
  14. They are typically only auto-generated for...

    They are typically only auto-generated for factory PIC's and that is if the PIC is defined in the discovery.sal, CC6400's need to be made from scratch as each can be different.

    Is the point you...
  15. Replies
    11
    Views
    565

    Yep, same thing with the OPN-UC & OPN-APP .....

    Yep, same thing with the OPN-UC & OPN-APP .....
  16. The CCN point is not mapped to a point in the...

    The CCN point is not mapped to a point in the control program. You cannot go directly to the CCN table from a graphic for point information. The graphic is looking at the control program. CCN points...
  17. Replies
    21
    Views
    782

    In addition ..... the S2 converter is powered...

    In addition ..... the S2 converter is powered with the USB connection, CVTPro converter needs a separate power supply.
  18. Replies
    11
    Views
    565

    The OPN-UPC will hold two control programs, you...

    The OPN-UPC will hold two control programs, you can pull points from several chillers in one control program. Just need to change the point path from "ccn://link/ to the address of the ccn device....
  19. Replies
    11
    Views
    565

    You can see ALAMHIST table from the PIC. ...

    You can see ALAMHIST table from the PIC.



    Don't know, haven't used this driver since AX v3.7.

    As hvac69 stated, we have been installing the Carrier's OPN-UPC on CCN devices to integrate...
  20. Replies
    11
    Views
    565

    There are two version of the driver, below are...

    There are two version of the driver, below are the features. The Extended mode driver is not offered for sale at this time, believe it is only available to Carrier Corp. Just don't have access to the...
  21. Thread: Jace Passphrase

    by Balibe
    Replies
    4
    Views
    336

    A cleandist will reset the passphrase in the Jace...

    A cleandist will reset the passphrase in the Jace and reset it to default, but not the passphrase in the config.bog of the file you are transfering. If you do not know the passphrase in the...
  22. Replies
    8
    Views
    691

    This is a live screenshot with the water detector...

    This is a live screenshot with the water detector in in alarm ......
    .
  23. Replies
    8
    Views
    691

    In a variable color expression the first color is...

    In a variable color expression the first color is a hex decimal is when the expression is true, the second is the false. It works the same way single-line text expression where you can change the...
  24. Replies
    8
    Views
    640

    There is Diagnostic Trace in NSTIV, not sure why...

    There is Diagnostic Trace in NSTIV, not sure why they didn't leave this feature when they resurrected NST after CView. It only runs in the program. It's not like you set them up then leave and let...
  25. Replies
    10
    Views
    285

    The Master will see 12 & 16 as offline and not...

    The Master will see 12 & 16 as offline and not calculate their values. Keep the total number of zones at 11, not 9 so the master looks all the way down to add 10.
  26. Replies
    10
    Views
    285

    Don't need a PAT if the RTU has a CCN controller,...

    Don't need a PAT if the RTU has a CCN controller, air source supply air temperature will be sent over linkage. Only need it if using a non-ccn RTU so the vav's can calculate the mode.
  27. Replies
    9
    Views
    345

    Carrier uses the same name for them. If they are...

    Carrier uses the same name for them. If they are stand-alone systems, it will need to be a System Touch for access, scheduling, etc.



    ID's are auto-generated once the address is changed and...
  28. Replies
    15
    Views
    694

    Carrier does give you the option to put a point...

    Carrier does give you the option to put a point in/out of service, even if the point is a read only point. Once in discovered networks and the points are scanned, remove the check from out of service...
  29. It does work on UC controllers, but appears to...

    It does work on UC controllers, but appears to only set device instance & baudrate.

    I just did a bunch of UC400 in OA units to change baudrate and set the device instance. The setup tool worked...
  30. Replies
    15
    Views
    694

    It is the newer USB printer cable ..... Type-A...

    It is the newer USB printer cable ..... Type-A USB connector (computer) at one end and a standard Type-B connector (printer) at the other end. If you have NSTV, it is the same cable between the...
  31. Replies
    15
    Views
    694

    Download Tracer® BACnet Setup Tool, it is free...

    Download Tracer® BACnet Setup Tool, it is free and does not need a license. Allows you to setup the units, device instance and points in the BCI to written. I havent used it on a Reliatel yet, but...
  32. Did you try to adjusting the "Number of APDU...

    Did you try to adjusting the "Number of APDU Retries" in the driver configuration? Default is 3, I have had to change this to 8 in the past to resolve issues similar to yours.
  33. Replies
    14
    Views
    575

    Thanks for the additional info!!!! I have 11 of...

    Thanks for the additional info!!!! I have 11 of these that were installed in 2019, 10 are OABD's and one is OAGB. They left the paper work in the units from install, but none had any points lists.
    ...
  34. Replies
    14
    Views
    575

    Thanks Orion!!!!! I owe you one, the information...

    Thanks Orion!!!!! I owe you one, the information is what I needed. They are the same units except these are single zone vav, no erv and modulating oa/ra dampers. Basically setup as a rooftop versus...
  35. Replies
    14
    Views
    575

    Thanks for looking tomorrow, any information will...

    Thanks for looking tomorrow, any information will help even for a different unit. These were installed about a year or so ago and been running stand-alone. The installer left the paperwork in the...
  36. This sounds like an error with the software as...

    This sounds like an error with the software as you are getting it when starting BEST++. Have you tried to re-install NSTV?

    Have to tried power cycling the controller to see if it resolve this. It...
  37. Replies
    14
    Views
    575

    Trane Horizon Integration Manual

    Does anyone have the integration guide for a Trane Horizon OABD with the UC600, the document should be BAS-SVP18*-EN. I have access to comfortsite.com but cannot locate the document anywhere for...
  38. Replies
    8
    Views
    376

    Should not need to adjust the program for the...

    Should not need to adjust the program for the sensor as the logic is the same for a wireless or hardwired sensor. Just make sure you do not get an addressable sensor as the default is 199 for the...
  39. Replies
    15
    Views
    528

    You will need to force (override) the point. If...

    You will need to force (override) the point. If you use Set from the Jace it will not be forced (a forcepri of 0) and look at the input contacts.

    With CCN, the highest priority is 10 not 16....
  40. I am at a loss. I think it is an issue with the...

    I am at a loss. I think it is an issue with the PIC and not the translator. If I remember correctly, CESR131309-04 was the latest for the translator. I will need to verify, all our FieldLoader files...
  41. Replies
    15
    Views
    528

    Sorry, it has been awhile on these controllers....

    Sorry, it has been awhile on these controllers. We typically don't enable the local override for our customers. OVRD is for a manual override to initiate or cancel an override over the network. The...
  42. Replies
    15
    Views
    528

    No need to worry about flash on these vav...

    No need to worry about flash on these vav controllers. The Carrier i-Vu interface writes them all-day long. If a schedule is changed in the controller locally with NSTV, i-Vu will change it back to...
  43. I am puzzled at the issue now, never seen this....

    I am puzzled at the issue now, never seen this. You mapped the points manually? Do these have the Pic 2 controls (CCM) or the older Pic1 controls (PSIO)?

    I would start fresh with the translator...
  44. The chiller must be in Network (CCN) Mode for the...

    The chiller must be in Network (CCN) Mode for the translator to write the Pic. If it is in local, remote, etc you can only read the points over CCN, all forces are disabled over the network.

    If...
  45. Since you have 2 chillers, going to assume the...

    Since you have 2 chillers, going to assume the internal lead/lag feature is enabled. With lead/lag enabled, you cannot command CHIL_S_S as it is being written by the lead/lag logic built into the...
  46. Replies
    6
    Views
    494

    AFAIK you cannot edit the px file that is a...

    AFAIK you cannot edit the px file that is a pxinclude from the px file you have open. You have to open the pxinclude file referenced to edit it.

    I actually got to see the screenshot posted before...
  47. Replies
    59
    Views
    2,642

    I created the 2D graphics for our projects as it...

    I created the 2D graphics for our projects as it is cheaper, but I am not a computer graphics designer by a long shot. We have been outsourcing to a graphics company to create our 3D floorplans for...
  48. Replies
    258
    Views
    105,011

    The DBACS was a pain and thankfully they no...

    The DBACS was a pain and thankfully they no longer using them in my area on new systems. The last 3 Daikin systems I have integrated they have supplied the ITM with the BACnet Server Gateway license....
  49. Thread: Trane Comm4

    by Balibe
    Replies
    11
    Views
    510

    Copy & pasted the cut-sheet info. I think you are...

    Copy & pasted the cut-sheet info. I think you are correct, comm3 was isolated and comm4 was non-isolated. I have only used the device on comm4 vav's, but data sheet says it supports comm3 and comm4...
  50. Thread: Trane Comm4

    by Balibe
    Replies
    11
    Views
    510

    There is one I have used in the past for vav's...

    There is one I have used in the past for vav's only. Converts up to 4 links to bacnet/ip. Works with VAV-1s through VAV-4s, Intellipak Rooftop Units, TCUs (Terminal Control Unit) and Voyager...