Page 1 of 2 12 LastLast
Results 1 to 20 of 37

Thread: Single stage stat on a two staage furnace, can I do that ?

  1. #1
    Join Date
    Oct 2012
    Posts
    16
    Post Likes

    Single stage stat on a two staage furnace, can I do that ?

    I have a Honeywell Pro TH4110D single stage stat, running a Goodman two stage 80% furnace. Goodman said this is the acceptable way to connect it up /run it, any thoughts on doing this ?

    Seems like my old set up with analog stat and single stage furnace worked better / kept house warmer (at same temp setting)

  2. #2
    Join Date
    Dec 2010
    Location
    The Quad-Cities area (midwest).
    Posts
    2,927
    Post Likes
    Quote Originally Posted by shankle View Post
    I have a Honeywell Pro TH4110D single stage stat, running a Goodman two stage 80% furnace. Goodman said this is the acceptable way to connect it up /run it, any thoughts on doing this ?

    Seems like my old set up with analog stat and single stage furnace worked better / kept house warmer (at same temp setting)
    The proper stat with that furnace, to make the home more comfortable, would be a 2-stage stat.

  3. #3
    Join Date
    Dec 2010
    Location
    The Quad-Cities area (midwest).
    Posts
    2,927
    Post Likes
    P. S.
    It could be that they put in too big of a furnace. That happens alot. Then it doesn't work as it should.

  4. #4
    Join Date
    Oct 2010
    Location
    Anderson, South Carolina, United States
    Posts
    21,021
    Post Likes
    You could do that but to get the full potential out of the system you need a 2 stage heat tstat

  5. #5
    Join Date
    Jul 2008
    Location
    Rochester NY
    Posts
    5,298
    Post Likes
    Ecobee baby! Dial right in when that sucker stages.

  6. #6
    Join Date
    Oct 2012
    Posts
    16
    Post Likes
    Thread Starter
    The furnace (Goodman) states right on the inside cover "this furnace is designed to be used with a single stage stat" despite furnace being two stage (as in the control for the stages resides on the furnace internal board not the stat).
    Should I still be using a two stage stat anyway? Not sure it's even wired up for that.
    thanks for all !!

    Seems our house is always COLD, we're constantly waiting for the stat to click on, takes forever to cycle (I've tried different cph settings, that did nothing)

  7. #7
    Join Date
    Dec 2010
    Location
    The Quad-Cities area (midwest).
    Posts
    2,927
    Post Likes
    Quote Originally Posted by shankle View Post
    The furnace (Goodman) states right on the inside cover "this furnace is designed to be used with a single stage stat" despite furnace being two stage (as in the control for the stages resides on the furnace internal board not the stat).
    Should I still be using a two stage stat anyway? Not sure it's even wired up for that.
    thanks for all !!

    Seems our house is always COLD, we're constantly waiting for the stat to click on, takes forever to cycle (I've tried different cph settings, that did nothing)
    It will work with a single stage stat. It will (then) work based on the timer. That's not the issue. To give you the comfort, you should have a 2 stage stat.

    Also, I've seen where a system is short on return air, the new furnace will bump the limit.
    This (shortage) did not effect the older style furnaces as much.

  8. #8
    Join Date
    Oct 2012
    Posts
    16
    Post Likes
    Thread Starter
    Do I have to rewire it to get/use a two stage stat ?

    what does this mean --->
    Also, I've seen where a system is short on return air, the new furnace will bump the limit.
    This (shortage) did not effect the older style furnaces as much.

    for whatever its worth, the original furnace and old type stat heated/maintained temperature in my house much more evenly

    thanks so much !

  9. #9
    Join Date
    May 2000
    Location
    Indianapolis, IN, USA
    Posts
    42,886
    Post Likes
    If it is a GMH, you can't use a 2 stage stat

  10. #10
    Join Date
    Oct 2012
    Posts
    16
    Post Likes
    Thread Starter
    The Goodman model is GMH80904BNA, is there a better stat I could be using with it instead of the current Honeywell Pro TH4110D

    thanks

  11. #11
    Join Date
    Dec 2010
    Location
    The Quad-Cities area (midwest).
    Posts
    2,927
    Post Likes
    Quote Originally Posted by shankle View Post
    Do I have to rewire it to get/use a two stage stat ?

    what does this mean --->
    Also, I've seen where a system is short on return air, the new furnace will bump the limit.
    This (shortage) did not effect the older style furnaces as much.

    for whatever its worth, the original furnace and old type stat heated/maintained temperature in my house much more evenly

    thanks so much !
    If the ductwork (supply or return) and/or the registers/grilles (supply or return) are not adequate, then the heat exchanger will get too hot and turn off the burners.

    The blower continues (to blow) so the homeowner doesn't even know the "heat" is off. This normally only happens when it's really cold outside unless the ductwork really sucks.

  12. #12
    Join Date
    Jun 2001
    Location
    Moore, Oklahoma, United States
    Posts
    4,648
    Post Likes
    Quote Originally Posted by BaldLoonie View Post
    If it is a GMH, you can't use a 2 stage stat
    The fact Goodman makes a 2 stage furnace w/o the capability to be optimized with a 2 stage stage leaves a bad taste in my mouth about Goodman...

  13. #13
    Join Date
    Jun 2001
    Location
    Moore, Oklahoma, United States
    Posts
    4,648
    Post Likes
    Quote Originally Posted by George2 View Post
    If the ductwork (supply or return) and/or the registers/grilles (supply or return) are not adequate, then the heat exchanger will get too hot and turn off the burners.

    The blower continues (to blow) so the homeowner doesn't even know the "heat" is off. This normally only happens when it's really cold outside unless the ductwork really sucks.
    It can also happen during recovery from setback.

  14. #14
    Join Date
    Jun 2001
    Location
    Moore, Oklahoma, United States
    Posts
    4,648
    Post Likes
    I've found in most cases you can just leave the 2nd stage unhooked completely since furnaces are typically sized twice as big as needed. Set the system as "two stage" and never use stage 2.

  15. #15
    Join Date
    Jul 2008
    Location
    Rochester NY
    Posts
    5,298
    Post Likes
    Quote Originally Posted by BaldLoonie View Post
    If it is a GMH, you can't use a 2 stage stat
    +1

    Not really a 2 stage furnace. Won't be polishing that one...

    Quote Originally Posted by 54regcab View Post
    The fact Goodman makes a 2 stage furnace w/o the capability to be optimized with a 2 stage stage leaves a bad taste in my mouth about Goodman...
    Hmmm. Not sure that's fair.

    Quote Originally Posted by 54regcab View Post
    I've found in most cases you can just leave the 2nd stage unhooked completely since furnaces are typically sized twice as big as needed. Set the system as "two stage" and never use stage 2.
    Sad but too true. Most with multiple stage furnaces spent xtra and got nothing for it. GMH at least is cheaper than a real 2 stage furnace.

  16. #16
    Join Date
    Dec 2010
    Location
    The Quad-Cities area (midwest).
    Posts
    2,927
    Post Likes
    Quote Originally Posted by 54regcab View Post
    It can also happen during recovery from setback.
    I had not thought of that, but so true.

  17. #17
    Join Date
    Jan 2004
    Location
    PA
    Posts
    80,602
    Post Likes
    Quote Originally Posted by tedkidd View Post
    +1

    Not really a 2 stage furnace. Won't be polishing that one...



    Hmmm. Not sure that's fair.



    Sad but too true. Most with multiple stage furnaces spent xtra and got nothing for it. GMH at least is cheaper than a real 2 stage furnace.
    It IS a real 2 stage furnace. It has 2 stages.

  18. #18
    Join Date
    Jul 2008
    Location
    Rochester NY
    Posts
    5,298
    Post Likes
    It is a "modified 2 stage" system. Low can run for the first 5 minutes, or 1-12 minutes at the BEGINNING of the cycle. To me, this is a soft starting single stage.

    I guess technically it is a 2 stage, but it misses 90% of the benefit of 2 stage. Any furnace that can't run high first then low, in my view (energy and comfort), misses the point. Ideally a 2 stage can cycle back and forth, modulating in an attempt to match envelope losses.

    (http://site.mypointnow.com/documents/25-k120602.pdf p12. Also, notice it doesn't even list a low output on spec sheet. )

    The real problem comes in when the sales person who like to oversize doesn't understand how this turd operates. He figures he can size to low stage and have "high for fast recovery". Now you have a grossly oversized piece of equipment you can't even lock on low.

    I Audited a house with one of these. 2200 sf, 120,000 btu. Client replaced a 30 year old furnace a year before I got there (same size of course). Bill analysis showed NO ENERGY SAVINGS and they have all kinds of comfort issue.


    IMO, calling it 2 stage is like painting a dog turd gold and calling it a gold brick. Makes true 2 stage devices look bad by association.
    Last edited by tedkidd; 10-12-2012 at 10:49 AM.

  19. #19
    Join Date
    Aug 2003
    Location
    Fort Worth, TX
    Posts
    11,847
    Post Likes
    I can see the timed two stage approach working correctly if:

    a) The high stage is sized for the winter design day (not low stage)

    b) Setback swings are minimized or eliminated

    c) The building envelope is above average in thermal integrity (including duct leakage)

    I would agree with you, Ted, that if the furnace high stage is being sized for "fast recovery", that's foolish. How is "fast recovery" quantified in engineering terms? "Oh, it should warm your house back up from 55 to 72 in about fifteen minutes". Sure, if you have a volcano blazing away inside the box, that might happen.

    The benchmark is the winter design day, not sizing low stage for winter design and then relying on high fire for setback or other recovery demand.
    Psychrometrics: the very foundation of HVAC. A comfort troubleshooter's best friend.

  20. #20
    Join Date
    Jul 2008
    Location
    Rochester NY
    Posts
    5,298
    Post Likes
    What it does is provide a gentle start. It puts some btu to the duct so that when the fan ramps up it's not blowing really cold air at max velocity.

    But imagine my frustration spending hours trying to figure out how to manage staging so I could help improve comfort and energy consumption, and my disappointment when I finally understood what this thing is.

    It's the epitome of "heat UP and shut off" design philosophy.

Page 1 of 2 12 LastLast

Quick Reply Quick Reply

Register Now

Please enter the name by which you would like to log-in and be known on this site.

Please enter a password for your user account. Note that passwords are case-sensitive.

Please enter a valid email address for yourself.

Log-in

Posting Permissions

  • You may post new threads
  • You may post replies
  • You may not post attachments
  • You may not edit your posts
  •