Thread: Nortec Humidifier

  1. #1
    Join Date
    Sep 2008
    Location
    Central Pa.
    Posts
    33
    Post Likes

    Nortec Humidifier

    i have a Nortec Humifier Model# NHMC100 giving "Excessive Current Error 1" code. Checked voltages, 460 3 phase unit, wire connections etc. Replaced the cylinder, checked the conductivity of the water and everything. Still getting the alarm and lockout. Any help would be great.

  2. #2
    Join Date
    Apr 2004
    Location
    Baltimore
    Posts
    31
    Post Likes
    Do you know what the current is that it is pulling when calling from humidty? what is the conductivity of the water? I have has some issues and It was a problem with the board. Not sure if any of this helps?
    My job is to send a man thats wants big money for little effort to a customer that has a problem but doesnt want to pay for it!

    Panic caos and disorder my work here is done!

  3. #3
    Join Date
    Mar 2004
    Location
    ottawa canada
    Posts
    4,011
    Post Likes
    Call 613-822-0335 and ask for tech support .
    The toy chest is officially full ... I got a new toy..... 2007 Aston Martin V8 Vantage and yes it still gives me goosebumps
    You bend em" I"ll mend em" !!!!!!!
    I"m not a service tech, I’m retired ….I used to be a thermodynamic transfer analyst & strategic system sustainability specialist
    In the new big shop , greasin', oilin' . tweakin' n shinin' !!

  4. #4
    Join Date
    Jan 2009
    Posts
    2
    Post Likes
    Is the unit draining OK? Or is the the drain stuck with dirt making it drain all the time?
    I had that problem this winter but I think it was giving a different alarm.

  5. #5
    Join Date
    Sep 2007
    Location
    SF Bay Area
    Posts
    130
    Post Likes
    Read Grahams' post above.

    If this is a regular PM for you, hopefully the operating amps are recorded somewhere on the job site, in your notes, or maybe there is another humidifier on site that you can compare the current amp draw against?

    If the humidifier is located outside, moisture can form inside the control cabinet on the control boards and cause nuisance trips. I've only ever seen the current error 1 caused by poor connections or a plugged cylinder drain.

  6. #6
    Join Date
    Sep 2008
    Location
    Central Pa.
    Posts
    33
    Post Likes
    Thread Starter
    This unit is inside an office building. Conductivity is 70 micromhos ( a little low i think). Each leg is pulling 23-25 amps. On start up the unit will call for 100% demand then the drain solenoid will open for about 3 seconds. It will cycle this way 6 or 7 times, then it seems to be ok. I'll come in the next day and it is off on alarm again. I have a new drain valve, i am waiting for a new fill valve. These items i was told to replace by tech support.

  7. #7
    Join Date
    Mar 2011
    Posts
    2
    Post Likes

    NORTEC 100 Humidifier

    I am thinking about installing 4 new NORTEC NHTC-100'S in our facility. Does anyone have any opinion about the Pro's and Con's with this humidifier.

  8. #8
    Join Date
    Jul 2001
    Location
    Canada
    Posts
    1,913
    Post Likes
    J U N K , have 18 on 1 site and nothing but GLITCHES , customer is slowly replacing them

  9. #9
    Join Date
    Jun 2010
    Location
    U.A. (upper Alabama)
    Posts
    1,253
    Post Likes
    Quote Originally Posted by Truck43 View Post
    i have a Nortec Humifier Model# NHMC100 giving "Excessive Current Error 1" code. Checked voltages, 460 3 phase unit, wire connections etc. Replaced the cylinder, checked the conductivity of the water and everything. Still getting the alarm and lockout. Any help would be great.
    Are you sure you received the right voltage tank, and not a 230v. Also, is it for sure draining to get rid of the hard water? Hard water equals higher conductivity which equals higher amp draw.

  10. #10
    Join Date
    Mar 2011
    Posts
    2
    Post Likes

    Control Guy

    Thanks for the reply. I've been hearing the same thing from other serviceman.

  11. #11
    Join Date
    Nov 2010
    Posts
    16
    Post Likes
    you need to keep up on the maintenance ,you can go through bottles pretty quick if you have hard water. Install an RO supply if possible it helps.

  12. #12
    Join Date
    Feb 2006
    Location
    michigan
    Posts
    177
    Post Likes
    I have serviced a NHMC200 several times. They are very touchy. You are supposed to clean the drain and fill valve every cylinder replacement. These humidifers are nice when they work but seem to break down more often then not.

Quick Reply Quick Reply

Register Now

Please enter the name by which you would like to log-in and be known on this site.

Please enter a password for your user account. Note that passwords are case-sensitive.

Please enter a valid email address for yourself.

Log-in

Posting Permissions

  • You may post new threads
  • You may post replies
  • You may not post attachments
  • You may not edit your posts
  •