Thread: chiller flow switch

  1. #1
    Join Date
    Jan 2001
    Location
    Carlisle, Pa
    Posts
    945
    Post Likes

    chiller flow switch

    I am working a system with a 3o ton trane chiller with 2 chilled water pumps in parrallel. It has a standard m&m paddle type flow switch on chilled water loop. The bas monitors pumps with current sensors and shuts off chiller call if no chw or cond pumps. The flow switch is part of the actual chiller control. We just replaced it several months ago. the switch failed today not so much a paddle issue. This chiller is very critical for a rare books area(humidty/temp control). My question what other options do I have that may be a little better more reliable. I understand I have seen this style flow switches 20 years old?? The customer is always trying to improve things. I was thinking diff pressure. also the pumps are on hand off auto switches.the way we are runnig them now is pump is on hand valve open while the backup pump is off with valve closed. we rotate bimonthly. I have suggested switching them automatically. thanks for your input.
    Quick reply to this message Reply  

  2. #2
    Join Date
    Jul 2006
    Location
    Anytown USA
    Posts
    2,257
    Post Likes
    Pressure differential on the chiller barrel or the pumps would work fine.
    Quick reply to this message Reply  

  3. #3
    Join Date
    Apr 2006
    Posts
    337
    Post Likes
    Are you having nuisance trips on flow? Do you have low flow through the chiller? I had a chiller that the flow was at the low range of the chiller and sometimes was not enough to operate the flow switch. We also had a 3 way valve in the picture too, though. I think a DP is more accurate than a paddle.
    Quick reply to this message Reply  

  4. #4
    Join Date
    Jul 2010
    Posts
    59
    Post Likes
    What about efector flow switches? They are really reliable and easily calibrated.
    Quick reply to this message Reply  

  5. #5
    Join Date
    Aug 2006
    Location
    Mixing oil and fire with a big spoon.
    Posts
    8,082
    Post Likes
    Quote Originally Posted by joey94 View Post
    What about efector flow switches? They are really reliable and easily calibrated.
    my recommendation too. oh...never use a dp switch across a pump to prove flow...look at a pump curve chart...at 0 gpm you have maximum pressure differential.
    "Right" is not the same as "Wise".

    Don't step on my favorite part of the Constitution just to point out your favorite part.

    Just because you can measure it, doesn't mean it is important. Just because you can't measure it, doesn't mean it isn't important.
    Quick reply to this message Reply  

  6. #6
    Join Date
    Jan 2001
    Location
    Carlisle, Pa
    Posts
    945
    Post Likes
    Thread Starter
    The flow is within trane specs. Not really nuisance trip total switch failure. The switch was sweating that probably doesn't help. I looked at those flow sensors. I didn't see any on off control. I am surethey have them. Looks like high quality controls though
    Quick reply to this message Reply  

  7. #7
    Join Date
    Jul 2006
    Location
    Anytown USA
    Posts
    2,257
    Post Likes
    Quote Originally Posted by jayguy View Post
    my recommendation too. oh...never use a dp switch across a pump to prove flow...look at a pump curve chart...at 0 gpm you have maximum pressure differential.
    Your post is making me wonder why I see them ALL the time on the pump.
    Quick reply to this message Reply  

  8. #8
    Join Date
    Mar 2007
    Posts
    3,824
    Post Likes
    For my money, IFM Efector is the way to go! I have lots of them installed and no failures yet! No moving parts, easy set up.
    Don't pick the fly crap out of the pepper.
    Quick reply to this message Reply  

  9. #9
    Join Date
    Aug 2009
    Location
    Prattville, Alabama
    Posts
    4,043
    Post Likes
    Here's another vote for IFM Efector. Also, beware of putting DP switch outdoors (air-cooled chiller?). Small lines with no flow + low ambient temp = freeze damage on small line and loss of water. Also, Turbo, maybe they were put there by building controls guy for feedback on pump status? If so, hope they are not also using them for flow status. A running pump does not neccessarily mean flowing water.
    Quick reply to this message Reply  

  10. #10
    Join Date
    Jan 2001
    Location
    Carlisle, Pa
    Posts
    945
    Post Likes
    Thread Starter
    bergermech do you know what model you use. All I need is to send signal back to chiller to sense flow. look like high quality controls
    Quick reply to this message Reply  

  11. #11
    Join Date
    Oct 2001
    Posts
    6,966
    Post Likes
    if you go differential mount the switch on the wall and pipe over to the taps the pump and water in the pipes willl make even more problems...if not on the walll...saw those resistance flow switches were they sense water flow and you set the sensitivity with the pumps on and then cycle for brake...saw them on a hostital York chiller MER job never again...swetting flow switch is always fun on the chiller side
    "when in doubt...jump it out" http://www.youtube.com/watch?v=U1qEZHhJubY
    Quick reply to this message Reply  

  12. #12
    Join Date
    Mar 2007
    Posts
    3,824
    Post Likes
    This is the stuff I use. These part numbers are from their website...

    SN0150 VS3000 controller
    EVC074 M12 angled connector
    E40174 clamp adapter
    SF6200 SFG flow sensor
    Don't pick the fly crap out of the pepper.
    Quick reply to this message Reply  

  13. #13
    Join Date
    Feb 2011
    Location
    OH
    Posts
    150
    Post Likes
    I HATE THOSE DP THEHY ALLWAYS PLUG EVEN CHILLED WATTER OR COOLING TOWER CONDENSING WATER ,EVEN ON FLUID COOLERS THEY ARE A PAIN LIKE THE PADDELS MYSELF.
    Quick reply to this message Reply  

  14. #14
    Join Date
    Mar 2007
    Posts
    3,824
    Post Likes
    Quote Originally Posted by maxster View Post
    if you go differential mount the switch on the wall and pipe over to the taps the pump and water in the pipes willl make even more problems...if not on the walll...saw those resistance flow switches were they sense water flow and you set the sensitivity with the pumps on and then cycle for brake...saw them on a hostital York chiller MER job never again...swetting flow switch is always fun on the chiller side
    The Yorkies definitely know more about this than me, but I think they have been using the electronic flow sensors for a little while. We also have a hospital we take care of with a bunch of big YK's and they all have it. I have also seen some air handlers that measure return and outside airflow using these sensors.

    I think the term they are using for them is "thermal dispersion sensor". I could be wrong, but as I understand it, there's a heater in the probe, and the controller keeps track of the heater temperature and the heat loss from the probe. It compares the two and determines whether flow is present.
    Don't pick the fly crap out of the pepper.
    Quick reply to this message Reply  

  15. #15
    Join Date
    Jun 2005
    Posts
    173
    Post Likes
    Quote:
    Originally Posted by jayguy
    my recommendation too. oh...never use a dp switch across a pump to prove flow...look at a pump curve chart...at 0 gpm you have maximum pressure differential.


    Quote Originally Posted by y7turbo View Post
    Your post is making me wonder why I see them ALL the time on the pump.
    Because JAYGUY scenario only happens if somebody CLOSED the shutoff discharge valve.
    If we evolve from the monkey then why are there still monkeys.

    GOD Bless America.
    Quick reply to this message Reply  

  16. #16
    Join Date
    Mar 2007
    Posts
    3,824
    Post Likes
    There are lots of different scenarios where a pump could be dead-heading without someone physically closing the discharge valve. If you're trying to prove flow through a heat exchanger, the only way to do it with a DP is with the differential across the heat exchanger.
    Don't pick the fly crap out of the pepper.
    Quick reply to this message Reply  

  17. #17
    Join Date
    Aug 2006
    Location
    Mixing oil and fire with a big spoon.
    Posts
    8,082
    Post Likes
    Quote Originally Posted by kelvin View Post
    ...Because JAYGUY scenario only happens if somebody CLOSED the shutoff discharge valve.
    guess what...you have just pointed out a scenario where the dp switch on a pump is a poor choice...also...

    the 2 way valves are not opening (or at the very least: not enough 2 way valves are opening), chiller isolation valves not opened far enough, strainers get plugged up or partially plugged, etc.

    there are lots of things that can cause LOW FLOW...it does not have to be NO FLOW to cause a problem.
    "Right" is not the same as "Wise".

    Don't step on my favorite part of the Constitution just to point out your favorite part.

    Just because you can measure it, doesn't mean it is important. Just because you can't measure it, doesn't mean it isn't important.
    Quick reply to this message Reply  

  18. #18
    Join Date
    Jun 2013
    Location
    Phoenix Arizona
    Posts
    5
    Post Likes
    This is the Ask Our Pro's forum. In order to post a response here, you must have verified qualifications and have been approved by the AOP Committee. You may ask a question by starting a new thread.

    You can find the rules for posting and qualifications here.

    Additional infractions may result in loss of posting privileges.
    Last edited by jpsmith1cm; 06-27-2013 at 09:55 PM.
    Quick reply to this message Reply  

  19. #19
    Join Date
    Sep 2008
    Location
    Western PA
    Posts
    26,690
    Post Likes
    NukeTech

    This is the Ask Our Pro's forum. In order to post a response here, you must have verified qualifications and have been approved by the AOP Committee. You may ask a question by starting a new thread.

    You can find the rules for posting and qualifications here.

    Additional infractions may result in loss of posting privileges.


    Quick reply to this message Reply  

Quick Reply Quick Reply

Register Now

Please enter the name by which you would like to log-in and be known on this site.

Please enter a password for your user account. Note that passwords are case-sensitive.

Please enter a valid email address for yourself.

Log-in

Posting Permissions

  • You may post new threads
  • You may post replies
  • You may not post attachments
  • You may not edit your posts
  •