Page 2 of 3 FirstFirst 123 LastLast
Results 21 to 40 of 43

Thread: Attic temperature/ventilation - smart ideas needed

  1. #21
    Join Date
    Aug 2007
    Location
    Northern VA 38 degrees N by 76 degrees W
    Posts
    5,115
    Post Likes
    Quote Originally Posted by newhomeboston View Post
    well got the cellulose...still a bit too warm. Even with a gable fan running all night it only got down to 6 degrees warmer than the outside temp when I got up at 6am today. I guess the R6 (or 8 I forget) flex duct and wrapped plenum and the Trane TWE just radiate too much heat up in my attic. How do most other new homes get by since many have similar complicated roofs with ducts up in the attic.
    I would be cautious running the gable vent fan while checking temperature rise in the atic.
    If you have any air leakage in the wall cavities, chases, drilled holes from plumbing vents, wiring, air handler, register boots, etc., you may be creating a negative pressure in the atic and drawing the heated air from the conditioned space and giving you the warmer atic.

    There was another mention of humid atic that would point to the negative pressure.

    In the summer time if all is not sealed you will loose cooling also.

  2. #22
    Join Date
    Jul 2005
    Posts
    717
    Post Likes
    Newhomeboston; It would seem as if your ceiling is lacking a "vapor " barrier on the warm side(just under the insulation. Also, inadequate insulation R value can be a cause of this ice damming too. Also the soffit and the high (near the peak) ridge vents need to be sized to allow enough air flow thru-out the attic.

    For every 300 sq ft of attic floor area there should be 1 sq ft of 'free' area venting, divided 50/50 between the soffit and the ridge vents.
    As long as you have adequate insulation within an attic it can NEVER have too much ventilation. and even with roof snow coverage an attic will still breathe.
    note; a properly vented attic, using just soffit and near the peak (continuous ridge vent is best) vents, needs no gable or other fan type vents.

  3. #23
    Join Date
    Oct 2006
    Location
    So. NH
    Posts
    824
    Post Likes
    I think I would leave that fan off and see how the house performs now that is better insulated. We have had alot of snow, rain, cold and warm patterns that also can cause ice build up, even on my shed roof.
    I'm also not so sure it is completely unusual that it is slightly warmer in your attic than outside, I might experiment with that a little.

  4. #24
    Join Date
    Oct 2006
    Location
    So. NH
    Posts
    824
    Post Likes
    I was curious so I put a thermometer in my shed that has a vented roof and is mostly shaded. The outdoor temp was 31 and it was 44 in the shed.
    So like I was thinking before you might be too worried and what you are seeing is quite normal.

  5. #25
    Join Date
    Jul 2005
    Posts
    717
    Post Likes
    A PROPERLY vented (via soffit/ridge) and well INSULATED attic should be at least within 20% -30% of that outside temp.
    in other words if it's 30 f outside, ideally it should be approx 36-39F within the attic. The closer to the outside temp the better.

  6. #26
    Join Date
    Jan 2008
    Posts
    20
    Post Likes
    What if your attic is finished. My sister lives in New England and is considering finishing off a very large attic space atop a colonial-style house. Presumably the house has soffits and a ridge vent. What do you have to do in this case to prevent the ice dams? You still have to maintain close to outside air temp in the winter on the backside of the roof decking, right? How is this done?

  7. #27
    Join Date
    Sep 2007
    Location
    Balto, MD.
    Posts
    199
    Post Likes
    Quote Originally Posted by Colt Hero View Post
    What if your attic is finished. My sister lives in New England and is considering finishing off a very large attic space atop a colonial-style house. Presumably the house has soffits and a ridge vent. What do you have to do in this case to prevent the ice dams? You still have to maintain close to outside air temp in the winter on the backside of the roof decking, right? How is this done?
    I forget what they are called, but panels are placed against the roof deck. Insulation is placed inside the roof joist, then dry wall as normal. The panels allow for ventilation between the insulation and roof deck with out blocking air flow to a from all the vents. This is the same practice when doing a vaulted ceilings in homes.

  8. #28
    Join Date
    Jan 2007
    Location
    Fife Lake, MI
    Posts
    214
    Post Likes
    I'm suddenly having issues with Ice Dams since replacement of my roof. Attic is insulated to R-38. Full Soffit ventilation and previously had a Hard Plastic Ridgevent. When we replaced the roof the roofing supplier recommended Cobra Vent in place of the rigid plastic. Now I have Icicles and Ice Dams. You guys think the cobra isn't allowing as much air to flow as the rigid plastic? Previous 9 years of winters never had a single icicle. Now they're everywhere.

    I'm not looking forward to climbing up there in middle of the winter to peel off the ridge cap/cobra vent and replace it.

  9. #29
    Join Date
    Aug 2002
    Location
    Office and warehouse in both Crystal River & New Port Richey ,FL
    Posts
    18,835
    Post Likes
    No ice damn issues,but we have high humidity issues with Cobra vents several times causing mold/mildew on the ceilings.

  10. #30
    Join Date
    Jun 2005
    Posts
    167
    Post Likes
    Thread Starter
    Quote Originally Posted by stvc View Post
    I was curious so I put a thermometer in my shed that has a vented roof and is mostly shaded. The outdoor temp was 31 and it was 44 in the shed.
    So like I was thinking before you might be too worried and what you are seeing is quite normal.
    Sorry for taking a while to get back to you guys...no big snow till now and I was out of town too. We got almost a foot of snow in the Boston area and without running the fan last night the attic was 41 degrees this morning after it had reached 25 outside as the low for a while. If I recall, the last big snow before the fan/cellulose it reached 45 but I had run the fan a bit yesterday on its timer.

    Sounds like the insulation may or forced ventilation may have helped some but not dramatically as we were getting big ice dams with the attic at 45 during the last heavy snow.

    I've got a guy coming in two weeks to do a blower door test and also use a thermographic camera to see if we have any cold spots in the walls/ceiling.

    But from what this other guy was saying about Cobra mesh vent which is essentially what I have, it does sound like I need a better ridge like Shingle Vent II that some people swear by. Still not sure how the attic breaths when the ridge is covered with snow though.

    Test results in two weeks. I assume enough attics have lesser insulated ductwork in the attic up North and don't have problems so this has to be fixable.

  11. #31
    Join Date
    Jun 2003
    Location
    Madison, WI/Cape Coral, FL
    Posts
    12,042
    Post Likes
    To stop the moist air from moving from the house into the attic when ventilating the attic, reverse the attic fan to blow outside air into the attic. This reduce moisture and air temperature. Regards TB
    Bear Rules: Keep our home <50% RH summer, controls mites/mold and very comfortable.
    Provide 60-100 cfm of fresh air when occupied to purge indoor pollutants and keep window dry during cold weather. T-stat setup/setback +8 hrs. saves energy
    Use +Merv 10 air filter. -Don't forget the "Golden Rule"

  12. #32
    Join Date
    Aug 2003
    Location
    Fort Worth, TX
    Posts
    11,847
    Post Likes
    Newhomeboston,

    Do the upstairs portions of your home have recessed "can" lights? If so, are they sealed? Can lights are notorious leakers if not sealed/rated IC for insulation contact. Unsealed, they can be a large contributer to setting up a stack effect in the home.

    Your indoor humidity levels...what do they normally run? Do you use an indoor humidifier? If you've been leaving it off, lately, what do your indoor humidity levels typically run?

  13. #33
    Join Date
    Jun 2005
    Posts
    167
    Post Likes
    Thread Starter
    Quote Originally Posted by shophound View Post
    Newhomeboston,

    Do the upstairs portions of your home have recessed "can" lights? If so, are they sealed? Can lights are notorious leakers if not sealed/rated IC for insulation contact. Unsealed, they can be a large contributer to setting up a stack effect in the home.

    Your indoor humidity levels...what do they normally run? Do you use an indoor humidifier? If you've been leaving it off, lately, what do your indoor humidity levels typically run?
    No cans, etc...ceiling upstairs is sealed with blown in foam. BUT Icynene now says that it needs a vapor retarder and my builder just primed the ceilings (cheapskate and I didn't notice the difference). So RH migrates through the ceiling into the attic where it generally should be dispersed with good ventilation but ours isn't that good. So I think I need to paint the ceiling with some latex paint which I guess has been shown to be an effective vapor retarder, not a barrier, but slows the migration down.

    When the humdifier is on in the house we keep it 35% in the winter about as it adjusts based on outside temp but without it the RH is 25-30%.

  14. #34
    Join Date
    Jul 2006
    Location
    Connecticut
    Posts
    271
    Post Likes
    I have heard of a special paint that acts as a vapor barrier in this situation, but I'm not sure of the composition. It could be sort of a rubber/latex type. But regular primer won't do it, not even KILZ.
    Tom D. - Long-time Journeyman from CT.

    On account of being a democracy and run by the people, we are the only nation in the world that has to keep a government four years, no matter what it does.

  15. #35
    Join Date
    Jun 2005
    Posts
    167
    Post Likes
    Thread Starter
    well the results are in and the energy audit showed there was plenty of insulation in the attic but there was some leakage in the ductwork noticed during the blower door test....

    I guess the poor attic ventilation combined with slight air leakage and the R8 insulated ductwork still radiating a lot of heat just is too much to overcome. I had the duct system installed very carefully with a solid trunk line and flex runs to the rooms so I'm not sure where the leakage could be to try and fix that. And the R8 insulation was the best the contractor said was possible. So I'm not sure I can really affect those two issues much.

    I guess I can try and improve ventilation which may help or the other suggestion the auditor had was to use foam and create a closed attic by insulating the underside of the roof. Does anyone have any preference?

    And if I go for the closed attic, is there a problem that I might cause somehow? I still have the attic floor insulated with foam already...will insulating the roof underside create a situation where the attic doesn't have any air movement, or excess humidity/condensation somehow?

    THanks.

  16. #36
    Join Date
    Feb 2003
    Location
    Huntsville,AL
    Posts
    4,125
    Post Likes
    visit BUILDINGSCIENCE.com
    harvest rainwater,make SHADE,R75/50/30= roof/wall/floor, use HVAC mastic,caulk all wall seams!

  17. #37
    Join Date
    Mar 2008
    Location
    florida
    Posts
    21
    Post Likes

    attic vent

    insatall an attic fan to work on attic temp common problen in florida attic temp 140 degrees,,,like putting duct work over a campfire,,,heat is penetrating the duct even if it is r-6.
    i fix many customer problems with attic fans use the right cfm for square footage.

  18. #38
    Join Date
    Feb 2008
    Location
    Waffleville
    Posts
    10,486
    Post Likes
    seal it up and install a dehumidifier thats what we are doing here, but our humidity is in the summer months, so thick you can cut it with a knife
    If Guns Kill People, Do Pencils Misspell Words?

    http://www.youtube.com/watch?v=An2a1...eature=related

    Before we work on artificial intelligence why don't we do something about natural stupidity?

  19. #39
    Join Date
    Jul 2006
    Location
    NJ
    Posts
    356
    Post Likes
    Quote Originally Posted by valerioac View Post
    insatall an attic fan to work on attic temp common problen in florida attic temp 140 degrees,,,like putting duct work over a campfire,,,heat is penetrating the duct even if it is r-6.
    i fix many customer problems with attic fans use the right cfm for square footage.
    And it's official, The can has been opened!

  20. #40
    Join Date
    Jul 2006
    Location
    NJ
    Posts
    356
    Post Likes
    Quote Originally Posted by bonafide View Post
    And it's official, The can has been opened!
    See for yourself

    http://www.hvac-talk.com/vbb/showthread.php?t=133420

Page 2 of 3 FirstFirst 123 LastLast

Quick Reply Quick Reply

Register Now

Please enter the name by which you would like to log-in and be known on this site.

Please enter a password for your user account. Note that passwords are case-sensitive.

Please enter a valid email address for yourself.

Log-in

Posting Permissions

  • You may post new threads
  • You may post replies
  • You may not post attachments
  • You may not edit your posts
  •