Thread: trane xl16i 2 stage, high humidity

  1. #21
    Join Date
    Apr 2008
    Location
    TEXAS
    Posts
    1,706
    Post Likes
    every bit of advice you have gotten here has been very good advice. the 16i doesn't remove humidity as well as single stage systems but CAN be set up to work very well. 350 cfm and comfort R is crucial in this climate. get your guys back out asap. the drain vent can be capped with a 90 cent 3/4 pvc cap. it won't do anything to remove humidity tho. call your install company.
    "When the people find they can vote themselves money,that will herald the end of the republic" - Benjamin Franklin

    "Government is not reason, it is not eloquence, it is force;like fire, a troublesome servant and a fearful master. Never for a moment should it be left to irresponsible action"- George Washington

  2. #22
    Join Date
    Nov 2003
    Posts
    19
    Post Likes
    Thread Starter
    Quote Originally Posted by smittyii View Post
    every bit of advice you have gotten here has been very good advice. the 16i doesn't remove humidity as well as single stage systems but CAN be set up to work very well. 350 cfm and comfort R is crucial in this climate. get your guys back out asap. the drain vent can be capped with a 90 cent 3/4 pvc cap. it won't do anything to remove humidity tho. call your install company.
    Thanks - I saw you on contractor map so I think you are S. of Austin.

    That's too bad about 16i - you are second person to mention this. Everything I could get my hands on says two stage is better at humidity control.

    Thanks for your patience - I will have to have tech back again to lower speed more because change from 450 to 400 didn't really make much improvement, if any.

    Take a look at my post above about tstat is this correct? i.e. how do I know if it is running first or second stage?

  3. #23
    Join Date
    Apr 2008
    Location
    TEXAS
    Posts
    1,706
    Post Likes
    Quote Originally Posted by bobl View Post
    Thanks - I saw you on contractor map so I think you are S. of Austin.

    That's too bad about 16i - you are second person to mention this. Everything I could get my hands on says two stage is better at humidity control.

    Thanks for your patience - I will have to have tech back again to lower speed more because change from 450 to 400 didn't really make much improvement, if any.

    Take a look at my post above about tstat is this correct? i.e. how do I know if it is running first or second stage?
    don't stress about it too much. the 16i needs to be tweaked to work well in this climate. i have seen happy customers with 16i systems , but in almost every case it took some tweakin to get them that way. i don't have the book in front of me, but tranes tstats are geared toward certain systems (i e comfort R). the fan needs to shut off soon after system shut off and run in lower speed at start. it can be done ,just be patient.
    "When the people find they can vote themselves money,that will herald the end of the republic" - Benjamin Franklin

    "Government is not reason, it is not eloquence, it is force;like fire, a troublesome servant and a fearful master. Never for a moment should it be left to irresponsible action"- George Washington

  4. #24
    Join Date
    Jul 2002
    Location
    Yuma, AZ
    Posts
    2,755
    Post Likes
    Make certain that the new duct connections to the equipment are air sealed.
    Make sure that old duct connections were not disturbed during the installation and leaking air in or out.
    Fix the drain air leak.
    Slow the fan to 350 cfm and other suggestions in post 12.
    "I have never let my schooling interfere with my education."
    Mark Twain
    NEVER STOP LEARNING.

  5. #25
    Join Date
    Nov 2003
    Posts
    19
    Post Likes
    Thread Starter
    OK - thanks. Humidity was 63% in house this morning.

    The service guy wasn't really interested in my observations - he said it is normal for high volume of air to come streaming out of drain line. No idea if this is true - it wasn't with previous unit. He also said 55% is what they recommend. I know 55% is not normal.

    If anyone else has 16i and access to drain line it would be good to know if this is normal as well as how I can tell if the unit is really working as two stage or one stage.

    This is complicated & expensive system not working well so I appreciate the help from experienced installers.

  6. #26
    Join Date
    Jan 2004
    Location
    PA
    Posts
    80,602
    Post Likes
    Duct work may be undersized for 4 tons. Old unit may have only been 3.5 tons.
    Air handler is probably not set up right.

    Blower can be set to a slower speed. Which will improve your indoor RH.

  7. #27
    Join Date
    Jan 2004
    Location
    PA
    Posts
    80,602
    Post Likes
    Quote Originally Posted by wraujr View Post
    Just to help the OP understand. Your video shows a duel fuel setup where the heat pump coil is on the bottom (upflow) and you can see the p-trap that was installed. The upper drain connection (that uses the tee fitting) is for condensate from the high efficiency furnace which has its own internal trap. From his description its sounds like he has an ac coil on top of furnace and that the AC coil drain uses a 'tee' fitting. Just guessing.
    Upflow furnace with the coil on the return?

    Improper install.

  8. #28
    Join Date
    Nov 2003
    Posts
    19
    Post Likes
    Thread Starter
    Update: thanks to the excellent replies on this thread. Absolutely useful and great education for me and hopefully helpful to others in future.

    Root cause found to be crossed wiring at outdoor unit. Tstat was signaling for compressor to run at low and turning fan to low. However, outdoor unit was not coming on until tstat signaled for high.

    Now at 42% to 45% humidity. Doesn't come on very often, when it does it's on low - very gentle air flow. No problem hold temp at 78 at 100+ outside. No sticking to floors.

    One observation: when the unit was running the fan w/o compressor we noticed that our normally blast furnace like upstairs was almost same temp as down stairs. It was dramatic change. This tells me that the classic upstairs/downstairs problem might be solved with a more continuous air flow. However, it would have to be done without humidity. It will take a few days to see how things are now that unit is working correctly.

    I asked about comfort-r setting, tech said he didn't set it. He wanted to try things without it.

    One last question - thanks for indulging me.

    What the heck is comfort-r exactly? When unit is in comfort-r what does it do that is different than when it is not in comfort-r?

  9. #29
    Join Date
    Aug 2011
    Location
    San Jose California
    Posts
    219
    Post Likes
    Quote Originally Posted by skippedover View Post
    You should have air streaming out of only your supply outlets. Air should be streaming in only through your return grilles.

    I didn't see any model numbers so I've got make some assumptions but the variable speed blower can be set for several different configurations. You need to have someone knowledgeable from the installing company pay a visit and set up and/or confirm that the blower is set as follows:

    1. Airflow set for a 4-ton system.
    2. Airflow set for 350 CFM/ton
    3. Comfort 'R' mode selected 'On'.

    It's very likely that no matter which stage the outdoor unit is using, the airflow for the system is set too high. The variables are 3.5-5.0 tons, (yours is 4.0-tons) and from 350 to 450 CFM (Cubic Feet Per Minute). The faster the airflow, the less dehumidification you'll get. Comfort 'R' is a Trane patented method of enhancing 'short cycles' by restricting blower operation to 50% of full speed for 1-minute (slow airflow to allow the indoor coil to cool faster) followed by 7-1/2 minutes of 80% of airflow. That's all to assist in greater moisture removal than would otherwise happen.
    Very detailed responses... nice!

  10. #30
    Join Date
    Nov 2003
    Posts
    19
    Post Likes
    Thread Starter
    Ack! I read that earlier and then completely pushed it out of my brain.

    Perfect description. Thanks Skippedover and freon22.

  11. #31
    Join Date
    Dec 2002
    Location
    Rochester, MN
    Posts
    5,307
    Post Likes
    Get the Comfort-R turned on. That will get the coil colder, and help with the humidity control.

  12. #32
    Join Date
    Jul 2006
    Location
    Prata di Pordenone Italy
    Posts
    8,069
    Post Likes
    I always turn on the comfort r on the 16 I

  13. #33
    Join Date
    Nov 2003
    Posts
    19
    Post Likes
    Thread Starter
    Thanks very much for the replies - the tech didn't set comfort-r. The unit is running really well right now. Austin has lower humidity than most place in south, but right now it is like 102 to 105F outside so maybe its the heat not the humidity for a change!

    You can read about our results with the unit here. We are so impressed right now, and it is one of those rare times things work better than you hope, I am afraid to mess with it!

    http://hvac-talk.com/vbb/showthread.php?t=894702&page=2

    My experience seems to show that two stage can work well even in hotter than h#ll Texas. Hope this technology comes down in price.

  14. #34
    Join Date
    Jul 2002
    Location
    Yuma, AZ
    Posts
    2,755
    Post Likes
    I don't know why Comfort R is not the default setting on those variable speed air handlers. It should be. IMO.
    "I have never let my schooling interfere with my education."
    Mark Twain
    NEVER STOP LEARNING.

Page 2 of 2 FirstFirst 12

Quick Reply Quick Reply

Register Now

Please enter the name by which you would like to log-in and be known on this site.

Please enter a password for your user account. Note that passwords are case-sensitive.

Please enter a valid email address for yourself.

Log-in

Posting Permissions

  • You may post new threads
  • You may post replies
  • You may not post attachments
  • You may not edit your posts
  •