  1. Replies
    9
    Views
    622

    Try Project, Batch Restore to add it to the...

    Try Project, Batch Restore to add it to the database
  2. Replies
    7
    Views
    1,404

    You can use your original BacNet commissioning...

    You can use your original BacNet commissioning kit. There is Bacnet Router selection in PCT when you are loading or commissioning a controller.
  3. Thread: honeywell xl15b

    by foyler
    Replies
    6
    Views
    1,123

    The XL15B is commissioned through LonSpec, but...

    The XL15B is commissioned through LonSpec, but needs to have a network connection to do it as opposed to a direct lon connection. When you connect select SLTA, Wan, XL15B, put in the XL15B user name...
  4. Replies
    9
    Views
    1,140

    W7750C is one of the selections in E-Vision...

    W7750C is one of the selections in E-Vision version 1.2 and Configuration Files version 1.3. Maybe you have an older version?
  5. Replies
    5
    Views
    946

    It's in the E-Vision folder.

    It's in the E-Vision folder.
  6. Replies
    5
    Views
    946

    n-state point can be created in switching logic....

    n-state point can be created in switching logic. Software Points, Pseudo Digital, give it a name, select sub-type n-state.

    The cfg file is for metric vs imperial units and is located in the...
  7. Replies
    32
    Views
    3,469

    In a nutshell it's the balancing tool for...

    In a nutshell it's the balancing tool for Honeywell XL10 and Spyder vav controllers. Allows you to set multiple boxes to max or min airflow setpoints or max/min valve positions. Allows adjustments to...
  8. Replies
    32
    Views
    3,469

    Valves too! Download from Honeywell Here...

    Valves too!
    Download from Honeywell Here
  9. Replies
    4
    Views
    970

    I had something similar happen when the point in...

    I had something similar happen when the point in AX was mapped as a NumericWritable point instead of plain Numeric.

    Even though there was no override, the point in the Vma1620 wouldn't work...
  10. Thread: FX Alarming

    by foyler
    Replies
    2
    Views
    442

    Right-click on foreground color and choose...

    Right-click on foreground color and choose animate. Select if true and if false colors. You could also animate the blink property so that stays solid when normal and blinks when in alarm. That should...
  11. Replies
    5
    Views
    1,434

    I would check the connections between the...

    I would check the connections between the thermostat and the controller. Maybe a cut/disconnected/loose wire.

    If you really want to see what's going on you could use RapidBalance to view the VAV...
  12. Replies
    12
    Views
    2,570

    If you're just balancing you can use...

    If you're just balancing you can use RapidBalance. Download here:
    http://customer.honeywell.com/Business/Cultures/en-US/Products/Applications+and+Downloads/RapidBalance%e2%84%a2+-+Version+4.0.htm
  13. Replies
    7
    Views
    1,285

    You can get them here:...

    You can get them here:
    http://pub.controls.johnsoncontrols.com/publish/b2b_aa/us/eng/abcs_exchange/facility_explorer/tecnical_support/facility_explorer_applications.html
  14. Replies
    26
    Views
    4,741

    Thanks, Dave. Appreciate the information. We...

    Thanks, Dave. Appreciate the information.

    We were hoping for an internet solution, but I guess not yet... but it will be nice not to have to bounce back and forth between the router and FX20/60...
  15. Replies
    26
    Views
    4,741

    Can someone provide more info on using the...

    Can someone provide more info on using the FX20/60 as the BACnet router for JCI CommPro BACnet through an internet connection?

    Is there a particular port that needs to be opened to the FX20/60 or...
  16. Replies
    4
    Views
    1,249

    If you have an existing boolean schedule that you...

    If you have an existing boolean schedule that you want to use to inhibit the alarm during unoccupied -

    open the schedule, go to property sheet, right click the schedule name, link mark.
    Open...
  17. Replies
    32
    Views
    3,270

    Chris, You have mail.

    Chris,

    You have mail.
  18. Thread: AX and N2 Comms

    by foyler
    Replies
    3
    Views
    706

    If it's an older FX60 you may need to install the...

    If it's an older FX60 you may need to install the 2.0.3 update. jcin2.jar and jcifxdriver.jar are both updated. You need Workbench to install. Available here:...
  19. Replies
    4
    Views
    946

    Did you select unit of measure - us when...

    Did you select unit of measure - us when generating the prn file? If so add a display to the FX07 and add System Point, Unit of Measure, US to one of the pages.
  20. Thread: FX20 Web Server

    by foyler
    Replies
    4
    Views
    615

    You'll need port forwarding on ports 1911 and...

    You'll need port forwarding on ports 1911 and 3011 to access remotely.
  21. Replies
    13
    Views
    2,357

    Anyone can access them from JCI:...

    Anyone can access them from JCI:
    http://pub.controls.johnsoncontrols.com/publish/b2b_aa/us/eng/abcs_exchange/facility_explorer/tecnical_support/facility_explorer_applications.html
  22. Replies
    4
    Views
    558

    I think you're going to need Workbench to get...

    I think you're going to need Workbench to get into the platform to change it back.
  23. Replies
    8
    Views
    748

    If you do an RMA the replacement part is an...

    If you do an RMA the replacement part is an LP-KIT400B-700. That's just the circuit board. JCI says it has more memory than the original.
  24. Replies
    8
    Views
    748

    I'm not sure what causes it, but I have one just...

    I'm not sure what causes it, but I have one just like it. I'm wondering if it has something to do with upgrading it to 2.0? Did you upgrade yours or was it 3.3.22 to start with?
  25. Replies
    8
    Views
    748

    This is from the JCI solutions database: Per...

    This is from the JCI solutions database:

    Per Brian Johnson (Tridium), Mar 07/08: "If you look [at the following URL using a browser connection] http://<jaceip>:3011/qnx/ndioc!status and see...
  26. Replies
    4
    Views
    619

    Open the bound label for editing, right click on...

    Open the bound label for editing, right click on the word foreground and select animate. Converter type should be "I Boolean To Simple". Choose colors for true and false values. You can do the same...
  27. Replies
    2
    Views
    3,107

    Try clicking the browse button when opening the...

    Try clicking the browse button when opening the palette, go to the modules folder on the server and click on kitPxHvac.jar. That should load the server's kitPxHvac palette into the palette work area.
  28. Replies
    2
    Views
    581

    Make sure you add the N2 protocol in Builder and...

    Make sure you add the N2 protocol in Builder and select which points are on network. Save in Builder, delete and add back in the FX20/60 using the apd file as the resource. You may need to rename...
  29. Replies
    1
    Views
    511

    If you have LonSpec you could do a project backup...

    If you have LonSpec you could do a project backup from the network screen in RapidZone then restore to LonSpec. Go to Network, Refer Points. Select the XL15A as the source controller and TOD Event 1...
  30. Thread: FX distributors

    by foyler
    Replies
    5
    Views
    707

    Tech support should be handled by your local ABCS...

    Tech support should be handled by your local ABCS distributor. Check the link above if you need info on who to contact.
  31. Replies
    2
    Views
    944

    macslim, Thanks for the info. All the data...

    macslim,

    Thanks for the info. All the data sheets show the classic blue metal case. This one has a plastic cover. We will probably suggest going the AX route eventually if these have been...
  32. Replies
    2
    Views
    944

    Honeywell Web-5 Controller

    I'm trying to find some information on this controller with little luck. I searched the Honeywell site and the Buildings Forum. It has the Niagara logo on it. Is it a re-packaged 403 or 545 or...
  33. Thread: FX40 setup

    by foyler
    Replies
    6
    Views
    704

    The FSC Solutions database has some helpful...

    The FSC Solutions database has some helpful information on the FX line. Download it to your hard drive and take a look....
  34. Replies
    18
    Views
    3,571

    Run E-Vision on XP in standard mode with a PCMCIA...

    Run E-Vision on XP in standard mode with a PCMCIA card. One issue - E-Vision has a problem finding the zmpp_im.cfg file and wants to use zmpp_si.cfg instead. If you copy zmpp_im.cfg to the project...
  35. Replies
    20
    Views
    1,680

    Johnson just posted the new jcin2.jar and...

    Johnson just posted the new jcin2.jar and jciFxDriver.jar files to the ABCS Exchange site. Check the property sheet of the N2 Network - Poll Scheduler - Busy Time before and after the update. I had a...
  36. Replies
    19
    Views
    3,228

    How about type SNVT_temp_diff_p. Had to do this...

    How about type SNVT_temp_diff_p. Had to do this in other lon programs for math equations and it prevented conversion and kept the units of measure.
  37. Thread: Care 2.02

    by foyler
    Replies
    3
    Views
    495

    The registration on 2.2 could get corrupted...

    The registration on 2.2 could get corrupted fairly easily - even by installing an external hard drive. Go to Help - Registration and see if you have a valid reference code. If it's a jumbled mess of...
  38. Replies
    20
    Views
    1,680

    Try checking the poll scheduler in the property...

    Try checking the poll scheduler in the property sheet of the N2 Network. Average poll time should be 30-50ms normally. Higher values could indicate N2 trouble. There is an update coming for the jcin2...
  39. Thread: FX20 Factory IP

    by foyler
    Replies
    17
    Views
    5,357

    For the FX20, 40, 60 you should be able to set...

    For the FX20, 40, 60 you should be able to set your computer to 192.168.1.1, plug into the ethernet port, go to the command prompt and ping 192.168.1.255. You'll get a reply back with the FXs...
  40. Replies
    6
    Views
    724

    digo, Thanks for the batch file info. Works...

    digo,

    Thanks for the batch file info.

    Works for FX Workbench with:
    CD C:\JCI\FXSupervisorPro-2.0\bin\
    START plat.exe installdaemon
    START wb_w.exe -profile:jciFxDriver:JciApplianceProfile &&...
  41. Thread: Passed AX

    by foyler
    Replies
    13
    Views
    1,691

    I'll throw my support behind Vern too. I've been...

    I'll throw my support behind Vern too. I've been to several of his Honeywell classes and have the AX class on my calendar.

    See you soon Vern.
  42. Replies
    5
    Views
    687

    I've gotten that same error due to an invalid DNS...

    I've gotten that same error due to an invalid DNS server address. You could try 63.200.183.70 to eliminate that as a possible issue.
  43. Replies
    6
    Views
    730

    Eggcellent. (Mr. Burns)

    Eggcellent. (Mr. Burns)
  44. Replies
    6
    Views
    730

    When you open the editor, you have to click on...

    When you open the editor, you have to click on the triangle associated with the physical point to open the table. Any triangles with hatching in them have switching logic assigned to them.

    If it's...
  45. Replies
    30
    Views
    2,646

    Didja read the quote? ;)

    Didja read the quote? ;)
  46. Replies
    30
    Views
    2,646

    Sounds to me like those controllers need to be...

    Sounds to me like those controllers need to be replaced.
  47. Replies
    13
    Views
    1,074

    For future reference, guys. I did try to bind the...

    For future reference, guys. I did try to bind the nvoMstrSlv3_element0 thru element29 to the slave nviMstrSlv3_element0 etc. individually using Link Mark Out to Link To in14 on all 29 elements. The...
  48. Replies
    14
    Views
    1,257

    In img00171 there are two applications stored. It...

    In img00171 there are two applications stored. It looks like the application you restored may be an older one.

    You could try restoring the application with 01.10.07 at the end. Maybe that is the...
  49. Replies
    14
    Views
    1,257

    Agree with rad1. The application is running, but...

    Agree with rad1. The application is running, but the alarm that came up on startup seems to be preventing the unit from running. Possibly a manual reset pressure switch?

    Careful doing a reset on...
  50. Well, I had to endure a lecture on what a poorly...

    Well, I had to endure a lecture on what a poorly written program it must be to require the user to be an admin and bla, bla, bla. That's about where I stopped listening.

    Bottom line is they are...
Results 1 to 50 of 72
Page 1 of 2 1 2
Comfortech Show Promo Image

Related Forums

Plumbing Talks | Contractor Magazine
Forums | Electrical Construction & Maintenance (EC&M) Magazine
Comfortech365 Virtual Event