Search:

Type: Posts; User: davem

Page 1 of 10 1 2 3 4

Search: Search took 0.01 seconds.

  1. Thread: Open protocols

    by davem
    Replies
    40
    Views
    2,448

    Isn't that 6? :grin2: Which one should I leave...

    Isn't that 6? :grin2: Which one should I leave out? :whistle:
  2. Thread: Pcg1611 fault

    by davem
    Replies
    10
    Views
    469

    SAB is the Sensor Actuator Bus, referring to...

    SAB is the Sensor Actuator Bus, referring to sensors that are wired to the SA Bus terminals on the controller.
  3. Thread: Pcg1611 fault

    by davem
    Replies
    10
    Views
    469

    With the controller programmed like that, you...

    With the controller programmed like that, you probably had to modify the default zone sensor signal from SAB to whatever resistive sensor you are using. Doing so would have removed the SAB setpoint...
  4. Thread: Pcg1611 fault

    by davem
    Replies
    10
    Views
    469

    Just to clarify the issue a little further: if...

    Just to clarify the issue a little further: if the zone sensor is a networked sensor (as opposed to something wired to one of the universal inputs), you should have something wired to the SA bus, but...
  5. Thread: Pcg1611 fault

    by davem
    Replies
    10
    Views
    469

    The problem may lie within the program - if the...

    The problem may lie within the program - if the program is expecting to see a networked zone sensor, that's one reason for the fault light to be on. You'd have to know how to use the PCT software to...
  6. Thread: Pcg1611 fault

    by davem
    Replies
    10
    Views
    469

    Does the .caf file contain references to any...

    Does the .caf file contain references to any networked sensors or PCX modules that aren't wired up?
  7. Replies
    9
    Views
    758

    Are you sure that the units are Comm4, not Comm3?...

    Are you sure that the units are Comm4, not Comm3? In my Intellipaks, I had to rotate the comm card and set a couple dipswitches for it to talk Comm4...I don't know about the comm cards in your...
  8. Replies
    9
    Views
    758

    I had a Comm4 job (with Maxline's driver), with...

    I had a Comm4 job (with Maxline's driver), with Intellipaks, that required the addressing to be above 32...so you may need to readdress the equipment...I can't remember if this was unique to the...
  9. Ditch the Auto-Pilot installation (and that...

    Ditch the Auto-Pilot installation (and that ancient SF1), and move the existing PUP network to a JACE...with a maximum of 32 devices per SF1, there can't be that much for a Tridium contractor to cut...
  10. Replies
    2
    Views
    299

    The kitPx palette contains an "EnumImage", in...

    The kitPx palette contains an "EnumImage", in which you can ord an Enum point, and select an image for any of the Enum's ordinal values.
  11. Not sure if you've got this document, but...

    Not sure if you've got this document, but starting on page 3, there's a pretty good definition of what each point does. If the Hub was set up with "scenes", you may not get quite the manual-control...
  12. Replies
    33
    Views
    2,943

    The 37 hours straight on a central plant...

    The 37 hours straight on a central plant cutover...no, just kidding - definitely the variety. That's what appealed to me most when I transitioned from commercial electrical work into controls -...
  13. Replies
    1
    Views
    364

    I didn't think Auto-Pilot could email...the most...

    I didn't think Auto-Pilot could email...the most sophisticated alarming I ever got working was sending custom text over a modem to an alpha-numeric pager...I don't think SageMAX/IP's could connect to...
  14. Replies
    4
    Views
    779

    Make sure an SD card is installed in the FG20 -...

    Make sure an SD card is installed in the FG20 - without it, you won't be able to install the firmware onto the FG20.
  15. Replies
    13
    Views
    6,061

    That manual is great - thanks for posting that!...

    That manual is great - thanks for posting that! I'd always wondered where to set a JCI VAV controller for various box sizes - I've had a Titus sheet with the "cfm @ 1"w.c." figures for awhile, that...
  16. I agree with Dansky (if I grasp what he's...

    I agree with Dansky (if I grasp what he's saying): this is all on the Lutron guy. For instance, on a job I was just on, the Lutron guy setup with the panels on each floor with the IP address I...
  17. Replies
    8
    Views
    636

    The PNC post-dates my AAM experience by several...

    The PNC post-dates my AAM experience by several years - although I see you work straight for AAM, and I haven't been an SI for almost 10 years, any chance I could send you the point.bob file for...
  18. Replies
    8
    Views
    636

    Thanks for that - while mildly sentimental to...

    Thanks for that - while mildly sentimental to look at, it turned out that the disk didn't have such a utility - which keeps me in the hunt for how to drag out the points list from a Sage into a...
  19. Replies
    8
    Views
    636

    Groovy - thanks! For some reason I found a...

    Groovy - thanks! For some reason I found a SageMax 1.8 IP setup disk on my laptop, but not the Utility disk...funny the old crud we keep around...(and then need the instant we throw it away...)
  20. Replies
    8
    Views
    636

    A little AAM conversion help, please!

    I've got a customer who is going to remove a SAGE from an end-user's facility, and replace it with a JACE. Having done several of these over the years, I know exactly what he needs to do to make a...
  21. Replies
    3
    Views
    419

    I think incontrol is looking for the information...

    I think incontrol is looking for the information to be available on the logic wiresheet, not necessarily a px page - that was a very handy feature of r2 wiresheets...
    What you need to do is...
  22. Replies
    14
    Views
    1,672

    That might be where you are slightly off-course -...

    That might be where you are slightly off-course - you won't be using the Program Service for this replace function:
    Make sure you're in Niagara Network>your JACE>Points>your new folder...that's...
  23. Replies
    14
    Views
    1,672

    Incontrol, you must be missing a step, because...

    Incontrol, you must be missing a step, because this process works perfectly...

    Make sure when you open the rtu4 folder, you then select all its points, then Edit. When the Edit dialog opens up,...
  24. Replies
    5
    Views
    596

    Mmelillo beat me to it - yes, I recommend option...

    Mmelillo beat me to it - yes, I recommend option 3, as it makes the temperature widgets a little more controllable (if you were to animate the Visible slot, as in option 1, and the binding condition...
  25. Replies
    5
    Views
    596

    Now that I've re-read the post, I see that I...

    Now that I've re-read the post, I see that I answered your first version of the question ("...based on the status of the controller...), but changing the image based on the reliability of the zone...
  26. Replies
    5
    Views
    596

    The Bound Label Binding's "ord" will be the...

    The Bound Label Binding's "ord" will be the pointer to the controller object (e.g. "station:|slot:/Drivers/BacnetNetwork/FPB_11_04"). Then, right-click "image", and select "Animate". Because of the...
  27. Replies
    3
    Views
    510

    While a similar calibration offset is found...

    While a similar calibration offset is found within Spyders, the OP needs not to calibrate his sensors, but configure the Spyder for a completely different sensor type.

    Since a Spyder doesn't...
  28. Replies
    29
    Views
    2,348

    Kinda pricey, but I've borrowed a Magbench a few...

    Kinda pricey, but I've borrowed a Magbench a few times (enough to get the boss to buy one for me) - there's always some metal to stick it to, whether in an electrical room or on a rooftop. ...
  29. Replies
    7
    Views
    659

    Do you have your heart set on the "Delta"-style...

    Do you have your heart set on the "Delta"-style enclosure? Kele sells a couple different styles of empty room sensor enclosures - you might find that their WMB-4 is a little more modern looking, and...
  30. Thread: TStat

    by davem
    Replies
    4
    Views
    565

    Honeywell T7350M has the outputs you need - well,...

    Honeywell T7350M has the outputs you need - well, except for that 2-15 volts...the stat delivers 4-20mA, which you'd need to convert to the voltage you need...
  31. Replies
    25
    Views
    3,867

    And there's the problem - for as nice as the...

    And there's the problem - for as nice as the Johnson stuff is, it absolutely doesn't play well on the same MS/TP trunk as other manufacturers. Figure out how to put the JCI stuff on their own trunk,...
  32. Hey, that's faster and easier!

    Hey, that's faster and easier!
  33. Use the Program Service to locate all...

    Use the Program Service to locate all history/NumericIntervalHistoryExt, and edit the property "enabled" slot to true.
  34. Replies
    8
    Views
    857

    And Y2K didn't garf the calendar!!

    And Y2K didn't garf the calendar!!
  35. Replies
    2
    Views
    394

    Yep - you'll have no problem seeing the CSC's,...

    Yep - you'll have no problem seeing the CSC's, and getting great gobs of points off of them - their validity depends on the CSC's configuration, of course, but you'll have no problem with the driver...
  36. Okay, but you better remove that email address...

    Okay, but you better remove that email address post haste, or the mods are gonna remove it for you...
  37. Replies
    7
    Views
    603

    Yeah, that's the feeling I'm getting - thanks for...

    Yeah, that's the feeling I'm getting - thanks for the input.
  38. Replies
    7
    Views
    603

    Well yeah, that kinda sorta does the N2 side, but...

    Well yeah, that kinda sorta does the N2 side, but what about the various GPL process setpoints, etc. that aren't N2 points? Or am I missing something? While keeping the NCM's in play for now is a...
  39. Replies
    7
    Views
    603

    NCMs into AX possible?

    It's been a few years since this topic saw any activity on this forum, so instead of resurrecting an old thread, I thought I'd renew the question:

    Has anyone developed an N1 driver solution...
  40. Replies
    7
    Views
    664

    I doubt that Obix is the solution theoldman is...

    I doubt that Obix is the solution theoldman is looking for, since that would leave the r2 JACE in place, which isn't a good long-term solution...plus, selling a Tridum-to-Tridium integration would...
  41. I tried to attach the handy spreadsheet I use to...

    I tried to attach the handy spreadsheet I use to calculate the linear scale and offset for inputs and outputs, but can't attach an xlsx, xls, or csv...so I'll just give you the answers:

    For...
  42. Replies
    6
    Views
    689

    Did you remember to change the dipswitches on the...

    Did you remember to change the dipswitches on the comm board as well? If memory serves (the document is somewhere on my other laptop...), dipswitch 1 is up, 2 and 3 are down. Be aware that the...
  43. Thread: AAM bus

    by davem
    Replies
    13
    Views
    923

    I completely agree with everything stated - the...

    I completely agree with everything stated - the idea of using 4/C cable certainly isn't a technically-supported one, and the fact that it has "worked" on a few occasions is in no way an endorsement...
  44. Thread: AAM bus

    by davem
    Replies
    13
    Views
    923

    I'm almost afraid to chime in here, given how...

    I'm almost afraid to chime in here, given how quickly the discussion turned to contractor skill...but I know exactly what happened here, as you described something I've run across a thousand times...
  45. Well, how cool is that? I was being more than a...

    Well, how cool is that? I was being more than a little facetious, being well aware of what a ridiculous task it would be to disconnect all the controllers, just to find the length of the...
  46. Yeah, I really think Marc has it right - the...

    Yeah, I really think Marc has it right - the length of the cabling be determined by an ohm-meter only if the network is completely powered-down (and provided the entire daisy-chain is comprised of...
  47. Replies
    4
    Views
    1,522

    There's a couple things that might trip you up,...

    There's a couple things that might trip you up, if you wanted to go down the path of removing the BCU's to replace them with JACE's...

    1) The Intellipaks might be Comm3, but if they contain the...
  48. Replies
    2
    Views
    340

    Have you tried this? I've used it successfully on...

    Have you tried this? I've used it successfully on several occasions, on everything from a failed upgrade to a fresh-out-of-the-box DOA JACE.
  49. Replies
    3
    Views
    464

    It looks like I couldn't change the text like I...

    It looks like I couldn't change the text like I thought on a new MultiValue Network Input...but I was able to specifically do what the original post asked: when building a hybrid activity, the Select...
  50. Replies
    3
    Views
    464

    I believe that if you select States(x) for your...

    I believe that if you select States(x) for your Enum set, and expose them to BACnet (which is a strange requirement, but crucial for customization), you will then be able to input custom state text...