  1. Isn't the 2 the BACnet device ID? Changing it to...

    Isn't the 2 the BACnet device ID? Changing it to 16 would make the packet to be sent to device 16 not priority level 16.

    kontrol out
  2. Replies
    10
    Views
    345

    This. I have seen a 16 motor fan wall section run...

    This. I have seen a 16 motor fan wall section run off four variable frequency drives. Four motors per drive, each with it's own contactor.

    kontrol out
  3. From my limited knowledge the router must be...

    From my limited knowledge the router must be configured via hyper-terminal and a null modem cable.

    kontrol out
  4. Replies
    4
    Views
    328

    Trash? kontrol out

    Trash?

    kontrol out
  5. Keep the teachers happy/comfortable so they don't...

    Keep the teachers happy/comfortable so they don't sic the teacher's union onto the district.

    kontrol out
  6. Replies
    52
    Views
    3,362

    I love how LON fanboi has to keep bringing the...

    I love how LON fanboi has to keep bringing the lvb subject up to justify their poor choice in protocol.

    kontrol out
  7. Replies
    7
    Views
    621

    You ain't kidding, and lots of them just have mb...

    You ain't kidding, and lots of them just have mb codes for names/descriptions.

    kontrol out
  8. Replies
    16
    Views
    1,596

    ALCshare forum has the weather program. ...

    ALCshare forum has the weather program.

    kontrol out
  9. Replies
    37
    Views
    11,066

    I have what you seek young padawan. Have no way...

    I have what you seek young padawan. Have no way to contact you other than using the force. My email is in my profile, reach out and contact me.

    kontrol out
  10. Thread: vav help

    by kontrolphreak
    Replies
    6
    Views
    422

    You can buy an over-the-counter VAV controller...

    You can buy an over-the-counter VAV controller from http://www.bacnetcontrol.com/shop/. This one here: http://www.bacnetcontrol.com/shop/hvac-controls/10-vav-controller-relay.html. Config software is...
  11. Replies
    33
    Views
    5,818

    Never mind. kontrol out

    Never mind.

    kontrol out
  12. Replies
    8
    Views
    656

    Please don't post your emails in any thread as it...

    Please don't post your emails in any thread as it is against site rules.

    kontrol out
  13. Replies
    16
    Views
    853

    Cylon buys AAM

    http://controltrends.org/2014/07/cylon-energy-inc-acquires-american-auto-matrix/

    kontrol out
  14. Replies
    3
    Views
    509

    If OAT is greater then 60degF and valid or...

    If OAT is greater then 60degF and valid or operator allows cooling when OAT is invalid and the follow (calculated in other parts of the program):
    System needs cooling.
    Economizer is in cooling....
  15. Replies
    7
    Views
    332

    A couple of vendors (Andover and Siemens) have...

    A couple of vendors (Andover and Siemens) have their own wireless BACnet/MSTP devices. Andover works as advertised, have not had any experience with Siemens' offering. Other option is using IP...
  16. Replies
    4
    Views
    636

    The most beneficial manual will be the Microblock...

    The most beneficial manual will be the Microblock Reference Guide and using EquipmentBuilder to generate programs that you can then dissect and learn about. The simulation feature in Eikon is an...
  17. Replies
    10
    Views
    488

    It probably is using a typical program for each...

    It probably is using a typical program for each piece of typical equipment. Each program has an address in the Ivu to CCN router (just a guess that this is where the programs reside), program 1 has...
  18. Replies
    25
    Views
    2,587

    I have had issues with Danfoss and not setting...

    I have had issues with Danfoss and not setting the max master in the highest MAC addressed drive. I would set it to a couple of addresses above it's MAC and see if that helps.

    kontrol out
  19. Replies
    25
    Views
    2,587

    My guess is JCI@38.4Kbs. As the MAC address...

    My guess is JCI@38.4Kbs. As the MAC address starts at 4, I know JCI reserve 0-3 and generally run at 38.4Kbs.
    Just a guess.

    kontrol out
  20. Software can be one of the freewares online such...

    Software can be one of the freewares online such as WACnet or InneaSoft BACnet Explorer ( demo version ) and even some on SourceForge, device is Contemporary Controls portable BACnet/MST router...
  21. This is why I carry a third-party BACnet to MSTP...

    This is why I carry a third-party BACnet to MSTP router and 3 or 4 BACnet applications. If none of them can discover the device I throw it back in the vendors court and/or installers court if it is a...
  22. Neither, superior Betamax technology! ...

    Neither, superior Betamax technology!

    http://ecx.images-amazon.com/images/I/512T3CT82HL._SL500_AA300_.jpg
    http://cdn.doyouremember.com/wp-content/uploads/2013/06/betamax-1.jpg

    kontrol out
  23. To answer the question in the title of the...

    To answer the question in the title of the thread, a stick. Caveman used a stick to move around the embers in his fire to reduce or increase the btu of the heat source. And that my friend is history....
  24. Replies
    7
    Views
    732

    Java Application Control Engine. BTW it's...

    Java Application Control Engine.

    BTW it's BACnet not BacNet.

    kontrol out
  25. Replies
    5
    Views
    513

    One if the systems I work with regularly does...

    One if the systems I work with regularly does this. It does not have a Multi-State network variable so we use Analog network variables to read and write to Multi-State BACnet objects. When we are...
Results 1 to 25 of 500
Page 1 of 20 1 2 3 4
Comfortech Show Promo Image

Related Forums

Plumbing Talks | Contractor Magazine
Forums | Electrical Construction & Maintenance (EC&M) Magazine
Comfortech365 Virtual Event