Search:

Type: Posts; User: black_syphilis

Search: Search took 0.00 seconds.

  1. Replies
    5
    Views
    229

    Problem solved. I sent serial number and date...

    Problem solved.

    I sent serial number and date to AAM and they sent me a master password level 3.

    I think they should add feature to restrict the upload of the app without an operator level...
  2. Replies
    5
    Views
    229

    My problem is I change level operator (3 to 1)...

    My problem is I change level operator (3 to 1) and after to upload configuration file import and export SD option disappear from BBC menu I can't do anything without this option...

    There is a...
  3. Replies
    5
    Views
    229

    BBC-SD Factory Reset

    Hi all,

    How can I make a factory reset to my touscreen BBC-SD?

    Thanks
  4. Replies
    7
    Views
    514

    Looking for ultrasonic flow meter

    Hi guys,

    I'm looking for a ultrasonic flow meter (BACnet or modbus or pulse) for a 3'' piping.
    Budget and delay are tight.

    Thanks.
  5. Replies
    29
    Views
    1,411

    Try to reset your Jace. Connect your PC to Jace...

    Try to reset your Jace.
    Connect your PC to Jace through Shell mode and select Reboot
    During boot, a message will appear like:
    Press any key to restore factory defaults
  6. Replies
    29
    Views
    1,411

    And What is your workbench and Jace 7 version ?

    And What is your workbench and Jace 7 version ?
  7. Replies
    29
    Views
    1,411

    Your error window when you try to enter in your...

    Your error window when you try to enter in your platform like this

    http://img11.hostingpics.net/pics/186798ScreenShot362.png
  8. Replies
    29
    Views
    1,411

    Can you send Details from error window

    Can you send Details from error window
  9. Allen Bradley Micro850 Modbus Error

    Hi all,

    I have a AB Micro 850 and I want transfer data in modbus TCP but I have an error on my MSG_MODBUS2 module

    ErrorID 33 (A bad MSG file parameter exists)
    SubErrorID 37 (???)

    Anyone...
  10. Replies
    4
    Views
    359

    No first installation and no message to create...

    No first installation and no message to create user
  11. Replies
    4
    Views
    359

    KMC BACstage Password

    Hi,

    I installed KMC BACstage. What is the Master Operator Name/Password??

    Regards.
  12. Replies
    0
    Views
    270

    FX7 Memory glitch

    Hi all,

    I have a FX-7 with BACnet network (23 Devices (Alerton VAV), 20 pts each), 2x N2 Network (30 Devices each (VMA), 20 pts each).

    The problem is sometime I lost station (reboot).

    I...
  13. Replies
    18
    Views
    1,716

    The building is 25 years old. I will purpose an...

    The building is 25 years old. I will purpose an air balancing.



    Yes I think I can add one static pressure for each floors, I will move the pressure sensor on 2/3 of duct. Why do you see wild...
  14. Replies
    18
    Views
    1,716

    We want centralize all tenant room, among other...

    We want centralize all tenant room, among other things, for high and low temperature watch.




    Good point. But what can I do with my chiller if I slowdown the VFD?

    It's a chiller Trane RTWD...
  15. Replies
    18
    Views
    1,716

    Can you to be most clear in your explaining? I...

    Can you to be most clear in your explaining?

    I have a boiler and chiller system.
    I calculated energy saving and If I stop the AHU systems all the night, I save $20,000.00 by year. I will paid my...
  16. Replies
    18
    Views
    1,716

    Dual Duct + VFD

    Hi All,

    I have a building 6 Floors with 2 HUA (Perimeter: Cooling Only; Interior: Dual Duct).
    I want stop the units during the night and weekend but sometime there are some tenants on some floor...
  17. Replies
    6
    Views
    647

    There is not DDC, just 4 stages command. The...

    There is not DDC, just 4 stages command.
    The quoting is $ for add Tekmar indoor/outdoor controller.

    Suppose to maximize the performance of the boiler and establish savings on gaz consumption
  18. Replies
    6
    Views
    647

    No, Raypak is existing

    No, Raypak is existing
  19. Replies
    6
    Views
    647

    Raypak Controller

    Hi all,

    I have a boiler Raypak model H9-2342B, the DDC control the 4 stages. A contractor recommend me to install a boiler controller like Tekmar Indoor/Outdoor, 4 stages. What you think about...
  20. Replies
    44
    Views
    6,290

    30P is correct but so so compare FG series

    30P is correct but so so compare FG series
  21. I'm bashing some Alerton products because it's...

    I'm bashing some Alerton products because it's right. I don't want educate you, but please shows me I wrong about some Alerton products, I'm listening :pop:
  22. Replies
    44
    Views
    6,290

    First Trend controls IQ3 ( I'm sentimental ) ...

    First Trend controls IQ3 ( I'm sentimental )

    Second EASY IO FG <-- ****ing great product, don't forget to vote for him #ControlTrendsAward
  23. Why alerton products are not the best?

    Why alerton products are not the best?

    - Old programming software and Visio plugin
    - Programming not really user friendly
    - Envision is obsolete
    - Webtalk is a joke
    - BCM-WEB can make Ice...
  24. Replies
    9
    Views
    1,664

    Sure, what is your problem?

    Sure, what is your problem?
  25. Replies
    10
    Views
    1,492

    What is the link between the BACnet user with...

    What is the link between the BACnet user with write permissions and the other BACnet software?
  26. Replies
    9
    Views
    1,664

    It's not an obligation to take the 6000 course...

    It's not an obligation to take the 6000 course for buy 963. For you information, 963 is very easy!
    Don't hesitate to contact me by email (In my profil) if you need help or 963 example :putergreet:
  27. Replies
    10
    Views
    1,492

    Bad day! I integrated my modbus Thermopump to...

    Bad day!

    I integrated my modbus Thermopump to BACnet MSTP, I can read all my BACnet point BUT I can't write on them with third software (Bacstage / Metasys / Orcaview), it's said like Write...
  28. Replies
    10
    Views
    1,492

    [QUOTE=noskilltech;14675321]You do not need a...

    [QUOTE=noskilltech;14675321]You do not need a link when you export a point in the Bacnet Export Manager. You just discover the points you want to export and give them an AV or BV number.

    Oh yeah...
  29. Replies
    9
    Views
    1,664

    You must have another licence for your laptop. ...

    You must have another licence for your laptop.

    Aren't you a Trend dealer?
  30. Replies
    10
    Views
    1,492

    Ok and after just a link between Modbus and...

    Ok and after just a link between Modbus and BACnet point?
  31. Replies
    9
    Views
    1,664

    Hi, What you mean by "I need to do standalone...

    Hi,

    What you mean by "I need to do standalone T&C through local Laptop"

    You can't use one 963 license for many PC.

    If you want you can install your 963S on your standalone laptop, but it's...
  32. Replies
    10
    Views
    1,492

    Tridium AX ModbusTCP to BACnetMSTP

    Hello,

    I have a heat pump with Gforce supervisor system and a Jace2.
    The communication of HP is ModbusTCP and need translate the HP to BACnet MSTP

    On the Jace, I created a BACnet network and a...
  33. Replies
    13
    Views
    808

    Can you post a printscreen of Resource Manager?

    Can you post a printscreen of Resource Manager?
  34. Replies
    5
    Views
    1,472

    Tips for safwan It's better for you to rewrite...

    Tips for safwan
    It's better for you to rewrite the strategy!

    I confirm you , pressure independent is include.




    IQview8 is a joke... hum... no, it's a good products with beautiful graphic...
  35. Replies
    14
    Views
    3,966

    You can mix Raspberri PI + arduino + Niagara...

    You can mix Raspberri PI + arduino + Niagara Supervisor for linux = Small web controller (Powered by Niagara AX Framework) !!!
  36. Replies
    6
    Views
    1,017

    I don't understand the Trend strategy with TOPS,...

    I don't understand the Trend strategy with TOPS, 963/TOPS/BINC is too "complicate" and more expensive... It's like cat food,
    "You're boring with your niagara, we have develop TOPS, take and leave...
  37. Noob with Spyder ILC

    Hello,

    I have a Spyder ILC and a niagara AX platform (TES - Trend).

    Normally I don't need spyder tool or other, right?

    I can discover the spyder but that's all, I can't configure or add...
  38. Noob with Spyder

    Hello,

    I have a Spyder ILC and a niagara AX platform (TES - Trend).

    Normally I don't need spyder tool or other, right?

    I can discover the spyder but that's all, I can't configure or add...
Results 1 to 38 of 38