Search:

Type: Posts; User: kontrolphreak

Page 1 of 20 1 2 3 4

Search: Search took 0.04 seconds.

  1. Replies
    289
    Views
    56,617

    Got it to work once and IP address was entered in...

    Got it to work once and IP address was entered in the BCM, as stated it didn't display any points when I was using a IP to Ethernet router. Once I was connected directly to the BCM via IP everything...
  2. Replies
    289
    Views
    56,617

    Does the BCM-TUX convert the TUX controller...

    Does the BCM-TUX convert the TUX controller objects into BACnet objects or does BACTalk use some other voodoo to display the proprietary points? I can see all the TUX controllers with another BACnet...
  3. Replies
    4
    Views
    314

    BBMD only routes to 1 controller on the IP...

    BBMD only routes to 1 controller on the IP subnet, other controllers need to be on a separate network for the BBMD to route to and from them. The secondary network can be IP, Ethernet or MSTP. Most...
  4. Replies
    2
    Views
    183

    Or SuckstureWare possibly. kontrol out

    Or SuckstureWare possibly.

    kontrol out
  5. End users can be set up by their local dealer for...

    End users can be set up by their local dealer for access to the documentation and software update downloads.

    kontrol out
  6. It's not proprietary bs, the proprietary side is...

    It's not proprietary bs, the proprietary side is an improvement over LON in Vista. More functionality and way easier to set-up, just way harder to sell in this "everything must be open" world we live...
  7. Replies
    4
    Views
    300

    I would add another controller to the MSTP...

    I would add another controller to the MSTP network that was not auto baud and set it to the speed you want the network to defualt to, that way if you lose the BCM the other fixed speed controller...
  8. Replies
    3
    Views
    223

    Welcome to the forum, Capslock can be found to...

    Welcome to the forum, Capslock can be found to the left edge of your keyboard.

    Does they network have EOL terminators installed?

    Is it the correct wire?

    Is the network ran in a daisy chain...
  9. Replies
    55
    Views
    19,370

    i) BACnet device instance is actually a property...

    i) BACnet device instance is actually a property of the device object. Some devices will allow a BACnet write service to modify this property, some require a proprietary service to modify it. Device...
  10. Replies
    55
    Views
    4,058

    I prefer reel to reel, or if that is not...

    I prefer reel to reel, or if that is not available 8 track.

    kontrol out
  11. Replies
    20
    Views
    3,046

    So anyone using Sweet Home for their 3D...

    So anyone using Sweet Home for their 3D floorplans? Just came across it today and was wondering if it was a viable solution for graphics?

    kontrol out
  12. Replies
    25
    Views
    1,081

    Another option is the ICC ETH-1000 or XTLR-1000....

    Another option is the ICC ETH-1000 or XTLR-1000.

    kontrol out
  13. Replies
    25
    Views
    1,081

    You can download the software application and a...

    You can download the software application and a capture to evaluate if it will meet your needs from their website.

    kontrol out
  14. Replies
    25
    Views
    1,081

    I had to buy it from their online store, they...

    I had to buy it from their online store, they convert EU$ to US$ straight. Was delivered in under 5 days. I have only got to test it on my test bench at work and found it very functional, just didn't...
  15. Replies
    25
    Views
    1,081

    Then take a look at this: MSB-485...

    Then take a look at this:

    MSB-485

    Handy little gadget.

    kontrol out
  16. Replies
    25
    Views
    1,081

    You should be able to set it's MAC to one that's...

    You should be able to set it's MAC to one that's not being used and make sure the IP network isn't the same as your other router. Just like using a Contemprary Controls BASRT-P on a network that...
  17. Replies
    25
    Views
    1,081

    Here it is: ...

    Here it is:

    http://www.loytec.com/products/routers-nic/lip-bacnet

    kontrol out
  18. Replies
    21
    Views
    1,013

    Good to hear you finally got your issue resolved....

    Good to hear you finally got your issue resolved.

    kontrol out
  19. Replies
    55
    Views
    4,058

    I'm confident my technology works for 99% of my...

    I'm confident my technology works for 99% of my applications and don't feel I have to remind everyone else how superior it is every 6 or so months. "Qu'ils mangent de la brioche"

    kontrol out
  20. Replies
    55
    Views
    4,058

    How did this go from a worst controller ever to a...

    How did this go from a worst controller ever to a my **** is bigger than your **** thread?

    kontrol out
  21. Replies
    21
    Views
    1,013

    Remember back in the day when equipment came with...

    Remember back in the day when equipment came with a phone number to the manufacturer's tech support? Man do I miss those days.

    kontrol out
  22. ASHRAE Guideline 36P - High Performance Sequences of Operation for HVAC Systems

    Anyone else using this guideline to program their systems? I have used the trim and respond reset logic for a few years now and find it very functional.

    ASHRAE 36P

    I hadn't heard about it till...
  23. Replies
    289
    Views
    56,617

    In the BCM BACnetIP setup there is a setting for...

    In the BCM BACnetIP setup there is a setting for configuring BACnetIP services which is a selection from 0 to 7, does anyone have a breakdown of what each setting does/enables?

    kontrol out
  24. This retrofit controller from Blue Ridge...

    This retrofit controller from Blue Ridge Technologies is made for such change outs. Data sheet indicates they are compatible with GE RR7, RR8 and RR9 relays. Just priced out a bunch and the pricing...
  25. Replies
    5
    Views
    587

    Unless they have the latest drivers and programs...

    Unless they have the latest drivers and programs the setpoints are not going to be able to be exposed to the network.

    kontrol out
  26. Replies
    14
    Views
    731

    LOL kontrol out

    LOL

    kontrol out
  27. Replies
    9
    Views
    1,060

    This was my first thought as well. kontrol out

    This was my first thought as well.

    kontrol out
  28. Replies
    2
    Views
    258

    For programming you will need Menta, for database...

    For programming you will need Menta, for database management (network set up, data transfer configuration, trend creation etc.) you will need XBuilder, for ASC (unitary / zone ) controller...
  29. Replies
    289
    Views
    56,617

    If you can read object properties with...

    If you can read object properties with VisualLogic the date is property 56 ( Local_Date ) of the device object ( 8 ), if Alerton devices support this property( I would assume BCM do, not sure about...
  30. Replies
    289
    Views
    56,617

    By setting the "home" network that is where it...

    By setting the "home" network that is where it would show up on a system tree. It also effects where it routes data to and from. If it resided on all networks you would have duplicate virtual...
  31. Replies
    289
    Views
    56,617

    Not sure with Alerton, but on another couple of...

    Not sure with Alerton, but on another couple of BACnet systems you can select which network (port?) a router resides on if it has multiple networks (ports?). Generally it is a IP1 network on a router...
  32. Replies
    9
    Views
    1,060

    Wow! Two of the best products in the HVAC...

    Wow!
    Two of the best products in the HVAC controls market now owned by the same company.
    This is exciting news.

    kontrol out
  33. http://www.kele.com/network-and-wireless/displays....

    http://www.kele.com/network-and-wireless/displays.aspx

    I have used the BBC-SD and it works as advertised. The one issue is that it can only communicate to controllers on the MSTP segment it...
  34. Replies
    18
    Views
    2,897

    The only controller that Max Master will make a...

    The only controller that Max Master will make a difference on is the one with the highest MAC address.

    Once the token is handed off that controller stop looking for the next highest controller,...
  35. Replies
    9
    Views
    578

    Why not just use a VFD rated current transducer...

    Why not just use a VFD rated current transducer and read amps?

    kontrol out
  36. Replies
    18
    Views
    2,897

    Not a BACnet standard, just something JCI does. ...

    Not a BACnet standard, just something JCI does.

    kontrol out
  37. Replies
    5
    Views
    525

    There is free/demo software online from companies...

    There is free/demo software online from companies like Contemporary Controls, Chipkin Automation, Brightcore and Inneasoft. That coupled with a couple of cost effective BACnet controllers off eBay...
  38. Replies
    14
    Views
    1,684

    These guys have some nice graphics: ...

    These guys have some nice graphics:

    http://bassg.com/

    Alper is a top notch guy to work with as well.

    kontrol out
  39. Replies
    8
    Views
    434

    I have used multiple different RS-485 adapters on...

    I have used multiple different RS-485 adapters on different Modbus devices, all worked.

    kontrol out
  40. Replies
    5
    Views
    525

    My advice is to use the correct spelling of...

    My advice is to use the correct spelling of BACnet, use paragraphs, the correct use of capitalization and punctuation.

    kontrol out
  41. Replies
    2
    Views
    328

    There was some EOM software (from Venmar I think)...

    There was some EOM software (from Venmar I think) that allowed you to change comm settings, it worked on MSTP not sure if it worked on the IP level. If you have Delta's software changing the IP...
  42. Replies
    9
    Views
    549

    Yea BACnet! kontrol out

    Yea BACnet!

    kontrol out
  43. Replies
    9
    Views
    549

    Not sure if you can discover them before it has...

    Not sure if you can discover them before it has had it's device instance set but everyone I have come ac cross (already configured) had all the objects exposed (generic points, VAV controllers had 16...
  44. Replies
    9
    Views
    549

    You will require VisualLogic to program and...

    You will require VisualLogic to program and configure IO. From my understanding Alerton is the only source for the software and usb dongle to run it. You will also require BACTalk to configure the...
  45. Because Wiljami is asking about WebCTRL 6.0 and I...

    Because Wiljami is asking about WebCTRL 6.0 and I think you are answering about Tridium. Not sure, but I have never worked or heard of .nav in WebCTRL and I know that PX is to do with Tridium....
  46. Replies
    32
    Views
    1,537

    At least the drive comes with BACnet on board,...

    At least the drive comes with BACnet on board, with LON you need an external card and god forbid if they changed the xif file and you don't have a copy of the new one readily accessible. But I see...
  47. Replies
    32
    Views
    1,537

    I regularly work with BACnet systems that can...

    I regularly work with BACnet systems that can handle 99+ controller per 2 wire network- ALC / Delta / Reliable Controls all can do it. As to moving forward BACnet seems to be offering new controllers...
  48. Replies
    32
    Views
    1,537

    What are your percentages on main equipment...

    What are your percentages on main equipment programmable controllers?

    kontrol out
  49. Replies
    2
    Views
    291

    The Reliable Controls MACHPro-Web interface also...

    The Reliable Controls MACHPro-Web interface also does this on a user by user basis (not all uses need to have this enabled), great feature and the Audit Log displays the reason so it is simple for a...
  50. Replies
    22
    Views
    1,106

    Another thing about the Garmin is that it only...

    Another thing about the Garmin is that it only takes about 30 minutes to fully charge from dead. Was shocked at how fast it charges when I first got it, maybe this will change as the battery ages.
    ...
Results 1 to 50 of 1000