    If the motor is rated 575VAC @ 60Hz, the drive...

    If the motor is rated 575VAC @ 60Hz, the drive should provide 575VAC @ 60Hz. Usually a motor accepts a +/- 10% variation in input voltage which would be 632VAC. You measured 650VAC. If you apply...
  2. VFD compressor has benefits but disadvantages as...

    VFD compressor has benefits but disadvantages as well. Here a few:

    + superior water temperature control
    + increased part load efficiency
    + soft start
    + reduced compressor cycling
    + reduced...
  3. Replies
    2
    Views
    1,102

    Has anyone got the service manual for the LSC...

    Has anyone got the service manual for the LSC screw. The Hartford internet page doesnīt issue that.
  4. Replies
    7
    Views
    1,758

    The valve is physically the same, but might be...

    The valve is physically the same, but might be different from size. The control algorithm in the control is the same except of the low suction superheat action.
  5. Replies
    31
    Views
    6,380

    Itīs all about the NEMA rating of the panel:bump:

    Itīs all about the NEMA rating of the panel:bump:
  6. Replies
    44
    Views
    4,762

    The software version is ok. There are no issues...

    The software version is ok. There are no issues with the electronic expansion valve control. I suspect that the issue is when the compressor unloads to start the lag system. The degree of opening of...
  7. Replies
    44
    Views
    4,762

    The type of chiller you mentioned...

    The type of chiller you mentioned (YCAS0140EC17YGADBC) does indicate to me that it is a style G chiller. Form 201.18-nm1 does refer to style F chillers. They are basically quite the same but your...
  8. Replies
    44
    Views
    4,762

    Do you have the manual for the chiller? It is...

    Do you have the manual for the chiller? It is form 201.19-nm1. It is quite good, a lot of information about almost everything of the chiller.
  9. Replies
    44
    Views
    4,762

    It sounds to me that your YCAS has electronic...

    It sounds to me that your YCAS has electronic expansion valves? Does the chiller has suction line HTX installed? What refrigerant R22 or R407C? Do you know the software version of the EPROM?
  10. The following qoutation is from the...

    The following qoutation is from the article:"Undercover agents posing as members of an al Qaeda sleeper cell met with Smadi several times while the terrorist suspect hatched his plot to commit jihad,...
  11. Replies
    44
    Views
    4,762

    The solenoid valve on the compressor is a 3-way...

    The solenoid valve on the compressor is a 3-way pressure regulating valve. It does control the oil pressure applied to the slide valve in accordance to the current running (voltage applied to the...
  12. Replies
    44
    Views
    4,762

    You should check compressor #2 for proper slide...

    You should check compressor #2 for proper slide valve operation. The amount of starts to hours is an indication for a slide valve problem (slide valve stuck in high position, broken sv spring, lip...
  13. Replies
    153
    Views
    37,912

    The motor protection / CT module can be reseted...

    The motor protection / CT module can be reseted by removeing itīs 24V power supply. Therefore you have to check always if the mp module shows a fault code. If yes, the internal contact is open, this...
  14. Replies
    21
    Views
    4,590

    There is no connection between the coolant and...

    There is no connection between the coolant and the electrical power! The reason why deinonized water is used, is corrosion. But you should never use anything else in the system then the original...
  15. Replies
    19
    Views
    1,017

    I am really tired of reading silly complaints...

    I am really tired of reading silly complaints about Obama......It is not good if you do not stand behind your president, this encourages others to gain an advantage over America. Therefore, general...
  16. Replies
    21
    Views
    4,590

    What about to fit a much smaller 3 phase motor...

    What about to fit a much smaller 3 phase motor (e.g. 3hp) to the output of the SSS instead of the compressor motor? Then starting and take measurements until the chiller trips on something else (low...
  17. Replies
    21
    Views
    4,590

    I suspect that they are quite expensive, even the...

    I suspect that they are quite expensive, even the single SCR`s! It isnīt easy to test them, because you canīt test them under load. If you have access to a FLUKE 434 power analyzer you could probably...
  18. Replies
    21
    Views
    4,590

    It will have almost no affect on the starting...

    It will have almost no affect on the starting amps with or without compressor coupled, because the starting current is mainly caused by the breakaway torque on the rotor itself. The problem could be...
  19. If there are just a few days where you have...

    If there are just a few days where you have design ambient conditions you could consider to choose a smaller system (lower installation / equipment and operation costs) with an additional electrical...
  20. Thread: Reincarnation

    by Entropie
    Replies
    132
    Views
    4,347

    Scientificly itīs totally clear! Energy cannot...

    Scientificly itīs totally clear! Energy cannot disapear, only change itīs state. We are energy, hence we cannot disapear but we transform into something new. Probably a lot of the atoms and molecules...
  21. Replies
    0
    Views
    500

    worldīs most known rogues

    Who is worth to be listed?
  22. Thread: Water temp

    by Entropie
    Replies
    95
    Views
    9,848

    Sorry, but this does not allign with the facts i...

    Sorry, but this does not allign with the facts i know about HVAC! Your cooling loop is undersized or the heat transfer / conduction in the ground is less then calculated! If the ground loop canīt...
  23. Thread: Water temp

    by Entropie
    Replies
    95
    Views
    9,848

    As mentioned previously, the cooling/heating...

    As mentioned previously, the cooling/heating capacity of your system depends on the evaporating and condensing temperatures. Higher condensing temperatures cause efficiency and capacity losses. Bring...
  24. How many hrs in the year will be at design...

    How many hrs in the year will be at design conditions (maximum heat/cooling load)? The less it is it the more it makes sense to go for a two stage ac/hp and an additional electrical heater. Have you...
  25. Replies
    6
    Views
    1,864

    I did send you already a pn. So it seems to be...

    I did send you already a pn. So it seems to be enabled.......
  26. Replies
    6
    Views
    1,864

    Enable your private messageing, i will pass you...

    Enable your private messageing, i will pass you the information...
  27. Replies
    6
    Views
    1,864

    It is possible but you need some experience with...

    It is possible but you need some experience with York products. The letters prior to the serial number do indicate the place and date of manufacturing of the chiller. So letīs start and post a few of...
  28. Replies
    7
    Views
    1,758

    The EEV on the YCAL is basically a thermostatic...

    The EEV on the YCAL is basically a thermostatic expansion valve with a heater at the bulb. The heater is fired with a 24V PWM signal to maintain the suction superheat setpoint. One end of the bulb is...
  29. Before the new coil has been installed you had...

    Before the new coil has been installed you had no problems, with the new coil you have. It is likely that there is a relationship. But sometimes it is difficult to reveal all problems on the first...
  30. Replies
    17
    Views
    5,547

    They are not mandatory but good for quick...

    They are not mandatory but good for quick reference / trouble shooting on a system. HVAC experts do not really need em:D
  31. Thread: Water temp

    by Entropie
    Replies
    95
    Views
    9,848

    The differences in water inlet to water outlet do...

    The differences in water inlet to water outlet do indicate that the flow rate is right. The temperature level is to high, you should ask what the original design temperatures where. This does...
  32. Replies
    29
    Views
    1,306

    I agree, replacement jobs with already installed...

    I agree, replacement jobs with already installed ductwork are far more difficult. Maby a two stage unit with a vsd fan can increase comfort/efficiency under off design conditions....But there will be...
  33. Replies
    29
    Views
    1,306

    I assume that not many customers will complain...

    I assume that not many customers will complain about a rule by thumb choosen unit because they are probably larger then needed. And a lot of customers perhaps even donīt know how "good" a proper...
  34. Replies
    4
    Views
    700

    I perform chargeing only in accordance to liquid...

    I perform chargeing only in accordance to liquid subcooling and suction superheat on DX systems, and the evaporator/condenser approach on flooded systems.
  35. What do you mean with low capacity? 0.5 tons, 5...

    What do you mean with low capacity? 0.5 tons, 5 tons or 500 tons? Which refrigerant, application? Ammonia, CFC, HFC? Which evaporating, condensing temperature?
  36. Replies
    6
    Views
    896

    This is only true in case of a motor burn out!...

    This is only true in case of a motor burn out! But two smaller compressors are better then one large under part load conditions (better efficiency). Full load conditions are only in 3% of the total...
  37. Thread: York D3CG

    by Entropie
    Replies
    2
    Views
    2,219

    As FLA says (Full Load Amps)........when the...

    As FLA says (Full Load Amps)........when the motor is not fully loaded it does draw less current then the FLA. On a fan motor this can be achieved by pumping less air through the impeller. It is...
  38. Thread: Water temp

    by Entropie
    Replies
    95
    Views
    9,848

    I donīt believe in any way that it takes 7 days...

    I donīt believe in any way that it takes 7 days for the temperature in the drilling hole to equalize! The average temperature in earth is about 50°F within the dept you mentioned. Have you seen the...
  39. Replies
    22
    Views
    1,447

    A proper installed shaft seal (with oil on the...

    A proper installed shaft seal (with oil on the mating surfaces) does withstand the vacuum that has been mentioned. Donīt forget to check the shaft seal oil pressure and adjust if neccessary when you...
  40. Replies
    153
    Views
    37,912

    At the time the starting command has been...

    At the time the starting command has been released by the controller the current monitoring starts. If there is no current read by the three phase module for 3 seconds, the chiller trips on the...
  41. You should adopt the metric system! The Britains...

    You should adopt the metric system! The Britains did it and even the NASA turned to it. So power is in Watt, which by the way makes sense.:D
  42. Replies
    45
    Views
    1,296

    I would appreciate that! We in Germany...

    I would appreciate that! We in Germany experiencing actually exactly the same as you in the US. Our export industries dropped by 30% within one year! We broke a 40 years old record of unemployed...
  43. Replies
    45
    Views
    1,296

    This wouldnīt help......our asses have been...

    This wouldnīt help......our asses have been already sold for Russian gas.......:D
  44. Replies
    45
    Views
    1,296

    You shouldnīt fear Obama because almost half of...

    You shouldnīt fear Obama because almost half of your country has already been sold to Mao and the Sonyland connection.........:D

    http://en.wikipedia.org/wiki/United_States_public_debt
  45. Replies
    11
    Views
    2,188

    I like them, they are a different from the...

    I like them, they are a different from the ordinary equimpment. The single stages in hot water application (waste heat from processes) are quite popular here. Steam as well but we have almost no...
  46. Replies
    3
    Views
    1,391

    I would recommend you to send it back to Danfoss...

    I would recommend you to send it back to Danfoss for investigation. Have you done all the recommended (short/shielded power wiring to motor, output filter), dedicated set up of the motor parameters)...
  47. Replies
    11
    Views
    2,188

    I did assume that all refrigerant has already...

    I did assume that all refrigerant has already been transferred on a dilution cycle and the chiller is off for a longer period (winter time) with the steam valve leaking. Steam control valves are not...
  48. Replies
    45
    Views
    1,528

    I consider George W. Bush to be the worst...

    I consider George W. Bush to be the worst president ever (and probably for all times as well, but this is my opinion as a European)...........:D. So basically the good news are it canīt become worse!
  49. Replies
    83
    Views
    3,571

    TXV?, EXV?, capillary tube?, liquid receiver?...

    TXV?, EXV?, capillary tube?, liquid receiver? Whatīs the unit like?
  50. Replies
    11
    Views
    2,188

    Agree, if you are a absorber specialist (like you...

    Agree, if you are a absorber specialist (like you :D) but difficult for others. If it completely crystalized it will need to have deionized water to add to make it work again. Am i right?
Results 1 to 50 of 160
Page 1 of 4 1 2 3 4
Comfortech Show Promo Image

Related Forums

Plumbing Talks | Contractor Magazine
Forums | Electrical Construction & Maintenance (EC&M) Magazine
Comfortech365 Virtual Event