Search:

Type: Posts; User: wojami

Page 1 of 3 1 2 3

Search: Search took 0.00 seconds.

  1. Replies
    1
    Views
    235

    In the property sheet of the History Points list...

    In the property sheet of the History Points list there is a slot called "time window" where you can tell it how many hours in the past to display.
  2. Thread: Trane Tracer TU

    by wojami
    Replies
    1
    Views
    401

    Trane Tracer TU

    Anyone know where to buy Trane's Tracer TU software other than the local trane office?
  3. Replies
    5
    Views
    907

    You cannot just swap out controllers without re...

    You cannot just swap out controllers without re assigning the neuron ids in tracer summit. When you see values on the graphic it will still be from the old controller.

    Do you have rover software...
  4. Replies
    26
    Views
    6,775

    There is a new beta ui out that does not use...

    There is a new beta ui out that does not use java. It is alot faster since it caches data but like I said it is beta until after the first of the year or later. It does have several bugs but it...
  5. Replies
    43
    Views
    9,200

    It seems to me if we are talking "Bacnet" that we...

    It seems to me if we are talking "Bacnet" that we already have the "barcode" that you are referring to in MAC addresses/ IP addresses. Each device is already unique, it would be a matter of plotting...
  6. Thread: Tracer SC

    by wojami
    Replies
    8
    Views
    1,183

    I dont not know exactly, I dont think there is a...

    I dont not know exactly, I dont think there is a set number. Alot depends on how loaded up it is devices, programming, graphics. From what I read it says it can store 40 million points with 15 min...
  7. Thread: Tracer SC

    by wojami
    Replies
    8
    Views
    1,183

    Current version of Tracer SC , 5 concurrent...

    Current version of Tracer SC , 5 concurrent users. Tracer ES depends on the version of SQL you have. If SQL Express, 30 concurrent users. If full licensed SQL, 100 concurrent users.
  8. Replies
    5
    Views
    430

    You should only control a point or variable once....

    You should only control a point or variable once. In situations like this I usually use local(*L0 -*L7 or real variables(R0-*R3) . You can use up to four real and 8 local in each program, they only...
  9. Replies
    7
    Views
    1,452

    I don't think it is the controllers that are the...

    I don't think it is the controllers that are the problem. It's the tu software/sc that is extremely slow. If you do a spy to analyze the link it is actually passing info very fast.
  10. Replies
    7
    Views
    1,186

    Shoot me an email and I will send you a file so...

    Shoot me an email and I will send you a file so you wont have to type that in every time. Email is on profile.
  11. Replies
    7
    Views
    1,186

    Sorry, the lon"x" should be whatever number your...

    Sorry, the lon"x" should be whatever number your echelon adapter uses. Mine is 1 but it could be different. It should be the same as whatever lon software you use. If you use rover it will be the...
  12. Replies
    7
    Views
    1,186

    I'm thinking 1.08 or 2.08 off the top of my head...

    I'm thinking 1.08 or 2.08 off the top of my head I will have to look. Mine always did that before, I would open Cmd and point it to the nodeutil.exe file and then -d Lon x to use my echelon adapter....
  13. Replies
    7
    Views
    1,186

    My nodeutil works fine on windows 7 with the...

    My nodeutil works fine on windows 7 with the echelon adapter. Hyperterminal is not included on windows 7. But you can copy the files off of a xp computer and it will work.
  14. Replies
    2
    Views
    473

    I usually get that winsock error when there are...

    I usually get that winsock error when there are duplicate ip addresses.
  15. Replies
    6
    Views
    521

    Go to belimo's website, their product guide as...

    Go to belimo's website, their product guide as alot of useful info. Valves, actuators, as well as wiring diagrams for all the different applications.
  16. Replies
    6
    Views
    1,118

    I have always used bcu config utility, it is...

    I have always used bcu config utility, it is located in the tracer summit bin folder
  17. Replies
    6
    Views
    1,154

    I did write some of the points from a jace, and...

    I did write some of the points from a jace, and it was a KCC unit. But, I would be very hesitant to take a program and have someone just dump it in. A lot of things could have changed and if the...
  18. Replies
    6
    Views
    1,154

    If these are the units I'm thinking of they are...

    If these are the units I'm thinking of they are made and programmed for trane. Everything is setup/controlled from the operator display . Features are turned on/off and set points are changed there...
  19. There is no master user/password since by default...

    There is no master user/password since by default security isn't set up. You will have to get it somehow. I don't know of a back door but their could be one but it might require trane tech support.
  20. Replies
    22
    Views
    3,101

    The drawback to the ES lite/express is the...

    The drawback to the ES lite/express is the memory. You are limited to 4 gb I believe. If you are going to do alot of trending it could be a problem. You are also limited to 5 bcu's/ sc's. Good fit...
  21. Replies
    12
    Views
    1,986

    I have a site site with some ahir handlers with...

    I have a site site with some ahir handlers with chw preheat oa/ra that the pid just locks up periodically and takes hours to days to go back to normal. If they are at version 5.1 you can map a bv...
  22. Replies
    4
    Views
    496

    You can use a bcu to communicate with vav I's....

    You can use a bcu to communicate with vav I's. Not sure what your wanting to communicate with. The bcu has to be at a high enough image and have a high enough service pack to do this.
  23. Replies
    4
    Views
    635

    It seems I am doing it fairly close to the same...

    It seems I am doing it fairly close to the same way. Your fight discharge air control with dx is tough. Its always interesting to see others methods. I have added both on and off delays as well as...
  24. Replies
    12
    Views
    1,986

    Hopefully the adaptive tuning has improved or...

    Hopefully the adaptive tuning has improved or been removed on the FEC controllers. It is anything but adaptive.
  25. Replies
    2
    Views
    442

    I have always had the best luck with modbus...

    I have always had the best luck with modbus registrys by going to the manufacturers site. This si usually open info.
Results 1 to 25 of 68
Page 1 of 3 1 2 3
Comfortech Show Promo Image

Related Forums

Plumbing Talks | Contractor Magazine
Forums | Electrical Construction & Maintenance (EC&M) Magazine
Comfortech365 Virtual Event