Search:

Type: Posts; User: Frosty_VA

Page 1 of 2 1 2

Search: Search took 0.00 seconds.

  1. Replies
    7
    Views
    354

    In my experience open air cases run lower low...

    In my experience open air cases run lower low side pressures - 33-36psi for R404a, maybe you put too much refrigerant? I know you weighed charge but on these critically charged systems 2-3 ounces can...
  2. Don't get me wrong, Promaster might be ok for...

    Don't get me wrong, Promaster might be ok for delivery guys or light duty purposes where no need for giant 5.4 v8 or 6.7 v10 or whatever. But for HVAC or plumbers with extremely heavy loads ... front...
  3. I drive company RAM ProMaster 3500 with utility...

    I drive company RAM ProMaster 3500 with utility body. V6 front Wheel Drive Gas Engine. Too weak. I try to balance load by putting it closer to mid but still many many times front tires spin like...
  4. It was the ignitor - whether old one wasn't...

    It was the ignitor - whether old one wasn't reaching gas flow(I doubt it though) or ignitor itself was bad - but I got replacement from Trane, 80V, and it started right away. Thank you guys for help.
  5. Well since I used ignitor from other furnace I...

    Well since I used ignitor from other furnace I thought it might be wrong one(80v vs 110v) so I ordered one from Aireco by m# and s# of furnace. It'll be here on Tuesday(I hope) and we'll go from...
  6. 1.5" was measured at the outlet of gas valve. No...

    1.5" was measured at the outlet of gas valve. No cracks on HSI, its not the curved or U-shaped one, it is just a rectangular "stick" so to speak. Completely black, no white signs of wear. Burner is...
  7. Trane TCY100R9V4V0 has gas, good HSI, but no flame

    Hey guys I got Trane TCY 2 stage high eff furnace - I can see ignitor glowing yellow, measured 1.5" W.C. of gas @manifold(1st stage) but no flame. Ignitor turns yellow, gas valve opens for 2-3 sec,...
  8. Trane YC048 rooftop new gas valve, has spark, but doesn't ignite. Stumped...

    Hey guys I have a problem with rooftop Trane YCD048: I can hear it has spark, but it didn't start. I checked pressure switch and all limit switches - all closed. Checked voltage at gas valve - it has...
  9. Replies
    61
    Views
    4,975

    v10 6.4l ford e350 superduty 8mpg, v6 3.6...

    v10 6.4l ford e350 superduty 8mpg, v6 3.6 promaster's 11mpg
  10. Replies
    61
    Views
    4,975

    I drive promaster with 2000 miles on it. 3500...

    I drive promaster with 2000 miles on it. 3500 with utility body. 11mpg, tons of space, poor acceleration. engine can't keep up on a highway and often has to go 3500-4500rpms, which is never good in...
  11. fan cycle control might help you

    fan cycle control might help you
  12. Replies
    25
    Views
    1,928

    For that much space you might need to rent...

    For that much space you might need to rent portable trailer AC unit, they're pretty expensive though. What type of load(meeting hall, storage place etc) this place will have? How long you plan to...
  13. Replies
    3
    Views
    494

    CircusEnvy, thank you sooo much for the link, you...

    CircusEnvy, thank you sooo much for the link, you made my life so much easier.
  14. Replies
    4
    Views
    474

    Get kW ratio from name plate and turn it into...

    Get kW ratio from name plate and turn it into Btuhs, multiply by number of units you have. And get a Manual N book, load calc for commercial buildings.
  15. Replies
    10
    Views
    778

    Most gas stations have residential units, only...

    Most gas stations have residential units, only some have rooftops. I also work for a major gas station chain. Be prepared to do a lot of PMs.
  16. Replies
    9
    Views
    675

    You're missing potential airflow problems(you low...

    You're missing potential airflow problems(you low side pressures will be lower than usual) -plugged evap coil, dirty filter, undersized ducts or undersized filter area(coil and ducts could be...
  17. Replies
    42
    Views
    3,010

    I just got exact the same H10 brand new for...

    I just got exact the same H10 brand new for $404.50.
  18. Thread: Warm freezer

    by Frosty_VA
    Replies
    5
    Views
    721

    Door heater produce very small amount of heat,...

    Door heater produce very small amount of heat, with properly working system you should have -10F(-23C) anyway. The same thing with defrost elements - after defrost is over, compressor should be able...
  19. Thread: sman-4

    by Frosty_VA
    Replies
    4
    Views
    468

    Look for the same threads about digital gauges,...

    Look for the same threads about digital gauges, including SMAN3 and SMAN4, there're plenty on this forum. Search engine is your best friend.
  20. Replies
    49
    Views
    2,690

    He is full of it. 20k a year? 80k total? Go to...

    He is full of it. 20k a year? 80k total? Go to college or university for this kind of money, get an engineering degree. Did he tell you this 80k story just to get rid of you so to speak?, you know...
  21. Replies
    19
    Views
    1,483

    I have SMAN3, had to replace plastic...

    I have SMAN3, had to replace plastic handles(Fieldpice sent them for free), temp clamp snapped(probably my fault) and replaced only one set of batteries over 3 years of use. Tossed them inside the...
  22. Thread: hiring in dc

    by Frosty_VA
    Replies
    2
    Views
    506

    Qualified HVAC/R techs are in very high demand in...

    Qualified HVAC/R techs are in very high demand in DC area, however how much you can make depends on your licenses and certifications, your clean DL and background. EPA, NATE, Journeyman HVAC - you...
  23. Replies
    5
    Views
    798

    I knew a guy who worked in DDC and he got his...

    I knew a guy who worked in DDC and he got his journeyman HVAC lic in VA. So if you got 240 hours of training and 4 years of exp, go for it, fill out couple of forms, pay fee and send it all to DPOR...
  24. Replies
    32
    Views
    4,194

    http://www.amazon.com/Imperial-Eastman-Straight-Kw...

    http://www.amazon.com/Imperial-Eastman-Straight-Kwik-Coupler%C2%AE/dp/B008HQ2TOY/ref=sr_1_1?ie=UTF8&qid=1390877419&sr=8-1&keywords=Straight+Kwik-Coupler

    These will solve the problem. I love them!
  25. Replies
    31
    Views
    2,559

    Aahahahaha! Priceless!

    Aahahahaha! Priceless!
  26. Replies
    15
    Views
    1,991

    I think it would be a good idea to elaborate on...

    I think it would be a good idea to elaborate on classes you've had in the college and HVAC training. Also I would delete all non-hvac related jobs(I think most employers don't care). In my resume I...
  27. Replies
    6
    Views
    1,066

    What refrigerant? 315-195=120 psi differential...

    What refrigerant?
    315-195=120 psi differential is too high. As far as I remember for stable operation diff should be a about 40-50 psi. For R22 and R404a I get 190-230 danfoss encapsulated fan cycle...
  28. Replies
    16
    Views
    1,379

    we bid about 4-5 hrs usually

    we bid about 4-5 hrs usually
  29. I honestly don't understand this idea about...

    I honestly don't understand this idea about reversing condenser fan in the OFF cycle, in real life it does not blow dust away(maybe just a bit). Helps to evaporate condensate from the drain pan -...
  30. We do everything from residential HVAC units to...

    We do everything from residential HVAC units to rooftops, light comm refrigeration, ice makers, sometimes even coffee machines. I don't even remember last time when I had less than 50 hrs per week....
  31. Replies
    34
    Views
    4,172

    It was a bad pump, checked old one with my...

    It was a bad pump, checked old one with my gauge(finally got it!) and showed about 60psi max, no matter how i try to adjust pressure screw. Also after a test dropped almost all the way to 0(not a...
  32. Thread: Gages?

    by Frosty_VA
    Replies
    7
    Views
    592

    Fieldpiece SMAN3(or SMAN4). Have them about a 1.5...

    Fieldpiece SMAN3(or SMAN4). Have them about a 1.5 years, work like a clock, lots of good features and good customer support from fieldpiece.
  33. I'd get more insulation in the attic first.

    I'd get more insulation in the attic first.
  34. I'd check TXV screen, replace LLFD(gotta do it...

    I'd check TXV screen, replace LLFD(gotta do it anyway because you'll open the system) and check nozzle in the distributor.
  35. Replies
    4
    Views
    759

    First get M# of evap. As far as I remember, 1HP...

    First get M# of evap. As far as I remember, 1HP for medium temp 35F box/25F evap is about 8000btuhs(1HP for low temp with -10F/-20F evap is 4000Btuhs), so say if you have 12000 btuhs evap(see evap...
  36. Replies
    3
    Views
    426

    Company, type of work(commercial/residential,...

    Company, type of work(commercial/residential, refrigeration, controls), your knowledge and licenses, area you live in etc etc.
  37. Replies
    21
    Views
    2,612

    Man, being on call is just another opportunity to...

    Man, being on call is just another opportunity to get valuable experience. You just need couple phone numbers to call in case you don't know what to do. No big deal, think nothing of it. The less you...
  38. Replies
    21
    Views
    2,612

    If you have only 7mnth of experience and this job...

    If you have only 7mnth of experience and this job gives you something valuable every day, don't leave. You have very thin skin, that's too bad. Consider this job as a good way to "make your skin...
  39. Replies
    41
    Views
    4,706

    Forgot to say, I'd also buy diesel if possible....

    Forgot to say, I'd also buy diesel if possible. Have heard good things about chevy 6.0 and people say 7.3 ford diesel is pretty much bullet proof with proper maintenance.
    E250 or 350 I personally...
  40. Replies
    34
    Views
    4,172

    So true. I remember years ago in college my HVAC...

    So true. I remember years ago in college my HVAC teacher spent time talking about his deer hunting experience rather than giving us info on oil furnaces, classes that had to be 4hrs lasted only 1.5,...
  41. Replies
    41
    Views
    4,706

    Very neat and well organized truck, HVAC_ Marc.

    Very neat and well organized truck, HVAC_ Marc.
  42. Replies
    41
    Views
    4,706

    For HVAC service I'd buy extended Ford E350 or...

    For HVAC service I'd buy extended Ford E350 or maybe Chevy 3500, also extended. Ford would be #1 choice, Chevy #2 because I've been told they have good engines and not so good transmissions. Thought...
  43. Replies
    34
    Views
    4,172

    Ok, I didn't know that. Thank you guys for such...

    Ok, I didn't know that.
    Thank you guys for such a quick and informative response, I'll keep the thread updated.
  44. Replies
    34
    Views
    4,172

    on my way to supply house

    on my way to supply house
  45. Replies
    34
    Views
    4,172

    I got oil gauge but no hose, that's all I could...

    I got oil gauge but no hose, that's all I could get from local suppliers, oil is not very popular here in DC area. I'm trying to get all my oil tools. Slowly but steadily.
    Luckily it's not a house,...
  46. Replies
    34
    Views
    4,172

    Can't tell you the pump pressure, got no oil...

    Can't tell you the pump pressure, got no oil gauge at the moment.
    Air gate opened only about 1/16.
    What piece of carbon, on the electrode or?
  47. Replies
    34
    Views
    4,172

    Got 'no heat' call. - - - Updated - - - ...

    Got 'no heat' call.

    - - - Updated - - -

    Could pump be bad? Is it possible to have oil from the bleed port but nothing to nozzle?
  48. Replies
    34
    Views
    4,172

    Need help with Beckett AFG oil burner

    Hi guys, need your help with Beckett AFG series oil burner: thing don't want to light. New nozzle, new oil filter, new electrodes(properly adjusted). Cleaned pump screen with compressed air, checked...
  49. Thread: test leads

    by Frosty_VA
    Replies
    5
    Views
    725

    grainger

    grainger
  50. Replies
    1
    Views
    376

    200 sq in of filter area per ton, 1000 sq in for...

    200 sq in of filter area per ton, 1000 sq in for 5 ton, so 20x20 and 20x30 should do it. Most 5 ton system not even close to this.
Results 1 to 50 of 90