Search:

Type: Posts; User: buzzman

Page 1 of 2 1 2

Search: Search took 0.00 seconds.

  1. Replies
    5
    Views
    432

    nate, Did it work?

    nate,
    Did it work?
  2. Thread: Alerton

    by buzzman
    Replies
    1
    Views
    502

    Alerton

    Is there an Alerton dealer outside NY State that would be willing to sell parts to us.
  3. Replies
    14
    Views
    1,677

    RS-485

    Right-On Sam,
    If anyone should know it would definately be you.
    jb
  4. Replies
    43
    Views
    2,383

    Raging D-bags

    I'm not an ex-jci employee. We've had the line since late 2003,long before the fx line came out. I didn't say it was all bad programming,hand tools.
  5. Replies
    43
    Views
    2,383

    NAE Gone? NAH!!!

    My company is an independent and we have installed +-150 NAE/NCE's. There were more issues in the beginning than there are now and with software rev's coming out about every 6 months things have...
  6. Point Maps

    Chet,
    See if this helps with VMA's:(delete the occ command first and then archive before adding the new point)

    The steps shown below are used to define a Multiple Command Object to control the...
  7. Replies
    17
    Views
    1,395

    NAE Exposed

    Right click on the site object and scroll to the bottom of the page in advanced view and modify the BACnet Site to true. Change the encoding to ASCII and then right-click on the nae and archive wait...
  8. Replies
    16
    Views
    1,090

    What I should have said in the above post is...

    What I should have said in the above post is "when deleting anything in an NAE, be sure to archive before re-adding".
  9. Replies
    16
    Views
    1,090

    Lost points no more

    Delete the controller(then right-click on the NAE and archive)then re-add it with a slightly different identifier(AHU-1A instead of AHU-1). You then can add the resource file and map in the points.
    ...
  10. Thread: Daikin System

    by buzzman
    Replies
    0
    Views
    540

    Daikin System

    I have a Daikin Lon Integration Panel. I can get the Neuron ID by pinning the controller but can't seem to integrate it to my lon NAE. I noticed that the Echelon Chip has FT-X1 stamped on instead of...
  11. Replies
    3
    Views
    624

    I know how to do it with Alerton Software. I'm...

    I know how to do it with Alerton Software. I'm asking if there is any other software that allows renumbering. Thanks for all the input.
  12. Replies
    3
    Views
    624

    Alerton\McQuay Heatpump Board

    Does anyone know how to change the instance number on an Alerton VL-MQ-WSHP1? I don't want to use Alerton Utilities and would like to think that, like other vendors, the instance number are...
  13. Thread: JCI Bacnet

    by buzzman
    Replies
    5
    Views
    550

    When Bacnet is chosen (true) in an NAE, the...

    When Bacnet is chosen (true) in an NAE, the choices for encoding are ascii or unicode. When integrating this device to third party devices,(head ends) ascii must be chosen or only instance numbers...
  14. Thread: NAE and Java

    by buzzman
    Replies
    2
    Views
    470

    java stuff

    This NAE could be version 1.5.0_04,1.5.0_06,or 1.5.0_10. Start with the earliest version and work your way up. To really check your version go to a dos prompt and type >java -version.
  15. Replies
    11
    Views
    7,087

    Nce25

    Dwright23,do you have I/O on your NCx?
  16. Replies
    11
    Views
    7,087

    Nce25

    Easy there JCI Dork! Its called an NCE but at its core and when booted up through the NCT tool Gives its name as NAEXXXXXXXXXXXX. I originally tried to tie into my first NCE by using NCEXXXXXXXXXXX,...
  17. Replies
    11
    Views
    7,087

    NAE25 passwword

    As an added note, this is their newest product
  18. Replies
    11
    Views
    7,087

    NAE25 Password

    There is an NAE25. It is the NCE 25. It comes up as an NAE25 when viewed in NIC tool as NAEXXXXXXXXXXXX (Default Name and MAC Address). I'm assuming that you are trying to access it through Ethernet....
  19. Replies
    3
    Views
    1,215

    NAE IP Address

    You need to make sure you have an ethernet cable plugged in at the same tim during the reboot or you'll get all Zeros. If you have access to IP Tracker(a johnson utility) you could use that with an...
  20. Replies
    3
    Views
    1,014

    Andover Password

    I have an unresponsive dealer and engineer on a community college job that needs some attention. I have cyberstation+continum+plain english.
    I'm logged into the software but probably don't have a...
  21. Thread: Ncm/nae

    by buzzman
    Replies
    4
    Views
    749

    Ncm/nae

    I have a job that I'm changing the NCM out for an NAE. Its an NAE45 with 27 UNT controllers and 3 DX's. The owner wants a warm fuzzy before he switches over to the NAE. When we are there during the...
  22. Replies
    0
    Views
    530

    JCI NAE and BACNet

    I have a NAE-5521 Tied into a system with Alerton. I can see all the points and command them no problem. I'm trying to get the alarming to work in the NAE and notify the Alerton system. I was...
  23. Replies
    16
    Views
    1,297

    I wonder how long thats going to go on now that...

    I wonder how long thats going to go on now that carrier owns ALC and just purchased the 2 biggest ALC dealers in the country
  24. Replies
    66
    Views
    5,811

    Still seems to me that the line programmers are a...

    Still seems to me that the line programmers are a little reluctant to admit that they blew a good part of their 20's and 30's with line code. It's like the old HVAC Technician who says "You Don't...
  25. Replies
    66
    Views
    5,811

    For ANYONE who has used graphical programming, it...

    For ANYONE who has used graphical programming, it is known that a custom block has been created in most graphical programming languages to let the programmer create his own custom code (If you were...