Search:

Type: Posts; User: GregF

Page 1 of 6 1 2 3 4

Search: Search took 0.01 seconds.

  1. Thread: Solidyne

    by GregF
    Replies
    8
    Views
    1,850

    Drivet

    I have not used it my self but I know someone that has. Said it worked ok
  2. Thread: Solidyne

    by GregF
    Replies
    8
    Views
    1,850

    Solidyne

    Yes there is a driver for these things. You can call them and they will direct where to buy it.
    Greg
  3. Replies
    5
    Views
    417

    License

    Talon is OPEN. Any time you see a * in a license file it means it will take any thing.
  4. Replies
    3
    Views
    967

    Ilon

    Just use the LonIP Network.

    G
  5. Replies
    6
    Views
    1,104

    Raptor

    It depends on the version, but there is a Talon block that was used a lot. Howevere it has a bug in it. You could power it down but DO NOT DO THIS untill you change the battery to a new one. The Lon...
  6. Replies
    9
    Views
    1,732

    Boolean Switch

    Ha Steve
    There's not a strait up way to do what your looking to do. I use them alot and I'll send you on in the morning.

    Greg
  7. Replies
    30
    Views
    3,415

    Jace I/O

    Well I use them all the time. If you follow the rules its as solid as any thing else. Have a few Chiller Plants with no problem. Lots of Boilers and AHU's.

    G
  8. Replies
    6
    Views
    1,104

    Staefa

    Thats an older Talon Raptor. You would need the Raptor Block Programmer, and hope the debug file is in it.
    G
  9. Thread: Distech EC-GFX

    by GregF
    Replies
    12
    Views
    1,796

    gfx Tool

    opps told you wrong, I've always have a station running in th backround. I just checked it out and to have to have AX, Lonmaker, Lonwatcher or other tool running to.

    Greg
  10. Thread: Distech EC-GFX

    by GregF
    Replies
    12
    Views
    1,796

    GFX Tool

    All you need is the EC-gfx Programming Tool. Launch that and you don't have to use the AX.

    G
  11. Replies
    15
    Views
    1,758

    Ram Disk

    This is a Jace 7?? Are you using the JCI appliance? What do you have on the thing??

    Greg
  12. Replies
    15
    Views
    1,758

    Ram

    checkvalve

    What you are saying I mostly agree, however I was trying to point out how little memory we work with. If he has the flash disk space he could increase the ram disk. The other side is...
  13. Replies
    15
    Views
    1,758

    Ram Disk

    Clean up, I could not tell you without seeing the station. The % ram is set out of the box at 10%, you could lower tha to say 4 or 5 %. It will fix the problem for a short time and can fix it all...
  14. Replies
    15
    Views
    1,758

    Ram Disk

    Questionz
    Theres more to it than Histories and trends. The whole station loads up into ram disk, this saves flash disk writes. Now what ever you have on the Jace loads into ram disk, Operating...
  15. Thread: Java and Niagara

    by GregF
    Replies
    6
    Views
    1,371

    Java

    Good question, first its Tridium Niagara so it is the same.

    Second, if you are talking jar files or drivers it is Java, you just have to use Tridium imports.

    Third, Niagara AX has program...
  16. Replies
    28
    Views
    2,430

    T Box

    All that works and works well, It will route lon to. Twisted to Ip no problem.

    Greg
  17. Opps

    Sorry I just saw 275 devices, I would still do it. That would be about 70 devices a trunk.

    Greg
  18. Jace 7

    Shockwave
    A Jace 7 is about 4times a Jace 6, you are good for 150 devices.

    Greg
  19. Replies
    6
    Views
    994

    Bql

    hvac69
    The problem you are having is the slot is not exposed, now you could expose the slots but you have to open each point to do it.
    You might as well just do the conversion one at a time.

    Greg
  20. Points

    The super is a device under the NiagaraNetwork, hit the plus sign and double click the point folder, do a discover add points. Link points to the graphic.

    Greg
  21. Graphics

    Any points you want to display in on sup, bring in the points under the station under the niagaranetwork. Then like linking with the bacnet side you would link from the niagaranetwork.
    Greg
  22. Thread: Novar JACE Help!

    by GregF
    Replies
    4
    Views
    720

    Novar

    Well good luck getting Novar's jar files, they are tighter than TAC. If you can't get them check the tridium base license and if it has what you need delete the Novar one reboot and you should be...
  23. Niagara

    Ok now you have all three sup's on the network, all set 81, 1911, 3011 and yes you will have to put the 81 at the end to browse.

    Double click the Niagara Network and do a discover, now this is a...
  24. Log In

    Well I still don't get the 3 sup's but it is what it is. First forget the 80, each IP is its own. Think about your LAN, do you think thats how they do it??
    Now each sup has its own IP, done, they...
  25. Access

    You can't make this work and don't need to. If you change port 1911 the jace's will have to be changed, if you change the jace's the server will not be able to see them. Example Jace 1 port 1912,...
  26. Replies
    1
    Views
    646

    Codes

    I too had a direct line and have used the commands as you have, however it was years ago and I lost them.
    G
  27. Ports

    I don't see how you will be able to make this work or why you would want to. Keep in mind that 1911 is the Niagara port, that said, if you got this to work how would your Jace's talk to 1912 and...
  28. Replies
    23
    Views
    1,898

    jace

    As a router would no, however you can take data off one trunk and send it down another trunk or lon ip. you can take the data from one trunk and build the
    snvt's one the other and make the jace...
  29. Thread: MSTP vs FT10

    by GregF
    Replies
    112
    Views
    6,534

    BacNet

    crab
    I don't have BacNet's know how but I will put my 2 cents in. I will use an example , On an Alerton system if you want to pass OSAT from one controller to another controller you have to poll it...
  30. Thread: MSTP vs FT10

    by GregF
    Replies
    112
    Views
    6,534

    BacNet

    lonboy
    The Jace is not limited to 127 devices. The number is 508 devices, however good luck getting the disk space on a 6. A 7 would get a bunch more and a NXS might get them all.

    GregF
  31. Replies
    8
    Views
    1,572

    Arcnet

    Missing the shield.
    Greg
  32. Replies
    8
    Views
    1,572

    Arcnet

    Every time I have seen a ALC Arcnet it was 2 wire, I don't know how much of a problem this would be in ALC but it would be a big problem with any other MSTP installation.

    I agree with the LGR...
  33. Thread: Help Contents

    by GregF
    Replies
    5
    Views
    408

    Help

    Igotworms

    When you commission a Jace you get 3 options, runtime, ui+runtime and ui+runtime+docs. This installs the doc files onto the Jace. This is as close as it gets. Keep in mind that it...
  34. Replies
    42
    Views
    8,941

    Wizards

    After you have imported the program to the device and sent it to the device, you need to do a save project. This will add a directory under files call extensions, this is where the program is saved...
  35. Replies
    42
    Views
    8,941

    Wiz

    You have to have the embedded workbench or thats the error you get.
  36. Replies
    42
    Views
    8,941

    wizards

    You have to have a PC to get them there, after its installed it lives on the Jace. You can hit it with a browser with no Distech software. I will add that I'm talking about the programmable, have not...
  37. Replies
    42
    Views
    8,941

    Wizards

    Distech plug-ins live on the Jace.
  38. Thread: What it is?

    by GregF
    Replies
    13
    Views
    1,107

    What is this??

    Well thats the way I always do it, however I don't bother with the actuator.

    G
  39. Replies
    7
    Views
    666

    alarms

    It sounds like you have the alarms set up right. Do you have the server in the jace and the jace in the server??

    Greg
  40. Replies
    20
    Views
    1,486

    Metasys

    ICC makes a gateway that you can bring in lon or bacnet and spit out N2. I am taking a leap that its N2. Look at their stuff. I can tell you it not real costly and it works well.
    Greg
  41. Replies
    15
    Views
    1,577

    Lon

    Chris
    I looked at your screen shots and I want to ask if you in the control panel at lonworks interface to see what lon port it was using. Lon driver 3.4 doesn't seam to work on 64 bit Win 7, but I...
  42. Replies
    7
    Views
    1,926

    Talon

    You be right It is R2 Version 515. Still open kind of but there is R2 licensing things he will have to deal with.
    I agree it would be easier to upgrade to AX.

    G
  43. Replies
    7
    Views
    1,926

    Talon

    Its an open Tridium Niagara product. If you have a Web Server you have all you need to update graphics and schedules. If not, the system must be Jace's, if the installer bought an imbedded workbench...
  44. Replies
    56
    Views
    2,843

    LNS

    Ok so now we are being a little more reasonable. Although I have stated many times that I use what the project requires, Ilon, TBox, and Alerton, S7's, slc500's and anything else I can get my hands...
  45. Replies
    56
    Views
    2,843

    Hawking

    Soooo, I take it there is no such thing as a Flat Lon Contractor (Side Note: There is no such thing as a completely Flat Lon System) that hawks a few customers every now and again. Just you guys...
  46. Thread: Smart 2 on AX

    by GregF
    Replies
    2
    Views
    717

    Smart 2

    Many times. Its a lot better in AX, however you are going to need a Smart 2 license. You will have to get it from a Talon dealer or maybe Lynxspring.

    Greg
  47. Replies
    3
    Views
    834

    BACNet

    Yes, just have a BACNet server license and your good to go.

    Greg
  48. Thread: AX Lon Links

    by GregF
    Replies
    5
    Views
    562

    Links

    Yes, the link is in the network. Just like a link in Lonwatcher or Lonmaker. After you link the device to its self or device to device, bind turn off the jace and take it away if you want, it will...
  49. Replies
    4
    Views
    899

    SmartServer

    381engineer
    I think you'll find that you have to use java, a SmartServer comes with the software to do this.
    Greg
  50. Thread: LynxSpring Jace

    by GregF
    Replies
    3
    Views
    750

    lynxspring

    berg2666
    They are the only one besides Tridium that make the Jace. The Jace software is the same, however they have their own flavor of the workbench. No difference except Lynxspring has some added...
Results 1 to 50 of 258
Page 1 of 6 1 2 3 4