    All I never change a start cap without...

    All

    I never change a start cap without changing relay. I figure the relay sticking is the most likely culprit and callbacks are expensive

    Thanks

    Mike
  2. Replies
    4
    Views
    525

    You might check to see if that comp has a liquid...

    You might check to see if that comp has a liquid injection port. If so you could put a 190 valve on it. It's is a small Txv that measures discharge temp and dumps a small amount of liquid into the...
  3. Timebuilder, I agree with everything you...

    Timebuilder,

    I agree with everything you have said, however my point was .................... If you look at the -30 column (or any column for that mater) it shows a differrent BTU capacity...
  4. Replies
    23
    Views
    1,400

    Zuke As I said earlier "Something is wrong if...

    Zuke

    As I said earlier "Something is wrong if u have 35 SH @ comp and that much ice on comp. wrong freon??? Bad gauges? Plugged suct filter?? "

    I'm sure you are on the right track. Most...
  5. Replies
    26
    Views
    3,032

    It's about a 1 hp. Probably runs about 2 hrs/...

    It's about a 1 hp. Probably runs about 2 hrs/ day. It can't possibly cool tank below ambient ground , which in my area is 55.9. If you think about it, all heat I pull out goes back in through the...
  6. Thread: Cap tube

    by mikeweber3
    Replies
    7
    Views
    745

    zuke, 6 degrees superheat should be fine...

    zuke,

    6 degrees superheat should be fine after it is pulled down. If you had 6 with a hot box, you're probably overcharged now. I wouldn't worry about the 95, that's not uncommon in a hot...
  7. Replies
    26
    Views
    3,032

    It's not really about bio heat as much as simple...

    It's not really about bio heat as much as simple sensible. Most of the water down the drain is 75 degrees or higher which can get you over 3.0 COP
  8. Replies
    23
    Views
    1,400

    Where are u measuring duct press? Comp model#. ...

    Where are u measuring duct press? Comp model#. ?
    Enter & leaving air temp at evap?

    Do u know how to test to see what kind of freon?
  9. Replies
    23
    Views
    1,400

    Zuke Something is wrong if u have 35 SH @...

    Zuke

    Something is wrong if u have 35 SH @ comp and that much ice on comp. wrong freon??? Bad gauges? Plugged suct filter??
  10. Replies
    26
    Views
    3,032

    Septic tank heat reclaim

    About 2 years ago I built a new house. It is an all electric house and I'm trying to get the lowest energy footprint possible. I put a coil of 3/4 pex in my septic tank and circulate a closed loop...
  11. licen, This chart makes no sense. No...

    licen,

    This chart makes no sense. No matter what you call it if you have the same evaporating temp then you should have the same suction pressure. If you have the same suct press and same...
  12. Replies
    23
    Views
    1,400

    It is rare, but something that has kicked my but...

    It is rare, but something that has kicked my but a few times is a leak in the liquid to suction heat exchanger. I'm not sure I understand all of your symptoms. Could you re list them? Is your...
  13. Replies
    27
    Views
    2,108

    Golden rule. Always treat everyone as you wish...

    Golden rule. Always treat everyone as you wish to be treated. If they wrong you anyway that's their problem. If you live your life in a way that is pleasing to the LORD, you will blessed.

    I...
  14. Replies
    13
    Views
    762

    jets, If it's 3 phase, you could have a...

    jets,

    If it's 3 phase, you could have a contactor single phasing intermittently.

    Mike
  15. Replies
    17
    Views
    1,226

    You can also build a non condensable separator...

    You can also build a non condensable separator into the liquid line. Just tap off the top of the liquid line into a piece of larger tubing (say 1 5/8) 2' long. Put a pressure tap at the top of it....
  16. Bordini, If you would give a few more...

    Bordini,

    If you would give a few more details we would try to help. One that doesn't make sense is the 20 psi suction press with the unit off. How long had it been off? Does it have any...
  17. Replies
    13
    Views
    762

    Jets, you could have a condensor fan going...

    Jets,

    you could have a condensor fan going out, causing the comp to pull high amps when you are not there.
    Mike
  18. Replies
    11
    Views
    1,010

    Dodge and Garden.

    FCS
    No, I am not in RSES. I used to be when we had a local chapter here, but it folded about 25 years ago. We never have had ASHRAE.

    Tiger,
    Our business (www.weberorange.com) operates...
  19. Replies
    25
    Views
    6,410

    How many systems?

    Jab,

    I question the wisdom of using one system on a 3 story house. Are you putting in a zoning system?

    Mike
  20. Replies
    10
    Views
    3,739

    Texas hit it

    Mara,

    Texas hit it on the head. We are in South west Kansas where we have almost a perfect match for annual heat removal vs storage, however every job is different. What climate are you...
  21. Replies
    14
    Views
    5,731

    What do you want?

    Mara,

    I am not an engineer, but have designed, serviced, and installed many systems. I have done horizontal, vertical, open loop, closed, cooling tower, liquid cooler, and boiler assisted...
  22. Yes

    Back in the 1980s we used to install a lot of these. Yes, they do slow the air down some, but they gain enough by the lowered entering temp that the net gain is significant. I'd like to give you...
  23. Replies
    94
    Views
    4,650

    Dad a Grocer

    Hi,

    When I was a kid my dad was a small town grocery store owner. He was very handy, and could do everything for himself except Refrigeration. Whenever he had to call them he would get...
  24. Tell us more

    Henderson,

    Do you just want a percentage, or do you want annual cost of operation?
  25. Replies
    11
    Views
    1,010

    Can they answer part of my question?

    Is it OK just to ask for a brand, or model #?
Results 1 to 25 of 35
Page 1 of 2 1 2
Comfortech Show Promo Image

Related Forums

Plumbing Talks | Contractor Magazine
Forums | Electrical Construction & Maintenance (EC&M) Magazine
Comfortech365 Virtual Event