  1. If he is using RC-Studio 1.1 then they were...

    If he is using RC-Studio 1.1 then they were probably setup using Reliable's proprietary RCP protocol. To switch it to Bacnet you need RC-Toolkit and run the MSet program and configure each...
  2. Replies
    12
    Views
    1,544

    If it is a .mpb file then you have N30s and can...

    If it is a .mpb file then you have N30s and can open it using Project Builder. If it is an NCM you need to unddl the database and use Notepad like controlgeek said.
  3. Replies
    8
    Views
    562

    The MAC address identifies the device uniquely on...

    The MAC address identifies the device uniquely on that particular network segment or MSTP trunk. The Device instance identifies it uniquely across the entire Bacnet network which can include...
  4. Replies
    23
    Views
    1,470

    Reliable has the Mach Stat and Smart Space...

    Reliable has the Mach Stat and Smart Space Controller. Both Bacnet thermostat looking devices that are freely programmable with different I/O configurations. The SSC is the best bang for your buck...
  5. Propmanage, My company does alot of work both...

    Propmanage,
    My company does alot of work both install and service with JCI product. My email is in my profile if you are interested. We are located in Woburn.
  6. Replies
    9
    Views
    1,670

    Are you in edit mode? In RC-Studio I've noticed...

    Are you in edit mode? In RC-Studio I've noticed that it won't generally start polling info until you save the System Group.
  7. Replies
    5
    Views
    2,119

    Is therewith any issue with increased demand on...

    Is therewith any issue with increased demand on the controller you have cover subscriptions to? I.e. does a controller that is respond
    ing to cover point subscriptions work harderw than one that is...
  8. Replies
    5
    Views
    2,119

    Bacnet COV vs. Polling

    Does anybody have a preference between using COV subscriptions vs. polling for points using Bacnet protocol. I was always had the understanding that if a controller supported COV subscriptions then...
  9. Replies
    4
    Views
    618

    the device instance is set in the CCT program as...

    the device instance is set in the CCT program as part of the Define Hardware section.
  10. Replies
    12
    Views
    1,277

    tapatalk works with all v-bulletin based forums

    tapatalk works with all v-bulletin based forums
  11. Replies
    5
    Views
    1,188

    Th limit for the license is actually four so if...

    Th limit for the license is actually four so if you want five I suggest using a MSTP to IP router like the onefrom Contemporary Controls to bring that fifth port in using Bacnet/IP.
  12. Replies
    4
    Views
    931

    in CCT you can set the priority for the program...

    in CCT you can set the priority for the program to write to. It defaults to 16 (lowest) but I generally change it to 14 so that this doesn't happen. Then you can bring them in as writable and still...
  13. Replies
    29
    Views
    1,718

    They're defensive because we're all sick and...

    They're defensive because we're all sick and tired of how easy our job is - sitting on our a$$ staring at a computer screen all day. A new tech to a new site, anyone worth their salt would spend a...
  14. Replies
    27
    Views
    2,622

    That's like saying put a V8 in a Pinto and it...

    That's like saying put a V8 in a Pinto and it will drive like a Corvette.
  15. Replies
    27
    Views
    2,622

    Can someone elaborate on the details of this- I...

    Can someone elaborate on the details of this- I must have missed the beginning
  16. Thread: FX70

    by justjohnson
    Replies
    10
    Views
    1,827

    Any idea on release date and will this...

    Any idea on release date and will this incorporate JCI's jump to 3.5 and allow CCT passthrough?
  17. Replies
    1
    Views
    2,327

    APDU length max accepted

    Can someone better explain the APDU length max accepted parameter in Bacnet MSTP? I've got a mix of controllers on a trunk with some mitsubishi VFD drives and I'm having trouble with the drives...
  18. Replies
    37
    Views
    3,672

    make sure you don't do an autodiscover of the...

    make sure you don't do an autodiscover of the microtech IIs. They try and respond but it overloads them with all their points and then they just crap out and require the manual reset.
  19. Replies
    62
    Views
    8,708

    It might happen but I don't see JCI breaking the...

    It might happen but I don't see JCI breaking the deal with Distech completely. Without the LN/LX products they don't have a viable LON line. What are they going to go forward with the NexSys ESUSA...
  20. Replies
    9
    Views
    668

    did you use N2B points instead of N2Open points?

    did you use N2B points instead of N2Open points?
  21. Replies
    4
    Views
    801

    JCI is at it again

    http://www.duluthnewstribune.com/event/article/id/164839/

    Thought this was funny.
  22. Replies
    36
    Views
    5,449

    Generally B is positive and A is negative.

    Generally B is positive and A is negative.
  23. Replies
    40
    Views
    7,481

    yes

    yes
  24. Replies
    40
    Views
    7,481

    The add uses soap calls and web services to...

    The add uses soap calls and web services to communicate to the nae it does not use bacnet ip
  25. Replies
    40
    Views
    7,481

    Export the points via bacnet/IP into the nae. ...

    Export the points via bacnet/IP into the nae. Not that it's a good solution as the fx is far superior to the nae