Search:

Type: Posts; User: MDSkiffer

Page 1 of 2 1 2

Search: Search took 0.00 seconds.

  1. Thread: Cad Library

    by MDSkiffer
    Replies
    3
    Views
    412

    I'll check Kele out, thanks!!

    I'll check Kele out, thanks!!
  2. Replies
    5
    Views
    442

    I actually put one together today and was not...

    I actually put one together today and was not nearly as bad as I thought it was gonna be. I was completely drawing a blank on how to start it but once I realized the count up part of it, the rest...
  3. Replies
    5
    Views
    442

    Thanks for looking, if it turns up that would be...

    Thanks for looking, if it turns up that would be great!
  4. Replies
    5
    Views
    442

    Snippet for 3 pumps or boilers?

    I was hoping someone has a Distech Snippet they are willing to share that is for three pumps that have timed rotation and failover.
  5. Replies
    6
    Views
    529

    Hmmm, I'm gonna assume the Stafea lon jar is on...

    Hmmm, I'm gonna assume the Stafea lon jar is on the Jace, you discovered, matched and the program IDs match and then replace. Other than that, I can't think of anything else. I know that doesn't help...
  6. Replies
    6
    Views
    529

    If the program ID is the same, I cant see why it...

    If the program ID is the same, I cant see why it wouldn't work. I have a BCPlon trunk at my office with Talon, Distech and a couple others and the replace function works here on the Talon...
  7. That's a valid question and one I asked often....

    That's a valid question and one I asked often. The bottom line is, in the era of open systems, it's a sure way of keeping your foot in the door as a company. Unless of course the customer gets fed up...
  8. You will need the Unitron software with a dongle...

    You will need the Unitron software with a dongle and engineering tool 4 or 5, depending on what version it was created in. If these are stand alone, you will have little success without the original...
  9. Thread: Cad Library

    by MDSkiffer
    Replies
    3
    Views
    412

    Cad Library

    I was curious if anyone has stumbled onto a decent freeware type of site that offers the normal symbols we use? I'm thinking these are protected for the most part but thought it was worth a shot to...
  10. Replies
    16
    Views
    1,508

    If you don't mind, I'd like a copy as well....

    If you don't mind, I'd like a copy as well. Thanks in advance!
  11. Replies
    16
    Views
    1,483

    Tuning can take a lot of time, which is why I...

    Tuning can take a lot of time, which is why I maintain a spreadsheet with control manufacture, my control variable type, P&I as well as bias and ramp time. This information will give me a good...
  12. Replies
    32
    Views
    4,507

    I know the battery in the Smart Tool is 12VDC but...

    I know the battery in the Smart Tool is 12VDC but my coworker soldered a 9 volt battery connector and popped a simple 9volt battery in his Smart Tool and it actually worked! It's worth a shot or...
  13. Did you actually fix it such as a new tuning...

    Did you actually fix it such as a new tuning policy or create a workaround?
  14. Replies
    11
    Views
    1,112

    There is a hole that does leave the system...

    There is a hole that does leave the system vulnerable to where it can be hacked and access to the network can be gained. During the conference Rios and McCorkle successfully demonstrated that
    with a...
  15. Replies
    20
    Views
    3,753

    You can scale them down to your favorite 10...

    You can scale them down to your favorite 10 points to work around this but I agree, "junk" is my opinion also.
  16. Replies
    2
    Views
    899

    Check the obvious then, polarity, baud rate and...

    Check the obvious then, polarity, baud rate and connection integrity. Most of the time that is why it wont work when it did on the test bench.
  17. Replies
    20
    Views
    3,753

    The UC10s are compliant but to a point. You...

    The UC10s are compliant but to a point. You cannot add all their points on a jace with a normal sized trunk without getting timeouts. They claim it's a Tridium issue but they're the only ones having...
  18. Replies
    4
    Views
    374

    It could be anything, even the device it is...

    It could be anything, even the device it is connected to to make it go "Off Hook". Another thing to consider is that the connected user is hanging up correctly and does not leave the modem in the...
  19. Replies
    7
    Views
    600

    I also recommend XP with a true serial port, I've...

    I also recommend XP with a true serial port, I've had issues running it through my USB to Serial and Win 7 64 bit works but not consistently.
  20. Thread: Old Staefa

    by MDSkiffer
    Replies
    89
    Views
    11,548

    I'm not sure what you mean by third party but...

    I'm not sure what you mean by third party but I've used the Smart II driver quite a few times and cannot think of where there are integer only points. You do have to mind the 255 count limitation of...
  21. Replies
    6
    Views
    478

    You could learn them but to add them and see the...

    You could learn them but to add them and see the points on the Niagara side, that will require you to commission the device. As soon as you do this, it severs your LNS links. Maybe it can be done...
  22. Replies
    4
    Views
    761

    I've done a lot of these and you get everything...

    I've done a lot of these and you get everything from a control standpoint . The only draw back is that you have to install a TTL to RS485 converter for each trunk, the driver is expensive and you...
  23. Replies
    6
    Views
    498

    You can commission the Jace in any prior version...

    You can commission the Jace in any prior version except ver "0" without any problems. You can also keep that Jace at the latest version and pass Niagara Network info without any problem. The problem...
  24. Replies
    7
    Views
    511

    Sounds like the smoke is out. I'd call tech...

    Sounds like the smoke is out. I'd call tech support anyways just to see if there are any tricks to try and if you can get that guy replaced under warranty. I don't think they will take a return...
  25. Replies
    7
    Views
    511

    Distech tech support is top notch and the GFX...

    Distech tech support is top notch and the GFX programming is intuitive as it can get. I have been through their training class so that helped fill in some gray areas but think I would of eventually...
Results 1 to 25 of 32
Page 1 of 2 1 2
Comfortech Show Promo Image

Related Forums

Plumbing Talks | Contractor Magazine
Forums | Electrical Construction & Maintenance (EC&M) Magazine
Comfortech365 Virtual Event