Search:

Type: Posts; User: justatech

Search: Search took 0.00 seconds.

  1. Replies
    49
    Views
    3,042

    Nothing runs like a Trane but theres no wreck...

    Nothing runs like a Trane but theres no wreck like a Trane wreck!!


    I'm pretty good at making things cold---just ask my first two wives!!!
  2. Thread: Adding Oil

    by justatech
    Replies
    13
    Views
    2,291

    Etheric999

    I would assume that its a copeland semi. I would recommend you only add oil to the bottom of the site glass and after unit runs a day or two return and make sure you do not have to much oil...
  3. Replies
    11
    Views
    732

    Those that want to try

    Look me up on the site (hvac)

    And like some others it has been years for me to and some have already handed me my butt on a plate but what the hey I enjoy the game.

    As for time you are...
  4. Replies
    11
    Views
    732

    Your modesty is self control is noted!:)

    Your modesty is self control is noted!:)
  5. Replies
    11
    Views
    732

    Any Chess Players

    Found a decent chess site (gameknot.com) and find myself bouncing back and forth from here to there. Any takers?
  6. Replies
    12
    Views
    1,629

    I have only had limited experience with one unit...

    I have only had limited experience with one unit with this option. It works well in the midsouth as long as the ambient temp is at around 40 degrees or less. The units refrigerant charge is...
  7. Replies
    17
    Views
    5,848

    tlrsr

    You should have mail. :D
  8. Replies
    32
    Views
    3,228

    WJ now thats not fair from what I've read Twili's...

    WJ now thats not fair from what I've read Twili's got nothin on this guy.

    asqgd. you really should call a good service company. And I think some new gauges on you machine would be a good start.
  9. Replies
    17
    Views
    1,476

    Joint Compound

    Fast drying mud is NOT for rookies!!

    No offense intended. Try usiing basic 5 gallon buckets of premix mud. Stir the bucket to smooth the mud and use long even passes with the mud knives and let...
  10. Replies
    6
    Views
    1,240

    My dad showed us boys that when I was a kid. ...

    My dad showed us boys that when I was a kid. Steel rod and the hot wire of an extension cord wrapped around it and taped up. Stick in the ground and plug in. I never have forgotten watching those...
  11. Replies
    17
    Views
    5,848

    If your not in a hurry I'm pretty sure I can dig...

    If your not in a hurry I'm pretty sure I can dig some manuals out for you.
  12. Replies
    9
    Views
    756

    Sounds like you have got the bulk up. Try washing...

    Sounds like you have got the bulk up. Try washing area with Virginia 10 it's done a good job under a few RTAA's for me after cracked oil lines.
  13. Replies
    7
    Views
    981

    Unbalance

    Been dealing with a phase unbalance issue with a RTAA for two years. I had to set the controller to 30% to keep the chiller from tripping daily. Worst part was line with the lowest voltage has the...
  14. Thread: YT Parts

    by justatech
    Replies
    2
    Views
    734

    Tx

    I found the parts lists in my hard copy stacks.
  15. Thread: YT Parts

    by justatech
    Replies
    2
    Views
    734

    YT Parts

    Need the publication # for a YTC. Specifically the oil pump and sump parts.

    THIA
  16. Thread: Cvhe080

    by justatech
    Replies
    18
    Views
    1,825

    berg2666

    No,, if I was I would probably have the answers to problems I'm dealing with (or a least trying to) on another chiller now. Just passing on what i ran into. Hope no one reads anything more into a...
  17. Thread: Cvhe080

    by justatech
    Replies
    18
    Views
    1,825

    I'm with TXHVAC

    Had the same end problem with different root cuase on a YK this past spring. Control guru set condensor temp to 46 and oil so much oil ended up in condensor I was concerned about startup...
  18. Replies
    6
    Views
    677

    chillerguy2002

    Surname fits ne I guess because I'm just trying to be as good as I can without being something I'm not.

    I see and talk to alot of people who have a considerable amount of experience over me and I...
  19. Replies
    6
    Views
    677

    Optiview for YK

    I'm told this chiller experienced a brown-out and now the control panel has a case of gremlins bouncing around in it. Erratic readings from transducers, shutdowns for no apparent readings, history...
  20. Replies
    14
    Views
    1,525

    Just installed and started two 130 ton Mqcuay...

    Just installed and started two 130 ton Mqcuay Split systems. Discharge air temps on both being controlled by W7100's. We purchased the controllers through Mcquay but Kele Products also sells them....
  21. Replies
    5
    Views
    679

    80GUGU is correct. I did a short term as a...

    80GUGU is correct. I did a short term as a commercial carpenter prior to swapping to ac/r. Is 25years short term.
  22. Replies
    18
    Views
    1,972

    Have you removed the top cover of the contactor...

    Have you removed the top cover of the contactor and checked the shade rings on the coil. I have found several contactors an AA's where the laqcuer had come loose and the shade rings had come loose....
  23. Replies
    14
    Views
    1,639

    hey crooned if you read this let me apoligize....

    hey crooned

    if you read this let me apoligize. your original post led me to think incorrectly that you new and short cutting. Sorry hope no hard feelings.
  24. Replies
    14
    Views
    1,639

    I honestly dont want to sound negative but you...

    I honestly dont want to sound negative but you are supplying the answer your looking for. Hussmantech asks if you have a p.t. chart and a thermometer because basics are everything. Pickup a hvac...
  25. Replies
    28
    Views
    2,391

    non union and company supplies what we need to do...

    non union and company supplies what we need to do the work that makes money for the company and the techs. This is a quality company that since I have been here has proven to take care of its...
  26. Replies
    17
    Views
    1,394

    Just as you do not make electricity just a...

    Just as you do not make electricity just a potential pathway fo it to pass electrons we dont make air or areas cold we simply relocate heat. The refrigerant absorbs the heat from the air or other...
  27. Thread: Carrier 48TJ

    by justatech
    Replies
    20
    Views
    2,892

    Thats possible. Try lowering the heat settings on...

    Thats possible. Try lowering the heat settings on all three stats out of the cooling range and see if the heat quits running on the two youve seen running. That will save gas expenses and compressor...
  28. Replies
    5
    Views
    1,225

    I dont think the 48TJD028 has split type coils or...

    I dont think the 48TJD028 has split type coils or at least the ones I have serviced dont. I have had to take the screws out from both ends of the 6 or 7 inch panel above the coil and also remove...
  29. Replies
    7
    Views
    828

    anything in peticular. anything i have or can get...

    anything in peticular. anything i have or can get your welcome to
  30. Replies
    12
    Views
    1,994

    in the last several years have repaired at least...

    in the last several years have repaired at least a dozen 2o ton and up units with leaks at the discharge header to the condensor. all new to 2 years old. questioned local trane reps and was told...
  31. Replies
    10
    Views
    934

    consider myself lucky. work on everything from...

    consider myself lucky. work on everything from drinking fountains to 1000 tn centrifigals and mid size refrigeration. believe a constant diet of refrig would be hard to contend with without a...
  32. Replies
    37
    Views
    3,072

    consider 2 rubber tired hand trucks laid down and...

    consider 2 rubber tired hand trucks laid down and handles stapped together for a small unit
  33. Replies
    4
    Views
    3,379

    recently worked on a 30gx with the navigator hand...