    ClarkBP, Yep the report doesn't show much...

    ClarkBP,

    Yep the report doesn't show much wrong at that point. As a suggestion can you release the following points and then initialize the TEC? Then attached the 99 point report the next time...
  2. Replies
    9
    Views
    707

    What is the part number on the TEC 540-105 or...

    What is the part number on the TEC 540-105 or 540-105N. Makes a difference on how the setpoint dial and switch over works. Also can you attach the full TECs sub point report. 99 Points list
  3. Replies
    1
    Views
    334

    Can you drag that same point (TEC subpoint) to...

    Can you drag that same point (TEC subpoint) to Commander (not Global Commander)? If so then yes you can put it in plotter, it will only show historical if its trended and collected. If you can't open...
  4. Replies
    36
    Views
    7,871

    dbushwar, I tried the gdosbox on the Droid4...

    dbushwar,

    I tried the gdosbox on the Droid4 running 4.4 and was not able to get it to work. When accessing the config from the app it just keeps crashing. The user reviews for gdosbos on the play...
  5. Replies
    36
    Views
    7,871

    Good to hear its working. Thanks for the feedback

    Good to hear its working. Thanks for the feedback
  6. Replies
    36
    Views
    7,871

    ibehvacr, To test the airconsole and the...

    ibehvacr,

    To test the airconsole and the adosbox you can go old old school. There was a dos terminal emulation program called kermit the would run a VT100 emulator. Here is the link to the...
  7. Replies
    36
    Views
    7,871

    Sounds like they stripped the serial emulation...

    Sounds like they stripped the serial emulation out of gdosbox to speed it up. Try installing the adosbox from the directions.
  8. Replies
    36
    Views
    7,871

    Did you try the SerialBot app from the play store...

    Did you try the SerialBot app from the play store to see if everything else is working, AirConsole / MMI cable?

    https://play.google.com/store/apps/details?id=nz.co.cloudstore.serialbot

    Set it...
  9. Replies
    3
    Views
    646

    Did a blood testing lab that needed a second...

    Did a blood testing lab that needed a second signal into a system they called DCS. Looked like an old AB PLC system. We use a loop powered signal splitter...
  10. Replies
    6
    Views
    731

    The MBCs require different firmware to be able to...

    The MBCs require different firmware to be able to use the ethernet port. You can't "hot swap" between rs-485 and ethernet like the PXCs.
  11. I'd suggest making B02PC (node 0) the "main...

    I'd suggest making B02PC (node 0) the "main backup" in both system bln definitions and have the MAIN (node 95) as the "backup" in both system bln definitions. The reason for this setup is that the...
  12. Replies
    36
    Views
    7,871

    The WIFI & internet access can be solved if you...

    The WIFI & internet access can be solved if you have hotspot on your phone. Requires the Air Console be setup to connect to your phone WIFI instead of the way I wrote the directions.
  13. Replies
    36
    Views
    7,871

    Full Droid4 to TEC setup

    Here is the full Drod4 to TEC setup. Do not ask me for the CIS software!
  14. Replies
    36
    Views
    7,871

    Mine was here; ...

    Mine was here;

    /sdcard/app-data/org.hystuido.android.dosbox/.dosbox/dosbox-0.74.conf
  15. Replies
    7
    Views
    1,331

    martinsbt, You try any of the guys on this...

    martinsbt,

    You try any of the guys on this post?

    http://hvac-talk.com/vbb/showthread.php?183138-Signal-4-4-1-software/page2
  16. Replies
    3
    Views
    920

    CylonAmerican, Thanks for the info. I'm going...

    CylonAmerican,

    Thanks for the info. I'm going to try the IP controller "stuff data" into the BBC-SD and see how it works out.

    Merkas
  17. Replies
    3
    Views
    920

    AAM BBC-SD Display Bacnet/IP points?

    Was looking at the American Auto Matrix BBC-SD Bacnet display that is sold by Kele. I see that the display is a MS/TP device and by reading the manual can interact with BACnet points/devices on the...
  18. Replies
    1
    Views
    685

    Have you played with AutoHotKeys app. I posted...

    Have you played with AutoHotKeys app. I posted about using it for a Siemens kiosk awhile back

    http://hvac-talk.com/vbb/showthread.php?926502-Siemens-Apogee-PPCL-OIP-Command
  19. Replies
    3
    Views
    1,035

    The QFA3001.BU is a 3 wire device. (1) is DC+,...

    The QFA3001.BU is a 3 wire device. (1) is DC+, (2) is DC-, and (9) is RH 4-20mA or 0-10V
  20. Replies
    3
    Views
    1,035

    You can till order a 2 wire version. Its...

    You can till order a 2 wire version. Its QFA3001.WU-2W
  21. LonWorks RS-485 to Fiber - Fiber to RS-485?

    I'm not very versed with Lon so bear with me. We have a building with a Lon network (6 devices) and then a RS-485 to fiber going out to another location with a fiber to RS-485. This second building...
  22. Noticed you said you were setting up the page as...

    Noticed you said you were setting up the page as A4 can you change this to Letter and try again? Tried it as a test and the A4 does leave a lot of "White Space" were the Letter was not to bad.
  23. can you post an example, one of the live graphic...

    can you post an example, one of the live graphic and one of the print preview?
  24. If its on windows 7 use the snipping tool to do a...

    If its on windows 7 use the snipping tool to do a screen shot. May give you better results then the print function in graphics.
  25. Switch print layout to landscape before you...

    Switch print layout to landscape before you preview.
  26. Replies
    36
    Views
    7,871

    whart or bonzai . It was user configured

    whart or bonzai . It was user configured
  27. Replies
    36
    Views
    7,871

    Using this on a laptop or android phone? Setup...

    Using this on a laptop or android phone?
    Setup on phone was load aDosBox update config file. Load DOS CIS files onto phone. Connect to Air Console XL WiFi. Log into the web interface for the Air...
  28. Replies
    36
    Views
    7,871

    you can't use serial bot. Load aDosBox from...

    you can't use serial bot. Load aDosBox from Google Play. Add the config line to the aDosBox .cong file. Did you buy an Air Console XL device?
  29. Replies
    36
    Views
    7,871

    serial1=nullmodem server:192.168.10.1 port:2167...

    serial1=nullmodem server:192.168.10.1 port:2167 transparent:1
  30. Replies
    36
    Views
    7,871

    Itís not really a Siemens App but I've been able...

    Itís not really a Siemens App but I've been able to connect to a TEC with a Droid 4 phone. You have to load aDosBox and the old Siemens dos CIS software. Then use a WI-FI to serial device for the COM...
  31. Replies
    2
    Views
    723

    Try here for...

    Try here for manualhttps://www.hqs.sbt.siemens.com/gip/general/dlc/data/assets/us/APOGEE-Heat-Pump-Controller---Multi-Stage-Owner-s-Manual_A6V10308419_us-en.pdf
  32. Replies
    3
    Views
    1,197

    Well I figured I'd do a follow up. So I've...

    Well I figured I'd do a follow up. So I've managed to us the ICC xltr-1000 to pull the BACnet points from a Carrier 30MPW system (after the Carrier rep put in the CCN to BACnet card) and export them...
  33. Replies
    3
    Views
    1,197

    ICC xltr-1000 BACnet MSTP to FLN?

    Have a customer that wants to use an ICC xltr-1000 to bring a Carrier chiller BACnet MSTP points into a Siemens FLN. I looked over the manuals and it's kind of vague on the Siemens FLN side. Sounds...
  34. Thread: Siemens node

    by Merkas
    Replies
    10
    Views
    1,520

    Monitor "your own node" APOGEE Powers Process...

    Monitor "your own node"

    APOGEE Powers Process Control Language (PPCL) Userís Manual

    Syntax
    LINK
    Use
    This resident point indicates the condition of communications.
    Depending on the...
  35. Ok don't laugh too much at this. 1) Go into...

    Ok don't laugh too much at this.

    1) Go into report builder and create a new Trend Definition Report. Click the Add button and in the object selector window enter * as the point name and do a find...
  36. Replies
    8
    Views
    1,929

    357551

    357551
  37. Thread: Siemens

    by Merkas
    Replies
    7
    Views
    1,111

    I know, Just checking that gazoo knows that....

    I know, Just checking that gazoo knows that. Should be able to do it from the front end even if its never had telnet enabled before. I do it all the time.
  38. Thread: Siemens

    by Merkas
    Replies
    7
    Views
    1,111

    Is this PXCM on a PII hard wired trunk or on...

    Is this PXCM on a PII hard wired trunk or on ethernet?
  39. Thread: Siemens

    by Merkas
    Replies
    7
    Views
    1,111

    Is there an Insight front end? Go to system...

    Is there an Insight front end? Go to system profile and double click on the panel you want to enable telnet. Find the button "Terminal Definitions" a config window will open with a check box to...
  40. Replies
    15
    Views
    3,502

    "You all agree/disagree using two different...

    "You all agree/disagree using two different BACnet netowrk numbers on the same network is going to cause trouble like this?"

    Not sure? Anyone?

    Can you move you "BACnet/IP 47808" port to another...
  41. Thread: siemens uc ?

    by Merkas
    Replies
    8
    Views
    1,845

    Formulas for a 4-20mA input on a UC Slope = (V2...

    Formulas for a 4-20mA input on a UC
    Slope = (V2 - V1) / 2602
    Intercept = V1 - (Slope x 650)

    Sensor 0-65
    V1 = 0
    V2 = 65

    Slope = (65 - 0) / 2602
    Slope = 0.024981
  42. Thread: siemens uc ?

    by Merkas
    Replies
    8
    Views
    1,845

    From the Book table B-3; Range Slope ...

    From the Book table B-3;
    Range Slope Intercept
    0 - 100 0.038435 -25.0
  43. Replies
    5
    Views
    1,397

    Can you log into the panel from the HMI port and...

    Can you log into the panel from the HMI port and poll the rev string. Or from the front end in system profile. If it is a rev 3.0 , 3.1 , 3.2 your true BACnet. Anything in the 2.X range is P2.
  44. Replies
    5
    Views
    1,397

    If "Siemens panel that already has the BACnet...

    If "Siemens panel that already has the BACnet drivers" means it is a P2 controlled loaded with the BACnet MSTP driver then your out of luck. Siemens has to manually build the application and loaded...
  45. Thread: siemens uc ?

    by Merkas
    Replies
    8
    Views
    1,845

    There is no option for UC in point editor. Your...

    There is no option for UC in point editor. Your 1000 ohm RTD would have a slope of 0.1 and intercept of -40.0, not taking into account wire size or lenght.
  46. Thread: siemens uc ?

    by Merkas
    Replies
    8
    Views
    1,845

    Check out Appendix B. Slopes and Intercepts of...

    Check out Appendix B. Slopes and Intercepts of this manual
  47. Replies
    3
    Views
    904

    gazoo, You can change the slope and intercept...

    gazoo,

    You can change the slope and intercept for the UC from the edit points menu. See the attached. highlight the field and start typing your values in. There is no calculator built in for this....
  48. Replies
    2
    Views
    937

    Tsasso, try this; 00010 PT1 =(6.112 * 10...

    Tsasso,
    try this;

    00010 PT1 =(6.112 * 10 .ROOT. (1/(7.5 * DEGC /(237.7 + DEGC))) * HUM / 100)
    00020 HUMIDEX = DEGC + 5/9 * (PT1 - 10)

    To raise a number to the power of another you use the...
  49. Replies
    4
    Views
    778

    You need to delete the printer from System...

    You need to delete the printer from System Profile. Also there is an Insight Printer Service that needs to be disable and stopped. Once those are done you're all set.
  50. Replies
    1
    Views
    972

    Realy that simple. The virtual point doesn't even...

    Realy that simple. The virtual point doesn't even realy need to be created. IE:

    Panel 1
    Point: TEST1

    Panel 2
    Point: TEST2
    PPCL in panel 2 could be: IF ("TEST1" .EQ. ON) THEN ON("TEST2") ELSE...