  1. Replies
    15
    Views
    280

    Not an expert but the OA units I just worked with...

    Not an expert but the OA units I just worked with were two stage and the first stage had hot gas reheat with a variable DAT setpoint. The DAt setpoint and reset limit on ours was set with dip...
  2. Replies
    13
    Views
    544

    That x8160 is a pretty special board, not sure...

    That x8160 is a pretty special board, not sure I've even seen one, this an OEM board?

    You could pick up a x16160 ($1,725 on ebay) and drop it in with no changes. Or you could combine a x880 and a...
  3. Replies
    7
    Views
    259

    Is this legacy exec6 CMnet? If so then the LGE...

    Is this legacy exec6 CMnet? If so then the LGE needs to have the CEM driver loaded into it via direct connect before it will respond to CMnet/IP.

    If you need execB you might have a legacy...
  4. Replies
    1
    Views
    230

    Looks like a yes if you are referring to a Tracer...

    Looks like a yes if you are referring to a Tracer BCI-R ReliaTel in a Precedent, Voyager, or Odyssey.
  5. Replies
    9
    Views
    541

    The wheel might not care but the wipers should it...

    The wheel might not care but the wipers should it rubs against probably do.
  6. Replies
    6
    Views
    384

    Not really certain, again it depends on how they...

    Not really certain, again it depends on how they set up the SNMP agent in the device. I want to say Liebert did that. Hit up ireasoning.com and grab the MIB browser, there should be a way to walk a...
  7. Replies
    6
    Views
    384

    Well seems every SNMP device is a bit different...

    Well seems every SNMP device is a bit different but some of them do have status points that reflect the alarm conditions, I want to say the Liebert UPS have this. In that case it's the same as...
  8. Replies
    3
    Views
    460

    I've never done it but you are supposed to be...

    I've never done it but you are supposed to be able to do all the devices on a CMnet in one shot, assuming they are capable of execB. If you have a bunch that might be worth looking at.
  9. Replies
    6
    Views
    384

    SNMP alarms are traps that get sent from the UPS....

    SNMP alarms are traps that get sent from the UPS. Is the interface in the UPS set up to deliver traps to the Babel Buster device?
  10. Thread: MAC

    by MaxBurn
    Replies
    3
    Views
    215

    I have pushed ALC support a couple times for the...

    I have pushed ALC support a couple times for the ability to use WebCTRL on a Mac, I think it would make a good combination and alternate platform for servers and development. That's considering the...
  11. Replies
    5
    Views
    556

    Sometimes that's hard to get info, you need to...

    Sometimes that's hard to get info, you need to cultivate a contact in their IT group to help with things like that. If that doesn't work we have used our companies email server at some customers, but...
  12. Replies
    35
    Views
    2,564

    I'm not really a fan on needing the decoder ring...

    I'm not really a fan on needing the decoder ring to be able to read what they are saying and change settings on them. Not really friendly.
  13. Replies
    3
    Views
    204

    Advice from WebCTRL likely the same: Do the...

    Advice from WebCTRL likely the same: Do the latest cumulative patch, it contains all prior patches. If any patch was released after that cumulative you would have to apply that. In general you can't...
  14. Replies
    7
    Views
    458

    From what little I have seen I agree. Our senior...

    From what little I have seen I agree. Our senior integrator has poured a TON of time into these DBACS systems and it has not been a smooth road for our customers. We are also adding in a small point...
  15. Replies
    6
    Views
    599

    I don't work from scratch but I edit the heck out...

    I don't work from scratch but I edit the heck out of floorplan graphics with regular old mspaint as well, and use the floodfill and some random color for the color regions. Not sure how the pros do...
  16. Supervision works happily under windows 98 and...

    Supervision works happily under windows 98 and missing some features under windows XP, both which are EOL and shouldn't be allowed on a customer site. Also supervision was EOL something like eight...
  17. Replies
    6
    Views
    508

    You really need to know what you are doing and...

    You really need to know what you are doing and spend a decent amount of time if you want to manually handle BBMDs, which is great and all but SiteBuilder can do it for you. In this situation consider...
  18. Replies
    6
    Views
    508

    Could be you don't have bindings, hit the check...

    Could be you don't have bindings, hit the check bindings button on the driver page. If it doesn't say "alarms will be delivered" near the bottom than you don't have your BACnet bindings set up...
  19. Replies
    20
    Views
    748

    Sounds like 1800LIEBERT time.

    Sounds like 1800LIEBERT time.
  20. Thread: BBMD vs VPN

    by MaxBurn
    Replies
    43
    Views
    3,764

    This right here could save us some headaches with...

    This right here could save us some headaches with some customers fooling with their network all the time...
  21. Thread: BBMD vs VPN

    by MaxBurn
    Replies
    43
    Views
    3,764

    Cisco then sold Linksys to Belkin almost two...

    Cisco then sold Linksys to Belkin almost two years ago, another company I dont trust with the job. Who knows who is providing software updates for those now.
  22. Thread: BBMD vs VPN

    by MaxBurn
    Replies
    43
    Views
    3,764

    Excellent point, I've also been burned by cheap...

    Excellent point, I've also been burned by cheap consumer routers and I'll never get anything with the words Dlink or Linksys on them again. I'm thinking some of the better SOHO routers from the big...
  23. Thread: BBMD vs VPN

    by MaxBurn
    Replies
    43
    Views
    3,764

    That's an interesting comment on the speed...

    That's an interesting comment on the speed difference. I'm not sure why that might be.

    How are you all handling the tech training for these VPN devices deployment, repair and troubleshooting?
    ...
  24. Replies
    3
    Views
    444

    Planning the network layout for devices that need...

    Planning the network layout for devices that need to talk to each other is one that is starting to be an issue on some sites I've seen. Good mention kontrol.
  25. Replies
    20
    Views
    748

    I don't believe it is, all you are really doing...

    I don't believe it is, all you are really doing with he switches is changing the media type on the CMnet port. So if it's part of the same system that could be a concern. Can you download to the...
  26. Replies
    20
    Views
    748

    I guess the key question is does it still work on...

    I guess the key question is does it still work on ARCnet if you put it back? ;)

    Other random thoughts
    For MS/TP the other dip switches need to be left off. You don't want to wire to port A or...
  27. Replies
    20
    Views
    748

    Is this a SiteLink-12 2mb with no network port?...

    Is this a SiteLink-12 2mb with no network port? Or is it a SiteLink-12E with a network port?

    IF a SiteLink-12 2mb currently working on ARCnet you should be able to move the ARCnet/9600/38400 3 pin...
  28. Replies
    6
    Views
    526

    How difficult is it to get the right parts?

    How difficult is it to get the right parts?
  29. Replies
    32
    Views
    4,262

    Submit to wall of shame?

    Submit to wall of shame?
  30. Replies
    4
    Views
    899

    If I remember correctly to pull info out of the...

    If I remember correctly to pull info out of the SiteLink you want modbus function code 3 which results in a 4xxxx register request.

    I think the intellislot cards support both function code 3 and...
  31. Replies
    4
    Views
    374

    I've had some trouble with this driver in the...

    I've had some trouble with this driver in the past. Take a look at the network points page and pay attention to the count down timers to the next point refresh. See if they stick at zero, if they are...
  32. Replies
    16
    Views
    1,240

    Non union here and always been non union. I have...

    Non union here and always been non union. I have worked with union installers in the past and in general I thought they did a good job but it wasn't ever possible to be quick with them.

    One of my...
  33. Replies
    9
    Views
    707

    Some of the OEM's don't even download source...

    Some of the OEM's don't even download source files for the same reason.
  34. Replies
    5
    Views
    438

    RC642D is still available but I hesitate to...

    RC642D is still available but I hesitate to mention it because you need ALC tools to program it. There is some modes where they can be set up with dip switches but not sure how useful that is on...
  35. Replies
    5
    Views
    438

    I had a big problem with an OEM KMC FlexStat and...

    I had a big problem with an OEM KMC FlexStat and as such I wouldn't recommend it.
    We didn't get into programming the stat at all though, used it as Bard supplied. They would all start...
  36. Replies
    5
    Views
    438

    I had a big problem with an OEM KMC FlexStat and...

    I had a big problem with an OEM KMC FlexStat and as such I wouldn't recommend it.
    We didn't get into programming the stat at all though, used it as Bard supplied. They would all start...
  37. Replies
    3
    Views
    499

    On the LGR properties page there is a modstat...

    On the LGR properties page there is a modstat button, below that button there is a "show bindings" button. Hit that and give us the results here. If you don't have bindings you aren't going to be...
  38. Replies
    20
    Views
    1,274

    On the ALC WebCTRL side of things the batteries...

    On the ALC WebCTRL side of things the batteries on older modules seem to be good for 8+ years with the 2330 or 2325 button batteries. The newer modules with the CR123 can go quick if it sees a lot of...
  39. Bard OEM KMC BACnet stat and Dehumidification

    We have three wings of Bard units with OEM KMC stats all running on BACnet MS/TP. Just noticed a problem with their dehumidification sequence. Or a problem with my understanding on how to run it.
    ...
  40. Replies
    6
    Views
    392

    Good point, I forgot about that. Do you know what...

    Good point, I forgot about that. Do you know what linux distro they are using on that box?
  41. Replies
    6
    Views
    392

    This is for the black box server that i-Vu comes...

    This is for the black box server that i-Vu comes on right? Seems a little under specc'd to me, for WebCTRL I've been recommending a minimum of 4gb ever sense 7 shipped and a little before honestly....
  42. Replies
    17
    Views
    1,436

    Thank you, my email is in my profile here, just...

    Thank you, my email is in my profile here, just click on my name.
  43. Replies
    17
    Views
    1,436

    Nope.

    Nope.
  44. Replies
    17
    Views
    1,436

    Regarding the KMC flex stats does anyone have a...

    Regarding the KMC flex stats does anyone have a BACnet point list for them? Something with point descriptions?

    We worked from a discovery and seemed to get things working after adding a couple...
  45. Replies
    6
    Views
    494

    Is this for WebCTRL? ALC does tend to lag in...

    Is this for WebCTRL? ALC does tend to lag in getting a patch out after finding some new java update breaks something for 5.5 and lower.

    Your dealers service dept should be able to send you the...
  46. Replies
    6
    Views
    494

    Constant annoyance, I'm so glad we don't need...

    Constant annoyance, I'm so glad we don't need java anymore with the latest version.
  47. Replies
    29
    Views
    1,986

    I have a couple of these, one for the laptop and...

    I have a couple of these, one for the laptop and one for me. They fit in my backpack. About $9.

    http://www.dickssportinggoods.com/graphics/product_images/pDSP1-10886923p275w.jpg

    I must admit...
  48. Replies
    3
    Views
    459

    That driver suggests that you are looking at an...

    That driver suggests that you are looking at an integration already, to a Dataguard system. You will likely find something between 200 and 1000 points of integration under that LGR. The points in the...
  49. Sounds like you need a local account added to...

    Sounds like you need a local account added to that computer so you can login to it with no network access. If it's normal for it to not have network access than that's not really optional.
  50. Replies
    3
    Views
    369

    Depending on what version of software the LGE was...

    Depending on what version of software the LGE was used under there are two different ways to put the IP in.

    If it is "legacy" exec 6 it needs to be programmed with supervision or webctrl as a...
Results 1 to 50 of 676