  1. Replies
    3
    Views
    361

    You can NOT discover the points out of the...

    You can NOT discover the points out of the controller you need the PRN files from Hvac Pro or GX9100...
  2. What part of it is not working for you it is a...

    What part of it is not working for you it is a bacnet mstp device and BTL listed.
  3. Replies
    2
    Views
    256

    Enable the IP port under the Barnet network so it...

    Enable the IP port under the Barnet network so it will route the points out and allow them to be discovered
  4. Replies
    8
    Views
    359

    You probably have a mstp trunk issue. Can you...

    You probably have a mstp trunk issue. Can you scan the trunk?
  5. Replies
    12
    Views
    789

    Dont beat yourself up. Evryone here started at...

    Dont beat yourself up. Evryone here started at the beginning at one time or another and needed some help. Experience Experience Experience......
  6. Replies
    23
    Views
    1,166

    Tha is 95 percent of the infoormation needed to...

    Tha is 95 percent of the infoormation needed to contact a supplier. Where are you and what HVAC suppliers are around you ...
  7. Replies
    23
    Views
    1,166

    But I see you have six schools with Facilitator...

    But I see you have six schools with Facilitator front end in place, so you have 1 N2 trunks with less than 50 devices under each. Make a list of each trunk and types of n2 devices under that trunk....
  8. Replies
    23
    Views
    1,166

    JCI FX also now comes licensed for MSTP out of...

    JCI FX also now comes licensed for MSTP out of the box. You will discuss the diferrent licenses needed with who ever yu get it from as they will have to license every option and therefore dicuss...
  9. Replies
    23
    Views
    1,166

    Each jace you buy will require a license to be...

    Each jace you buy will require a license to be purchased for each of them individually, no matter if you buy them one at a time or all at one time. They do come with a station right out of the...
  10. Replies
    11
    Views
    1,180

    I was under the impression each manufacturer...

    I was under the impression each manufacturer provides a baseline K Factor for there boxes and then the TAB crew adjusts this after they actually dothe TAB on the boxes. Nothing magic there......
  11. Replies
    1
    Views
    186

    Yes were is it you are connecting t them...

    Yes were is it you are connecting t them from. Check your IP service at your house/office. That is the common link here, probably VPN issues........
  12. Replies
    13
    Views
    790

    Do you still have any of the MI files available,...

    Do you still have any of the MI files available, such as the NET ,GLOBAL, or NC files? Is the PMI OWS still online?
  13. Replies
    13
    Views
    790

    You can try to auto doscover them but I can not...

    You can try to auto doscover them but I can not tell you that 100 percent for sure as I have personnaly not done a N2 Jace gig yet...
  14. Replies
    13
    Views
    790

    You need the same N2 poins out f the MIG that are...

    You need the same N2 poins out f the MIG that are located in the NCM. Get the Net, Global and NC files from the drive of the PMIOWS.
  15. Replies
    5
    Views
    538

    I have all the needed java files on my laptop and...

    I have all the needed java files on my laptop and have no problem at all interafcing into a NAE or a Jace of any brand. Clear your Java cache in the Java control panel.
  16. Why would N2 be listed on the BTL website???????

    Why would N2 be listed on the BTL website???????
  17. Thread: NAE Query

    by berg2666
    Replies
    12
    Views
    520

    Cluck over the trunk then click the global search...

    Cluck over the trunk then click the global search button...This will allow you to search the entire trunk. If you were clciked on a specific cntroller when you enetered the global search it only...
  18. Replies
    16
    Views
    1,667

    You can upload a NAE that is at a lower revision...

    You can upload a NAE that is at a lower revision then your SCT but when you upload it it will be at the revision of your SCT........
  19. Tuning policies check the max write time and...

    Tuning policies check the max write time and see what it is then wait for that time and see if the read value comes back in that time
  20. Replies
    10
    Views
    837

    If you have it prior 4.1, you can download 4.11...

    If you have it prior 4.1, you can download 4.11 or higher , it will license and mske the necessary changes...
  21. Replies
    157
    Views
    27,169

    Shoot a copy my way also Thanks

    Shoot a copy my way also Thanks
  22. Replies
    157
    Views
    27,169

    Can I get a copy of this program also? email in...

    Can I get a copy of this program also? email in profile.
    THANKS
  23. Replies
    1
    Views
    333

    Most N2 devices are self terminating. I...

    Most N2 devices are self terminating. I would go find where they cut the wire and make sure there is no wires shorted together.
  24. Replies
    14
    Views
    768

    Check the focus tabs of the NAE and they will...

    Check the focus tabs of the NAE and they will tell you the last time they rebooted.
  25. Replies
    14
    Views
    768

    Is it happening at midnight?

    Is it happening at midnight?