Search:

Type: Posts; User: Dynawiderider

Page 1 of 2 1 2

Search: Search took 0.00 seconds.

  1. Replies
    7
    Views
    1,132

    Hmmm.... I need to check that...

    Hmmm.... I need to check that...
  2. Replies
    7
    Views
    1,132

    FX Supervisor VERY slow

    Any help is appreaciated. I have a AX server running 3.6. It is the JCI version. It is painfully slow for the web appliance AND workbench loaded directly on the machine. The OS is win 7 64 bit with 4...
  3. Branch Purchace Package.. LCT? For an NAE or do...

    Branch Purchace Package.. LCT? For an NAE or do you mean LCP the older predated DX Controller
  4. Replies
    7
    Views
    1,295

    Thanks mikeSands02, I thought R2 was different...

    Thanks mikeSands02, I thought R2 was different but I did not realize how different. Do you know of a good way to intergrate this JACE into a JCI FX60 Platform? I have a 60 in place doing another part...
  5. Replies
    14
    Views
    1,189

    Couple of things... 1st Look in the BO object in...

    Couple of things... 1st Look in the BO object in the UNT itself to see if you have the min on/off times and interstage delays set up this will help with cycling. Is your cooling command going up and...
  6. Replies
    7
    Views
    1,295

    TAC Jace and a BellyUp Contractor

    Hopefully someone can help! I have an older TAC UNC jace that a contractor installed in '06. I have inherited this site due to the contractor going under. I have a back-up copy of the database but it...
  7. IF you replace a NAE the ADX needs to re verify...

    IF you replace a NAE the ADX needs to re verify the engine. If the MAC address has changed then the engine is not verified as the one the ADX had originally and it will be unable to make those types...
  8. Why can't I Override a numeric writable object in niagara

    Does anyone know how to override and release a numeric writable object in niagara. I want to override a vortex damper at night and release it to local control during the occ period. It appears that...
  9. Replies
    1
    Views
    355

    Niagara says NULL

    Does anyone know how to have the e-mail service in AX put a header on
    the mail? When my customer get his mail it just says "null" in the sender space
    Any Ideas?
  10. Replies
    1
    Views
    328

    FX40 Flash to factory defaults

    Can anyone tell me how to Flash a FX40 back to factory defaults. I am having connection
    problems and would like to start fresh.
  11. Replies
    7
    Views
    669

    Yes Set the command to say release with a...

    Yes Set the command to say release with a prioirty of 14 not release all
  12. Replies
    1
    Views
    327

    Yes. Generate a n2 protocol for builder and use...

    Yes. Generate a n2 protocol for builder and use this as a point mapping guide. Map objects in the same way as you would any ASC Becareful of how you map due to override restrictions
  13. Scheduling in niagara with different systems

    Help! I have a FX Server with 3 different systems and I am trying to schedule all of them from 1 place. I have a Tridium Jace with a andover driver 2 honeywell jaces and a JCI
    fx20. I can discover...
  14. Replies
    12
    Views
    982

    OK I have seen this and have done it myself but...

    OK I have seen this and have done it myself but it has been years ago.

    JCI uses a database that can be opened in excel and modified to use a unt program in a vav controller. Is this your code or...
  15. I am using a AX Serial connection. Works but is...

    I am using a AX Serial connection. Works but is VERY slow to update and for that matter slow to do anything! If you have other alternatives try them if the speed is OK. But if you can live with the...
  16. Thank you Freddy-b That turned the trick. Do you...

    Thank you Freddy-b
    That turned the trick. Do you know why this one is this way and not the others? I did not have to do this when I discovered any of the other systems points.
  17. Unable to Command points in the continuim thru niagara

    Hello all,
    I am trying to be able to change setpoints in a Andover continuim system thru an JACE
    but the actions view is greyed out I have no problems for the honeywell JACE and the JCI JACE but...
  18. Replies
    6
    Views
    815

    Thank you for your reply. This has gotten very...

    Thank you for your reply.
    This has gotten very frustrating. I will try this 1st thing tomorrow. Any other suggestions?
  19. Replies
    6
    Views
    815

    I am not sure I understand. When I add a value to...

    I am not sure I understand. When I add a value to the 1st pane it shows up in all the others
    I keep looking for a way to only have it show up once and then in the other panes have something else
  20. Replies
    6
    Views
    815

    Tabbed Pane in Niagara

    Can anyone help please. I am new to niagara and I am having an issue with a tabbed pane.
    It seems that I cant keep the value in the 1st pane from "bleeding" through to the rest of the tabs. I am...
  21. Don't bother using the cable-pro if you dont need...

    Don't bother using the cable-pro if you dont need it. Go to blackbox.com and find a device called edgeport-1 made by digi. Then get a rs-232 to 485 converter. balck box also sells them.

    the only...
  22. If the password is lost you will have to send it...

    If the password is lost you will have to send it back or replace it. If you do rewrite the code
    then after you save it go under File/write user names and give it a name. What this will do is...
  23. Replies
    12
    Views
    833

    RS232 Converter

    Use the RS-232 to 485 converter from black box it is cheaper the the cablepro. we have been using it for years. you can use it with the onboard serial port or the usb to serial connection. Use the...
  24. Replies
    7
    Views
    735

    DMO to DDL

    Hello,
    I have a dmo to ddl converter that gets rid of all unused/not wanted objects in the file so that the commisioning tool will show you everything. contact me and I will send you a copy.
    It...
  25. Replies
    4
    Views
    474

    O.K.... Are they physical cards? How about...

    O.K....

    Are they physical cards? How about binary inputs. Are the sst card a dual BI/BO card?
Results 1 to 25 of 35
Page 1 of 2 1 2
Comfortech Show Promo Image

Related Forums

Plumbing Talks | Contractor Magazine
Forums | Electrical Construction & Maintenance (EC&M) Magazine