Search:

Type: Posts; User: lwarren

Page 1 of 20 1 2 3 4

Search: Search took 0.05 seconds.

  1. Replies
    3
    Views
    1,152

    Try subtracting 128 from any alarm value that is...

    Try subtracting 128 from any alarm value that is over 128 and use that value.
  2. Replies
    2
    Views
    187

    You should be able to accomplish this easily...

    You should be able to accomplish this easily through the Alarm Instructions Manager. Just right click on the alarm service and select the alarm instructions manager view.
  3. Replies
    13
    Views
    427

    Yes.

    Yes.
  4. Replies
    13
    Views
    427

    No, in this example the DO will the have a value...

    No, in this example the DO will the have a value of 1 when the X input of the select is 0=Ocupied, 2=Bypass or 3=Standby. The DO will have a 0 input when the X input is 1=Unoccupied. The Bacnet Venom...
  5. Replies
    13
    Views
    427

    If you are actually using the share object from...

    If you are actually using the share object from another controller then link from the niShare_EffOcc to the X slot of the select.
  6. Replies
    13
    Views
    427

    Something like this. 663811

    Something like this.

    663811
  7. Replies
    13
    Views
    427

    That will only work if you are using the nviShare...

    That will only work if you are using the nviShare in that controller. IE, linked from another controllers nvoShare. Also the occupancy value is going to be a logical 0 for a lon occupancy point, so...
  8. Replies
    1
    Views
    222

    I put one in at our Corporate office a few years...

    I put one in at our Corporate office a few years ago for access control and HVAC. The biggest problem is that they arent updating the versions like they do regular jaces. I just installed one about a...
  9. Replies
    10
    Views
    1,431

    You need to discover Jace 1 in the niagara...

    You need to discover Jace 1 in the niagara network of your other jaces and then bring the OAT into the other jaces from Jace 1.
  10. Replies
    2
    Views
    271

    Just use the program service displayName = "point...

    Just use the program service displayName = "point name" then use the edit slot flags option.
  11. Replies
    12
    Views
    659

    If the XL50's are Lon you are going to have a...

    If the XL50's are Lon you are going to have a problem because the points have to made as Lon points to be exposed in the XL50 with the Honeywell CARE software.
  12. Replies
    9
    Views
    434

    Thanks. It was an awesome night and year. 16 and...

    Thanks. It was an awesome night and year. 16 and 0 in only their second year of UIL.
  13. Replies
    9
    Views
    434

    My son made Fox Sports Play of the year!

    Got to give a shout out to my son for making Fox Sports play of the year and ESPN Sportscenters Top 10 with the number 3 play with his TD run in their State Championship game at NRG Stadium in...
  14. Replies
    18
    Views
    877

    If this is a VAV unit then you should probably be...

    If this is a VAV unit then you should probably be writing to nviDACLSP.
  15. I don't think it was comm port settings I had to...

    I don't think it was comm port settings I had to change in the Continum software. It has been over a year since I did this, I should have made notes. I spent several days messing around with stuff in...
  16. I believe the pinout is correct. I don't remember...

    I believe the pinout is correct. I don't remember exactly what I did, but I had to get something setup right in the Andover Continuum software before my communications would work.
  17. Your APDU timeout settings should match for all...

    Your APDU timeout settings should match for all of your devices on the network. I think the default APDU setting on the jace is 3000 milliseconds by default.
  18. I have integrated many of these over the years...

    I have integrated many of these over the years with AX via Lon and BACnet without very many problems. Don't wast your time with AAon, call Orion Controls tech support www.orioncontrols.com as that is...
  19. Per Amigo's suggestion If you are not familiar...

    Per Amigo's suggestion If you are not familiar with this, right click on the LonNetwork and select the Lon Utilities Manager. In the Command dropdown select Reports. In the SubCommand dropdown you...
  20. Replies
    5
    Views
    895

    It's been awhile, but if I remember correctly the...

    It's been awhile, but if I remember correctly the Copeland digital scroll controller takes a 0-5 VDC signal and has to have at least 1.2 VDC for the compressor to run. So, if I remember correctly if...
  21. They should have discovered if they were truly on...

    They should have discovered if they were truly on the same domain. Niagara default domain is 0 Length. I believe the XL10's came from the factory with a domain length of 1 and domain id of 2C
  22. Replies
    6
    Views
    789

    Rip that piece of crap out and just bring the...

    Rip that piece of crap out and just bring the stuff in via modbus. You wont have anymore problems.
  23. Replies
    7
    Views
    807

    Always a good idea to check the software manager...

    Always a good idea to check the software manager on a Jace before making any changes. Glad you got it worked out. Make sure you have the latest consolidated patches for 3.8 as well.
  24. Replies
    7
    Views
    807

    Are you sure the workbench you are connecting to...

    Are you sure the workbench you are connecting to the Jace with has the same version modules? I would verify with the software manager.
  25. Replies
    7
    Views
    807

    Sounds like something got corrupt. I would save...

    Sounds like something got corrupt. I would save the logic to the Spyder Library. Add a new spyder to the network. Delete the nueron from the current spyder. Discover, and match to the new blank...
  26. Replies
    5
    Views
    973

    If you are using Lonworks jar 3.7.106.3 I would...

    If you are using Lonworks jar 3.7.106.3 I would go to spyder tool 3.8.38.6.1.1 and get the latest consolidated patches for 3.7. Before you install the consolidated patches stop the platform daemon.
  27. Replies
    5
    Views
    973

    What version of AX and spyder tools are you using?

    What version of AX and spyder tools are you using?
  28. Thread: tabbed pane

    by lwarren
    Replies
    7
    Views
    460

    I would look at the document klrogers mentions...

    I would look at the document klrogers mentions and first get the structure of your px file correct. I have seen issues in versions prior to 3.8 if the canvas scale was set to fit ratio like the...
  29. Thread: tabbed pane

    by lwarren
    Replies
    7
    Views
    460

    Not the root pane. Is your tabbed pane not inside...

    Not the root pane. Is your tabbed pane not inside a canvas pane?
  30. Replies
    11
    Views
    1,161

    Fixing to do one of these myself. I have been...

    Fixing to do one of these myself. I have been waiting for a month to get an integration manual from Trane. Can't find it online. If you guys have one I would appreciate it if you could send it to me....
  31. Thread: tabbed pane

    by lwarren
    Replies
    7
    Views
    460

    Do you by chance have the Canvas Pane Scale set...

    Do you by chance have the Canvas Pane Scale set to Fit Ratio?
  32. Replies
    3
    Views
    587

    http://bassg.com/ This is what I use most of the...

    http://bassg.com/ This is what I use most of the time.
  33. Replies
    9
    Views
    1,726

    Email is in my profile.

    Email is in my profile.
  34. Replies
    10
    Views
    2,049

    They are from BAS graphics

    They are from BAS graphics
  35. Replies
    10
    Views
    2,049

    I did these for our demo site with regular px...

    I did these for our demo site with regular px pages except for the schedule and trend page. I used the mobile app service for them.
  36. Replies
    9
    Views
    1,726

    [QUOTE=kontrolthis;20126591]That would be great...

    [QUOTE=kontrolthis;20126591]That would be great if you don't mind. Email is in my profile.

    You got mail.
  37. Replies
    9
    Views
    1,726

    Once I figured out all of the registers it was no...

    Once I figured out all of the registers it was no problem. Have not had one problem with those units since I got rid of those gateways almost 2 years ago. I can send you a config.bog if you are using...
  38. Replies
    9
    Views
    1,726

    I worked on some of these a few years ago that...

    I worked on some of these a few years ago that were giving alarm numbers that were not on the simplicity point map. I can't find the email correspondence that I had with JCI but they had to talk to...
  39. Replies
    19
    Views
    2,405

    So that is the only enumerated value that will...

    So that is the only enumerated value that will show up? I guess the notification class is not what I was thinking it was. I was thinking each class would display multiple enumerations and each...
  40. Replies
    19
    Views
    2,405

    I was assuming it like some McQuay units I had...

    I was assuming it like some McQuay units I had done before. There was a point list for each notification class that gave specific info on what each ordinal was for the enumeration.
  41. Replies
    19
    Views
    2,405

    Well I finally got the integration manual, but it...

    Well I finally got the integration manual, but it does not list the info for the enumerated values in the Critical, Warning and Information notification classes. Would anyone have this info?
  42. Replies
    19
    Views
    2,405

    The units are already on the job site and that is...

    The units are already on the job site and that is what is in them. I just need the integration manual.
  43. Replies
    19
    Views
    2,405

    I am in need of the UC400 integration guide for...

    I am in need of the UC400 integration guide for WSHP's if someone can send it to me. Thanks in advance.
  44. Replies
    8
    Views
    705

    on the Honeywell Buildings Forum.

    on the Honeywell Buildings Forum.
  45. Replies
    3
    Views
    1,015

    This should be in the controls forum. The Image...

    This should be in the controls forum. The Image may need to be restored in the jace.

    P.S. I would edit your post and remove that external IP address.
  46. Someone will have to contact Tridium Licensing...

    Someone will have to contact Tridium Licensing and order the appropriate BACnet driver.
  47. No, you need to look at the Webs License

    No, you need to look at the Webs License
  48. Go to your license manager in the jace, open the...

    Go to your license manager in the jace, open the license file and make sure it lists Bacnet.
  49. Replies
    22
    Views
    4,233

    Indeed it has been James. I hope all is well with...

    Indeed it has been James. I hope all is well with you.
  50. Replies
    22
    Views
    4,233

    I had the Bobs tools a long time ago but lost it....

    I had the Bobs tools a long time ago but lost it. I would like to have it again as well if anyone could share it.